background image

REE — Thyristor

REE 1 and REE 2 - Surface mounting or with flush mounting
casing included.

L

(L)

N

N

N

L

(L)

N

N

N

M

M

REE 4 - Surface mounting.

Note:

Starting currents must be considered when you select the
speed controller type. Products that are used with this
speed controller must have a built-in overheating protec-
tion and must be designed for thyristor speed control.

• L: the connection with cutting function on the speed control.

• (L): the connection without cutting function.

REU

Manual 5-step transformer for high/low speed operation.
Used together with a change-over contact, for example a tim-
er or a thermostat.

REU 1,5

2

1

2

3

3

N

N

REU 3 REU 5 REU 7

1

~

A

B

C

1.

External change-over contact

2.

Left selector switch

3.

Right selector switch

A.

Fan

B.

Earth

C.

Mains supply

RTRE

Manual 5-step transformer with motor protection.

N

Rt

Rt Tk Tk

N

~

~

N

A

B

C

D

E

F

RTRE 1,5 RTRE 3

RTRE 5

Rt

Rt Tk Tk

N

N

~

~

N

A

B

C

D

E

F

RTRE 7

RTRE 12

20

Summary of Contents for TFE

Page 1: ...Installation Operation and Maintenance instruction EN TFSR Roof fan AC EC TFSK Roof fan AC EC TOE Roof fan AC TOV Roof fan AC TFE Roof fan AC ...

Page 2: ...ng 9 6 2 To do the commissioning 9 7 Operation 10 7 1 To start a product with an AC motor 10 7 2 To start a product with an EC motor 10 7 3 To stop the product 10 7 3 1 To stop the product in an emergency 10 8 Maintenance 10 8 1 Maintenance schedule 10 8 2 To clean the product 11 8 3 Spare parts 11 9 Troubleshooting 12 10 Disposal 14 10 1 To disassemble and discard the parts of the product 14 11 W...

Page 3: ...maximum temperature of 45 60 C the tem perature depends on the type of fan For information about temperature ranges refer to www systemair com The product is intended to be used for airflow of small areas for example apartments storages and offices The product is not applicable for transportation of air that contains explosive flammable or aggressive media The product is not applicable for locatio...

Page 4: ...1 4 2 Product overview for TFSK fans 6 7 2 1 4 5 3 1 Base plate 2 Service Lid 3 Fan impeller 4 Motor 5 Connection box 6 Name plate 7 Mounting holes for roof curb 2 ...

Page 5: ...ith motor bracket 2 Fan impeller 3 Position of connection box and name plate with air flow direction arrow The TOE fan is delivered with connection box the TOV fan is delivered without 4 Base plate 5 Casing 6 Screws attaching the lid to the casing 7 Mounting holes for roof curb 3 ...

Page 6: ...1 7 1 Name plate with airflow direction arrow 2 Mains isolator switch 3 Fan impeller and motor 4 Base plate 5 Duct connection 6 Lid lock 7 Motor bracket 8 Lid 9 Motor bracket screw 10 Screw for opening of lid 1 5 Name plate 1 3 2 11 13 12 7 8 9 10 4 5 6 4 ...

Page 7: ... phase 230 V EC Elec tronically commutated 1 phase 230 V 230 V 1 phase 400 V 3 phase 230 V 1 phase 1 after the product name means that the product is sold outside EU 1 6 Product liability Systemair is not liable for damages that the product causes in these conditions The product is incorrectly installed operated or maintained The product is repaired with parts that are not original spare parts fro...

Page 8: ...d size Visit www systemair com for more de tailed information about your product The product is not to be used by persons including chil dren with reduced physical sensory or mental capabil ities or lack of experience and knowledge unless they have been given supervision or instruction Do not allow children to play with the device 2 3 Personal protective equipment Use personal protective equipment...

Page 9: ...rical work Make sure that the installation surface has sufficient ca pacity to hold the weight of the product Refer to the airflow direction arrows on the name plate or on the product to install the product in the correct position Make sure that all cable glands are tight against the ca bles to prevent leaks 4 2 To install the product 4 2 1 To install the TFSR fan Note Make sure the installation l...

Page 10: ...ve earthing is equal to or larger than the cross section of the phase conductor Install a circuit breaker in the permanent electrical installa tion with a contact opening of a minimum 3 mm at each pole If a residual current device RCD is installed make sure that it is an all current sensitive RCD Consider if the prod uct has a frequency converter uninterruptible power sup ply UPS or an EC motor EC...

Page 11: ...s in the air inlet and the air outlet Make sure that installation material and unwanted objects are removed from the product and the ducts 6 2 To do the commissioning 1 Set the installed safety switch in the OFF position 2 If it is possible to get access to the fan impeller do the steps that follows a If it is necessary remove parts of the installation b Turn the fan impeller by hand and make sure...

Page 12: ...n and wait 5 seconds 3 Adjust the fan speed with the 0 10 V signal speed con troller If an external speed controller is not installed ad just the fan speed directly with the integrated potentiometer 7 3 To stop the product 1 Set the installed speed controller in the OFF position Refer to the instruction manual for the installed speed controller 2 Set the installed safety switch in the OFF position...

Page 13: ... cable connections for damage Make sure that the cable glands are tight against the cables X X If flexible connections are installed examine them for damage X X 1 The unusual operation conditions are classified as follows If a stable ambient temperature is higher than 30 C or lower than 10 C if the temperature changes are large or if very contaminated air is transported 8 2 To clean the product Ca...

Page 14: ...til the product operates smoothly Refer to 6 Commissioning page 9 The air output is not sufficient The fan impeller does not turn in the correct direction Make sure that the electrical connection is correctly done The electrical connection is not correctly done Make sure that the electrical connection agrees with the wiring diagrams The air pressure is too low because of incorrect installation Do ...

Page 15: ...cal blockage Remove the blockage Phase loss occurs If the motor is a 3 phase motor make sure that no phase is missing The motor does not rotate A component in the power supply is defective Do a check of the power supply Replace defective components and connect the power supply again The electrical connection is not correctly done Make sure that the electrical connection agrees with the wiring diag...

Page 16: ...led at an approved disposal location for electrical and electronic equipment 10 1 To disassemble and discard the parts of the product 1 Disconnect and disassemble the product in the opposite sequence of electrical connection and installation 2 Recycle the product parts and the packaging at an appli cable disposal location 3 Obey the local and national requirements for disposal 14 ...

Page 17: ... temperature of transported air C Refer to the data sheet in the online catalogue at www systemair com Max ambient temperature C Sound pressure dB IP class Voltage current frequency enclosure class weight Refer to the name plate Refer to 1 5 Name plate page 4 for more information Motor data Refer to the motor name plate or the technical documentation from the motor manufacturer 12 2 Product dimens...

Page 18: ...illimetres F D C B A G E ØA B C D E ØF 4x c c G TFSK 125 M 284 119 144 36 321 9 245 TFSK 125 XL 284 119 144 36 321 9 245 TFSK 160 334 120 145 36 421 9 330 TFSK 200 364 123 160 36 421 9 330 TFSK 315 L 1 404 160 206 36 521 11 450 TFSK 315 M 1 404 160 206 36 521 11 450 TFSK 315 Sileo 404 160 206 36 521 11 450 TFSK 160 EC Sileo 334 147 172 36 421 9 330 TFSK 200 EC Sileo 364 150 187 36 421 9 330 1 afte...

Page 19: ...0 x1 5 12 4x 395 M8 8x 450 557 615 TOV 450 4 800 400 350 50 M8 8x 487 800 M20 x1 5 14 4x 487 M8 8x 590 757 830 12 2 4 Product dimensions for TFE fans Note If the unit of measure is not specified the dimensions are given in millimetres C B A G D F E A B C D E F G TFE 220 M 421 209 36 421 421 209 5 209 5 17 ...

Page 20: ... BK GY N L TFSR 125 XL Sileo TFSK 125 XL Sileo TFSR 160 Sileo TFSK 160 Sileo TFSR 200 TFSK 200 TFSR 315 L 1 TFSK 315 L 1 TFSR 315 M 1 TFSK 315 M 1 TFSR 315 Sileo TFSK 315 Sileo 1 after the product name means that the product is sold outside EU TOE fans 1 phase 230 V TOE 355 4 C TK TK TK Z2 U2 Z1 U1 TK N L TOV fans 3 phase 230 V 3 phase 400 V TOV 355 4 TK TK L1 L2 L3 TK TK W2 U1 U2 V1 V2 W1 TK TK L...

Page 21: ...phase 230 V TFSR 160 EC TFSK 160 EC Sileo N N L L 1 2 3 4 BU BU RD WH YE BK BN GY TFSR 200 EC TFSK 200 EC Sileo 12 3 3 Wiring diagrams for speed controller for AC motors Note The selection of electrical accessories must be done in line with the technical parameters of the product RE Manual 5 step transformer RE 1 5 N N N RE 3 RE 5 RE 7 D C B A A Relay connection There is always 230 V between and N...

Page 22: ...control L the connection with cutting function on the speed control L the connection without cutting function REU Manual 5 step transformer for high low speed operation Used together with a change over contact for example a tim er or a thermostat REU 1 5 2 1 2 3 3 N N REU 3 REU 5 REU 7 1 A B C 1 External change over contact 2 Left selector switch 3 Right selector switch A Fan B Earth C Mains suppl...

Page 23: ...se Tk must be looped together FRQ5S E 6A Frequency converter with built in all pole sine filter and 5 step switch N N L1 N L1 PE L1 U1 U1 U2 U2 K2 E1 GND TB TB D1 D1 GND A2 Digital In 1 Analog In 1 10 V 0 1 M 1 U1 U2 PE TB q TB FRQ5S E 6 10A 22 24 21 BU RD BK 0 1 2 3 5 4 D C B A A Contact rating maximum AC 250 V 2 A B Mains supply 1 phase 208 277 V 50 60 Hz C Motor with internal thermal contacts D...

Page 24: ... the front of the unit RTRD2 7 N L1 L2 L3 L3 L2 L1 N PE U V W PE V W U TB TB TK TK RT L L N 230 V AC RT FS FS Y M 3 0 1 A A A B C D F E A If the function is not necessary the terminals must be bridged B Contact rating 230 V AC maximum 1 A C OFF ON D OFF ON only by reset E Mains supply 3 phase 400 V 50 60 Hz F 3 phase motor with internal thermal contacts 22 ...

Page 25: ...3 0 1 5 4 2 3 C B D E G F RTRDU 0 1 A A A A If the function is not necessary the terminals must be bridged B Contact rating 230 V AC maximum 1 A C Time switch D OFF ON E OFF ON only by reset F Mains supply 3 phase 400 V 50 60 Hz G 3 phase motor with internal thermal contacts 12 3 4 Wiring diagrams for speed controllers for EC motors Note An internal potentiometer is installed on the terminal block...

Page 26: ...Basic EC Basic 230V AC 1 IN Vac 2 IN Vac 4 Out 5 GND 10V 0 10V GND MTV 1 10 MTV 1 010 1 IN Vac 2 IN Vac 4 Out 5 Out 10V 0 10V GND 230V AC S 5EC FRQ MTP 10 GND 10V A 10V 0 10V GND EC Vent EC Vent IN RPM PWM IN 10V OUT PWN GND TACH optional 10V 0 10V PWM GND 24 ...

Page 27: ...ay NO Relay NC 10V 0 10V GND Din1 12 3 6 Wiring diagrams for demand control for EC motors EC Basic EC Basic T for temperature control EC Basic 230V AC 1 IN Vac 2 IN Vac 4 Out 5 GND 10V 0 10V GND EC Basic CO2 T for temperature and CO2 control EC Basic H for humidity control EC Basic U EC Basic U for universal 0 10 V control 1 110 240 V 50 60Hz 2 3 4 5 6 7 8 OUT 0_10V 0_10V GND GND IN V L N 25 ...

Page 28: ...ystem has 2 units The control board CB and the room unit RU Connect the fan to the control board and remove the internal potentiometer EC Vent IN RPM PWM IN 10V OUT PWN GND TACH optional 10V 0 10V PWM GND Room Unit RU Br 24VDC Y 0 10V Gr Bl GND R 24VDC Y 0 10V W CB A B GND 24V REF T1 I2 I1 24V C B A 26 ...

Page 29: ...V GND A D PT1000 24V N out N in L out L in IN3 IN2 IN2 A Mains supply 230 V 1 AC 10 A B Analogue sensor for example pressure sensor C Analogue sensor for example pressure sensor type PT1000 D Digital sensor for example IR presence detector E Alarm output maximum 24 V AC DC maximum 500 mA Cosφ 0 95 F Output to EC fan G Output to analogue actuator with 24 V DC supply H Output to digital signal DC ma...

Page 30: ...V Output maximum 0 10V PCA 1000D2 Pressure controller For constant air volume control CAV or variable air volume control VAV GND A GND 1 2 US US PCA 1000 6000D2 10 24 V DC p p V PI Ri 4 kΩ 01 0 Setpoint 1 1 Setpoint 2 Uout 3 1 2 4 1 Mains supply 10 24 V DC 2 Output 0 10 V 3 Pressure connections 4 Voltage input for switch on Setpoint 1 Setpoint 2 13 Accessory overview 13 1 Accessory overview for TF...

Page 31: ...d covering plate 3 TOS Roof curb with flat covering plate 13 2 Accessory overview for TFSK fans TOE fans TOV fans and TFE fans Note For more information about accessories refer to www systemair com or speak to Systemair technical support 29 ...

Page 32: ...2 3 5 4 6 1 1 Fan 2 FDS Flat roof socket 3 FDS L Flat roof socket large 4 TG Roof curb 5 STG Connection plate base plate 6 ASK Inflow box SSD 30 ...

Page 33: ...losures IP Code Directive electromagnetic compatibility EMC 2014 30 EU EN 62233 2008 Measurement methods for electromagnetic fields of household appliances and similar apparatus with regard to human exposure EN 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial environments RoHS Directive 2011 65 EU EN IEC 63000 2018 Technical documentation for the ...

Page 34: ...y Regulations 2016 EN 62233 2008 Measurement methods for electromagnetic fields of household appliances and similar apparatus with regard to human exposure EN 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial environments The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012 EN IEC 63000 ...

Page 35: ...33 ...

Page 36: ...ir AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously agreed specifications Systemair Sverige AB Industrivägen 3 SE 739 30 Skinnskatteberg 46 222 440 00 info systemair se www systemair se last page ...

Reviews: