background image

4

Press “Down” to go to “Metrics units” and press “P” to
choose “1: metric unit” (The factory setting, measures in
Pa, m3/h, K-factor).

5

Press “Down” to go to “Measuring range” and press “P”
to set the measuring range:

• 1 = 0-1000 Pa

• 2 = 0-500 Pa

• 3 = 0-300 Pa

• 4 = 0-200 Pa

6

Press “Up” and “Down” at the same time to leave the
“Base set-up” menu.

7

Press “Down” to go to “Settings”.

8

Press “Down” to go to “Set the pressure set point” and
set the pressure setpoint:

• Setpoint 1 — The normal operation pressure setpoint.

• Setpoint 2 — The pressure setpoint during a secon-

dary operation mode. The factory setting is 50% of
the measuring range. Setpoint 2 is active when there
is a connection between input 1 and 2.

The active setpoint is shown in “Info” with a moon symbol
when setpoint 2 is active.

To set up the controller for VAV with outdoor
compensation

1

Press “Down” to go to “Base set-up”.

2

Press “P” to enter the menu.

3

Press “Down” to go to “Mode” and press “P” to choose
4.02.

4

Press “Down” to go to “Metrics units” and press “P” to
choose “1: metric unit”, (the factory setting, measures in
Pa, m3/h, K-factor).

5

Press “Down” to go to “Sensor type” and press “P” to
choose sensor type:

• KTY81210 (the factory setting)

• PT1000

6

Press “Down” to go to “Measuring range” and press “P”
to select the desired measuring range:

• 1 = 0-1000 Pa

• 2 = 0-500 Pa

• 3 = 0-300 Pa

• 4 = 0-200 Pa

7

Press “Up” and “Down” at the same time to leave the
“Base set-up” menu.

8

Press “Down” to go to “Settings”.

9

Press “Down” to go to “Set the pressure set point” and
set the pressure setpoint:

• Setpoint 1 — The normal operation pressure setpoint.

• Setpoint 2 — The pressure setpoint during a secon-

dary operation mode.

10

Press “Down” to go to “T-Band SA” and set the tempera-
ture range in which the setpoint changes with the out-
door temperature (The factory setting is: 30.0 K).

11

Press “Down” to go to “T-Start SA” and set the tempera-
ture for when reduction starts (The factory setting is: 15 °
C).

12

Press “Down” to go to “Min. setpoint” to set the minimum
pressure for a very low outdoor temperature (The factory
setting is: 500 Pa).

4.2.4

To change from VAV control
to CAV control

1

Loosen the screws on the casing and the electrical cabi-
net and open the lids, refer to

4.2.1 To install the TFC-P

fan and the TFC-S fan page 4

.

2

Remove the tube (1) from the minus inlet (-) and put it on
the plus inlet (+) on the pressure controller.

2

1

1

1

2

3

Put the blue tube (2) on the minus inlet (-) on the pres-
sure controller. The other end of the blue tube (2) is in-
stalled on the fan impeller cone from the factory.

4.2.5

To set up the controller for
CAV

1

Press “Down” to go to “Base set-up”.

2

Press “P” to enter the menu.

3

Press “Down” to go to “Mode” and press “P” to choose
5.01 CAV control.

4

Press “Down” to go to “Metrics units” and press “P” to
choose “1: metric unit” (The factory setting, measures in
Pa, m3/h, K-factor).

5

Press “Down” to go to “Measuring range” and press “P”
to set the measuring range:

• 1 = 0-1000 Pa

• 2 = 0-500 Pa

• 3 = 0-300 Pa

• 4 = 0-200 Pa

6

Press “Down” to go to “K-Factor” and set the K-factor de-
pending on your product size. Refer to the table

1 K-fac-

tor page 8

.

7

Press “Up” and “Down” at the same time to leave the
“Base set-up” menu.

8

Press “Down” to go to “Settings”.

7

Summary of Contents for TFC-P Roof fan EC

Page 1: ...Installation Operation and Maintenance instruction EN TFC P Roof fan EC TFC S Roof fan EC...

Page 2: ...5 3 Speed controller for EC motors 9 5 4 Motor protection for EC motors 9 6 Commissioning 9 6 1 To do before the commissioning 9 6 2 To do the commissioning 9 7 Operation 10 7 1 To start a product wit...

Page 3: ...uct is used for transportation of clean or contami nated air with a maximum temperature of 60 C in continuous operation The product is intended for installation outdoors on commer cial and residential...

Page 4: ...e The data on the name plate applies to standard air that is specified in the standard ISO5801 1 5 1 Type designation Product name TFC P TFC S Dimension 225 225 280 280 355 355 450 450 500 500 560 560...

Page 5: ...adjacent area during all work on the product Make sure that you know how to stop the product quickly in an emergency Use applicable safety devices and personal protective equipment during all work on...

Page 6: ...If you install the product with free suction or free dis charge it is necessary to install a protection grille Make sure that the safety distance agrees with the standard DIN EN ISO 13857 and the stan...

Page 7: ...Release the lock by pulling the lever beside the lock Caution Keep fingers away from the back of the hinge The back of the hinge is a poten tial pinch point Note TFC 225 and TFC 280 have no handle Ho...

Page 8: ...the roof in accordance with applicable building standards and connect the fan to a duct system Note Obey local laws and regulations for installation of the roof curb on the roof 7 Close the electrica...

Page 9: ...the pressure setpoint Setpoint 1 The normal operation pressure setpoint Setpoint 2 The pressure setpoint during a secon dary operation mode 10 Press Down to go to T Band SA and set the tempera ture r...

Page 10: ...nd press P to select the desired measuring range 1 0 1000 Pa 2 0 500 Pa 3 0 300 Pa 4 0 200 Pa 6 Press Down to go to K Factor and set the K factor de pending on your product size Refer to the table 1 K...

Page 11: ...until the vibrations are decreased Continuous strong vibrations can cause damage to components Do not increase the fan speed to a higher rpm value than the maximum value that is given on the name pla...

Page 12: ...ion manual for the installed speed controller 2 Set the installed safety switch in the OFF position 7 2 1 To stop the product in an emergency Set the installed safety switch in the OFF position 8 Main...

Page 13: ...ons are classified as follows If a stable ambient temperature is higher than 30 C or lower than 10 C if the temperature changes are large or if very contaminated air is transported 8 2 To clean the pr...

Page 14: ...e 9 The air output is not sufficient The fan impeller does not turn in the correct direction Make sure that the electrical connection is correctly done The electrical connection is not correctly done...

Page 15: ...al blockage Remove the blockage Phase loss occurs If the motor is a 3 phase motor make sure that no phase is missing The motor does not rotate A component in the power supply is defective Do a check o...

Page 16: ...ed at an approved disposal location for electrical and electronic equipment 10 1 To disassemble and discard the parts of the product 1 Disconnect and disassemble the product in the opposite sequence o...

Page 17: ...re of transported air C 60 Sound pressure dB Refer to the data sheet in the online catalogue at www systemair com Corrosion class IP class Voltage current frequency enclosure class weight Refer to the...

Page 18: ...Abbreviation in wiring diagram Cable colour RD Red YE Yellow BU Blue WH White GN Green BN Brown BK Black GR Grey GY Green Yellow 12 3 1 Wiring diagrams for TFC P fans TFC P fans 1 phase 230 V TFC P 2...

Page 19: ...TF Us 13 14 2 ID1 ID2 GND GND A A B B 10 24VDC WH BU YE RD GND Us BK WH BN GN YE BN BU T24 24V 230V 2 1 4 3 PE L1 N PE L1 L1 L1 L2 L3 N NC COM N L2 PE BU BN GN YE N NC C 3 8 4 5 6 7 2 9 1 11 12 10 15...

Page 20: ...16 TFC P 560 1 Safety switch 2 Aux contact Signal relay 3 24 V DC 4 0 10 V out 5 0 10 V out 6 Digital input 7 Digital input 8 Temperature 9 Modbus slave 10 Transformer 11 Connection box 12 Pressure co...

Page 21: ...ection box 2 0 10 V DC Ext 3 Time 1 min 4 Safety switch 5 Motor 6 230 V 1 TFC S fans 1 phase 230 V TFC S 355 4 BK BU GN YE GN YE BU BN WH 1 WH 2 5 2 1 4 3 PE L N RSA RSB BN BU WH YE RD DC GN YE BN BU...

Page 22: ...RD M L2 L1 GN YE L3 WH WH PE L1 L2 L3 NC COM GN YE BN BK GY PE L1 L2 L3 4 5 TFC S 560 1 Connection box 2 0 10 V DC Ext 3 Time 1 min 4 Alarm 5 Safety switch 6 ON OFF 7 Motor 8 230 V 1 12 3 3 Pressure...

Page 23: ...as with higher pressure 7 Digital input D1 terminals 1 2 8 Input outdoor temperature sensor terminals TF TF 9 MODBUS interface terminals GND A B ID1 ID2 and jumper J1 12 3 4 Wiring diagrams for speed...

Page 24: ...MTV 1 10 MTV 1 010 1 IN Vac 2 IN Vac 4 Out 5 Out 10V 0 10V GND 230V AC S 5EC FRQ MTP 10 GND 10V A 10V 0 10V GND EC Vent EC Vent IN RPM PWM IN 10V OUT PWN GND TACH optional 10V 0 10V PWM GND 22...

Page 25: ...y NO Relay NC 10V 0 10V GND Din1 12 3 6 Wiring diagrams for demand control for EC motors EC Basic EC Basic T for temperature control EC Basic 230V AC 1 IN Vac 2 IN Vac 4 Out 5 GND 10V 0 10V GND EC Bas...

Page 26: ...stem has 2 units The control board CB and the room unit RU Connect the fan to the control board and remove the internal potentiometer EC Vent IN RPM PWM IN 10V OUT PWN GND TACH optional 10V 0 10V PWM...

Page 27: ...GND A D PT1000 24V N out N in L out L in IN3 IN2 IN2 A Mains supply 230 V 1 AC 10 A B Analogue sensor for example pressure sensor C Analogue sensor for example pressure sensor type PT1000 D Digital s...

Page 28: ...Output minimum 0 10V Output maximum 0 10V PCA 1000D2 Pressure controller For constant air volume control CAV or variable air volume control VAV GND A GND 1 2 US US PCA 1000 6000D2 10 24 V DC p p V PI...

Page 29: ...2 1 1 TFC P TFC S fan 2 Roof curb TG Note For more information about accessories refer to www systemair com or speak to Systemair technical support 27...

Page 30: ...s IP Code Directive electromagnetic compatibility EMC 2014 30 EU EN 62233 2008 Measurement methods for electromagnetic fields of household appliances and similar apparatus with regard to human exposur...

Page 31: ...lations 2016 EN 62233 2008 Measurement methods for electromagnetic fields of household appliances and similar apparatus with regard to human exposure EN 61000 6 2 2005 Electromagnetic compatibility EM...

Page 32: ...r AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously agreed specifications Systemair Sverige AB In...

Reviews: