Product information

3.1

General

This installation manual concerns Roof fans TFC 225, TFC 280, TFC 355, TFC 450, TFC 500 and TFC 560 manufactured
by Systemair Sverige AB.

The S-fans are delivered with potentiometer, 0-10 V. The integrated potentiometer is factory preset to 10 V. This value
can be changed manually to obtain a different motor rpm/fan performance. Fan performance charts for this purpose
are shown in the table by voltage steps (chapter 3.2.2). An external potentiometer can be connected if necessary. If so
the internal potentiometer needs to be disconnected from the connection terminals. It is also possible to use an exter-
nal pressure meter to set the desired airflow using the K-factor table (chapter 4.3).

The P-fans are regulated with a built in differential pressure and airflow controller. The fans are delivered with VAV con-
trol – Variable Air Volume but can be converted to CAV – Constant Air Volume (see chapter 4.2).

This manual consists of basic information and recommendations concerning the design, installation, start-up and opera-
tion, to ensure a proper fail-free operation of the unit. The key to proper and safe operating of the unit is to read this
manual thoroughly, use the unit according to given guidelines and follow all safety requirements.

The TFC 225-560 S/P are intended for transportation of air in air handling systems. The fans are meant for use in ducted
systems and should always be duct connected on the inlet side. No moving parts shall be accessible after installation.
TFC 225-560 S/P roof fans are adapted to continuous operation.

Roof fans are exclusively intended for extract air applications.

Danger

• The fans are not to be used in hazardous environments or connected to flue ducts.

• The appliance must be connected to a mains circuit breaker in the fixed installation.

• Switch power off (all-pole circuit breaker) before servicing or maintenance, and make sure the impeller

has come to standstill.

• Make sure protection grid has been installed (EN ISO 13857), no moving parts shall be accessible after

installation.

• Do not remove, short-circuit or disconnect safety accessories (i.e. motor protection, safety grille).

Warning

• The fans can have sharp edges and corners which may cause injuries. Be careful when opening the fans,

the motor assembled on the motor bracket is relatively heavy.

Caution

• Take precautions to prevent the back flow of exhaust gases from flues from other appliances installed in

the same room, which are fired by gas or other fuels.

• This appliance can be used by children aged from 8 years and above and persons with reduced physical,

sensory or mental capabilities or lack of experience and knowledge if they have been given supervision
or instruction concerning use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children
without supervision.

206434 | A006

Summary of Contents for TFC 225 P

Page 1: ...Document in original language 206434 A006 Roof fans TFC 225 560 S P Operation and Maintenance Instructions GB...

Page 2: ...Systemair AB All rights reserved E OE Systemair AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously...

Page 3: ...3 Wiring diagram 6 3 2 4 Residual current devices 10 3 3 Transportation and storage 10 4 Installation 10 4 1 Installing the fans 11 4 2 Change from VAV to CAV 13 4 3 K factor 13 4 4 Commissioning 14 4...

Page 4: ......

Page 5: ...essment and risk reduction EN 13857 Safety of machinery Safety distances to prevent hazard zones being reached by upper or lower limbs EN 60 335 1 Household and similar electrical appliances Safety Pa...

Page 6: ...ies Caution Indicates a risk of damaging the product or prevent optimal operation Important This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory...

Page 7: ...ms The fans are meant for use in ducted systems and should always be duct connected on the inlet side No moving parts shall be accessible after installation TFC 225 560 S P roof fans are adapted to co...

Page 8: ...B C D E F G H Weight kg TFC 225 413 422 281 330 435 266 49 195 12 4 TFC 280 514 523 333 450 535 368 86 245 17 1 TFC 355 618 627 376 535 637 491 150 300 27 5 TFC 450 728 737 417 655 747 602 176 375 35...

Page 9: ...10V TFC 280 2 6V 0 0 4 0 8 1 2 1 6 0 250 500 750 1000 Q m s Ps Pa 0 1000 2000 3000 4000 5000 m h 16745 16744 5V 7 3V 10V TFC 355 2 5V 0 0 5 1 1 5 2 0 200 400 600 800 Q m s Ps Pa 0 2000 4000 6000 m h 1...

Page 10: ...s possible from TFC 355 see wiring diagram Tacho 0 10V DC Ext RD YE BU WH 1 3 2 4 BU BN BK GN YE 230V 1 N L PE 1 TFC 225 280 S M RSA RSB 0 10V DC Ext RD YE BU WH BN 1 3 2 4 230V 1 BU BN GN YE N L PE G...

Page 11: ...1 PE L3 GY BK BN GN YE 0 10V DC Ext RD YE BU WH BN RSA RSB WH 2 WH 1 BK 3 BK 2 BK 1 GN YE 1 TFC 500 S M 3 1 3 2 4 400V 3 5 6 BK BN GN YE GY C NC L3 L2 L1 PE L2 L1 PE L3 GY BK BN GN YE 0 10V DC Ext 10V...

Page 12: ...N BK GN YE N L PE Tacho A GND US GND 1 2 TFC 225 280 P M 10V DC 10 24 V DC 2 1 Ri 4 k 1 3 2 4 230V 1 RD YE BU WH BN BU BN GN YE WH 2 WH 1 BU BK GN YE N L PE BU BN GN YE RSA RSB A GND US GND 1 2 1 2 TF...

Page 13: ...4 400V 3 5 6 BK BN GN YE GY C NC L3 L2 L1 PE L2 L1 PE L3 GY BK BN GN YE 10V Ain1U GND RSA RSB A GND US GND 1 2 TFC 560 P M 3 10V DC 10 24 V DC 2 1 Ri 4 k 1 Safety switch 2 Fan control 3 Alarm RD Red...

Page 14: ...ft the fans by the connecting cable connection box motor bracket impeller or inlet cone 4 Installation Danger Make sure that the mains supply to the unit is disconnected before performing any maintena...

Page 15: ...cal compartment Figure 2 Connect the mains supply to the lockable safety switch 1 Image show S controller 2 The hinges on the hatch to the electrical compartment prevents the hatch from falling down F...

Page 16: ...on 4 5 Figure 5 Mains supply 4 can be run through the cable glands beside the electrical compartment or inside a roof curb if used Note Don t cover this gap 5 It is for drainage if water enters the fa...

Page 17: ...nection to the con troller the tubing from the bottom of the fan 1 to plus inlet and the tubing from the cone 2 to minus The tubing from the cone is labelled with blue tape In BASE SETUP 5 01 in table...

Page 18: ...Rated current must not be exceeded with more than 5 at rated voltage The direction of rotation should correspond to direction of rotation arrow 3 phase Smoothness of motor operation no abnormal noise...

Page 19: ...t for Escape Esc Info Selection of the menu group e g BASE SETUP to the right through the key to the left through the key You can go to the menu items in the menu groups e g mode by using the P key Us...

Page 20: ...depending on adjusted setpoint and measured actual value Table 1 Parameter table Parameter Display Factory setting Function Mode 4 00 4 01 5 00 5 01 Mode INFO Information p 0 Pa 0 Pa Different actual...

Page 21: ...01 0 100 sensor measuring range 5 01 0 Max Range qV depending on K factor and sensor measuring range 2 Small value quick regulation great value slow regulation high stability BASE SETUP Base setup Mod...

Page 22: ...cessary at least once a year to avoid imbalance and unnecessary damage to the bearings The fan bearings are maintenance free and should only be replaced if damaged Do not use a high pressure cleaner s...

Page 23: ...ce release the lock using the handle to bring the motor down Fasten the motor bracket with the screws Note TFC 225 and TFC 280 has no handle hold the motor bracket to lift the motor 7 Troubleshooting...

Page 24: ...of fans Operation and Maintenance Instructions 206434 en_GB 21 11 2017 A006 Systemair Sverige AB Industriv gen 3 SE 739 30 Skinnskatteberg Sweden Phone 46 222 440 00 Fax 46 222 440 99 www systemair co...