background image

Maintenance |

9

3.3.3

Checking the fans

Even if the required maintenance, such as change of filters is carried out, dust and grease may slowly build up inside
the fans. This will reduce the efficiency.

The fans are easily taken out from the unit by loosening the 2 bolts (pos 1) on the rail (pos 2) and disconnecting the fast
couplings to the electric wires. Depending on the accessories installed, remove the tubing next to the fast couplings for
the extract air fan or both the extract air fan and supply air fan.

Clean the fans with a cloth or a soft brush with a recommended interval of once per year. Do not use water. White spirit
can be used to remove obstinate settlements. Allow drying properly before remounting.

3.3.4

Checking the hot water heating battery

After long periods of operation (usually several years) dust may have deposited on the surface of the battery. This may
reduce batteries capacity. The battery can be cleaned with a pressure washer with misting jets, or with compressed air.
Cleaning should be carried out carefully so as not to damage the batteries aluminium fins. Once a year the battery
water circuit needs to be vented to maintain the batteries capacity.

3.3.5

Checking the electrical heating battery

After long period of time dust and pollutants can build up on the heating rods. This can cause unpleasant odors and in
the worst case fire. Clean with compressed air, vacuum or brush. The automatic safety function needs to be tested and
verified.

3.3.6

Cleaning the extract louvres and inlet diffusers

The system supplies treated outdoor air to the building and extracts the used indoor air via the duct system and diffus-
ers/louvres. Diffusers and louvres are mounted in ceilings/walls in bedroom, living room, wet rooms, WC etc. Remove
diffusers and louvres and wash in hot soapy water if required. Diffusers/ louvres must be put back with their original
settings and positions in order not to unbalance the system.

The cleaning of these parts is done when necessary.

3.3.7

Checking the outdoor air intake

Leaves and pollution could plug up the air intake grille and reduce the unit’s capacity. Check the air intake grille at least
twice a year and clean if necessary.

3.3.8

Checking the duct system

Dust and grease settlements may build up in the duct system even if filters are changed regularly. This will reduce the
efficiency of the installation. The ducts should therefore be cleaned/changed when necessary. Steel ducts can be

154394 | A001

Summary of Contents for Topvex SX/C

Page 1: ...Document in original language 154394 A001 Topvex SX C Topvex TX C Air Handling Unit Operation and Maintenance Instructions GB...

Page 2: ...Systemair AB All rights reserved E OE Systemair AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously...

Page 3: ...escription 4 2 2 10 Section defrosting 5 2 3 Internal components electrical connection box 6 3 Maintenance 7 3 1 Important 7 3 2 Maintenance intervals 7 3 3 Maintenance instruction 8 3 3 1 Changing su...

Page 4: ......

Page 5: ...ies Caution Indicates a risk of damaging the product or prevent optimal operation Important This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory...

Page 6: ...ply air 2 Fan extract air 3 Filter supply air 4 Filter extract air 5 Heat exchanger 6 Electrical connection box 7 Damper by pass outdoor air 8 Pressure transmitter supply air fan extract air filter 9...

Page 7: ...icing is in operation For defrosting a pressure transmitter is installed which measure the differential pressure over the heat exchanger 2 2 5 Switch module A switch module with HMI and 2 TCP IP conne...

Page 8: ...s the night temperature indoor and outdoor temperature during 3 minutes at the set starting hour when the fans are started so that the sensors can perform a temperature measurement If above conditions...

Page 9: ...will start After stop defrosting the unit will re start If the pressure does not decrease the air handling unit is stopped and an alarm is shown in the display Make sure that the ice is melted before...

Page 10: ...ts 4 Terminals for internal wiring 5 Terminals for mains power supply to the unit 6 Contactor K2 On Off Pump control water HW units only not present in EL units 7 Automatic fuse 8 Automatic fuse for h...

Page 11: ...eware of hot surface on the heating battery during maintenance and service 3 2 Maintenance intervals The table below shows recommended maintenance intervals for the unit and the installation To ensure...

Page 12: ...an alarm in the control panel When this occurs do the following 1 Replace the filters with new ones as described below 2 Press on the alarm symbol on the control panel 3 Choose Filter alarm and press...

Page 13: ...o be vented to maintain the batteries capacity 3 3 5 Checking the electrical heating battery After long period of time dust and pollutants can build up on the heating rods This can cause unpleasant od...

Page 14: ...up capacitor saves the memory and keeps the clock running for at least 10 minutes after the power supply is removed Therefore if the battery replacement takes less than 10 minutes there will be no nee...

Page 15: ...if diffusers and louvres need cleaning Check diffuser louvre openings Check if fans and exchanger block need cleaning Check if the roof unit or air intake is clogged Check ducts for visible damage an...

Page 16: ...0V 25 A 50Hz Systemair Sverige AB Industriv gen 3 SE 73930 Skinnskatteberg Sweden 4016 W IP23 225kg Ver A Serial no 1234 567891 0001 140214 Topvex XXXX 16kW 16kW www systemair com 2 3 4 5 Fig 3 Type l...

Page 17: ...154394 A001...

Page 18: ......

Page 19: ......

Page 20: ...C Topvex TX C Operation and Maintenance Instructions 154394 en_GB 14 01 2019 A001 Systemair Sverige AB Industriv gen 3 SE 739 30 Skinnskatteberg Sweden Phone 46 222 440 00 Fax 46 222 440 99 www syste...

Reviews: