17
10
Purge sector
The figure 16 describes how the purge sector change the direction of the outdoor air to exhaust air and by that rinses
the exchanger from remaining of extract air in the rotor material. The air handling units are delivered with the purge
sector function deactivated, step 0.
Two purge sectors are built in the rotary wheel housing one on each side of the rotor as a preparation for both left and
right units. If the angle needs to be changed it is the purge sector on the supply air side.
4
3
1
2
5
6
Fig. 16 Image of right handed exchanger
1
2
3
4
5
6
Exhaust air
Extract air
Outdoor air
Supply air
Direction of rotation of the rotor
Purge sector
Hold on to the purge sector and unscrew the sector according to figure 17. Move the purge sector to step 5 to activate
the purge sector function.
On Topvex SR/TR20–35 the door beam has to be removed to access the purge sector.
Fig. 17
254050 | A004
Summary of Contents for Topvex SR
Page 4: ......