background image

Controller for Fan Coil Units

Installation and maintenance manual

TControl POD glass EC

Summary of Contents for TControl POD glass EC

Page 1: ...Controller for Fan Coil Units Installation and maintenance manual TControl POD glass EC...

Page 2: ......

Page 3: ...INSTALLATION INSTRUCTION NOTICE D INSTALLATION INSTALLATIONSHANDBUCH ISTRUZIONI INSTALLAZIONE INSTRUCCIONES DE INSTALACI N English Fran ais Espa ol Deutsch Italiano...

Page 4: ...TIME SLOT 10 7 3 DATE AND TIME 11 7 4 ALARM MODE 12 7 4 1 OVERVIEW 12 7 4 2 TEMPERATURE THRESHOLDS 12 7 5 FAN MENU 13 7 5 1 OVERVIEW 13 7 6 CONFIGURATION MENU 14 7 6 1 PRE CONFIGURATION 14 7 7 LANGUAG...

Page 5: ...ng contact Function control Setpoint adjustment 0 50 C Screen LCD 60 x 44 mm 240 x 160 px white backlighting Functions PI or 2 3 point control Unit PC high strength tempered glass Protection rating IP...

Page 6: ...to two parts Simply pull slightly on the unit in one corner Figure 1 2 Then depending on the cable entry the push button is removed 20 mm backwards or 12 mm up down and deburred 3 Attach the back of t...

Page 7: ...nsmission used by the TControl POD glass EC allows a maximum of 32 objects per bus segment This constraint is only due to a current reading ability of the material The TControl POD glass EC can be con...

Page 8: ...this value will be shown on the screen Refer to the MODBUS TABLES page 22 address 18 Depending on the configuration Refer to the MODBUS TABLES page 22 address 10 the screen may display ambient temper...

Page 9: ...ndow contact etc are available These symbols are grouped together Only one symbol per set can be shown at a time They may or may not be inhibited Refer to the MODBUS TABLES page 22 addresses 11 12 13...

Page 10: ...to access this menu The button combination can be locked by the button access menu parameter Refer to the MODBUS TABLES page 22 address 124 so that a user will not be able to change the parameters af...

Page 11: ...Language Active line Highlighted Next menu Header 7 1 4 SYMBOLS The following symbols are used in the menu for better guidance when navigating the menu 7 1 4 1 CHANGE OF VALUE The value can be changed...

Page 12: ...day 1 4 Start time Fan speed Temperature setpoint ECO mode Table 1 Time slot structure A period is active if the start time and days match the programmed values A period remains active until the condi...

Page 13: ...3 Overview Selecting the time slot period 4 Setting the time slot period Time format 24 hour 12 h A M P M mode display or no display mode Date format No display or display in English or Continental mo...

Page 14: ...ns on permanently The alarm is signaled via the temperature alarm register Refer to the MODBUS TABLES page 22 address 526 It remains active until it is reset via Modbus Refer to the MODBUS TABLES page...

Page 15: ...C O 20 100 4T 20 100 SCC30 2T 20 100 2T2F 50 100 2TC O 20 100 4T 20 100 SCC40 2T 20 100 2T2F 40 100 2TC O 20 100 4T 20 100 SCC50 2T 20 100 2T2F 50 100 SCC60 2TC O 20 100 4T 20 100 SYSCOIL COMFORT Unit...

Page 16: ...ved from the minimum value in the table Example for a minimum value of 30 you must enter 30 32 768 in register 111 i e 32 738 Ventilation can operate in 2 modes permanent ventilation ventilation opera...

Page 17: ...n English Fran ais To access the diagnostic menu select the parameter menu header then press ENTER On this display you will find various information such as the type of object its software version the...

Page 18: ...C by default Refer to the MODBUS TABLES page 22 address 24 If a time slot interval with ECO mode is active the ECO symbol is shown at the top of the main screen When ECO mode is active the value of t...

Page 19: ...r to the MODBUS TABLES page 22 address 6 The controller has 2 configurable inputs 11 CONFIGURATION 11 1 TEMPERATURE 11 2 INPUTS UNIVERSAL INPUT 1 INPUT 2 230 V Use input 2 for 230 V equipment Change O...

Page 20: ...alue determines the output value The digital input has the highest priority When the in use function is active its symbol is automatically visible if it has been selected in the footer 11 2 1 CHANGE O...

Page 21: ...configuring a digital input Address 18 The thermostat has a PI or discrete controller to regulate the heating and cooling demand The adjusted variable is delivered by the outputs 11 3 HOT AND COLD CON...

Page 22: ...s active if the start time and days match the programmed values A period remains active until the conditions of another period are met The active setpoint can be overridden by Modbus via the basic set...

Page 23: ...utes after power up as long as the instrument is not integrated into a Modbus network As soon as the object receives a valid Modbus message access to this menu is locked Without a valid communication...

Page 24: ...ew point 4 Ventilation stage 5 Hourly programming 4 14 0 5 1 Footer symbol 4 0 No symbol 1 Heat Cold 2 In use 3 Window contact Dew point 4 Ventilation stage Factory setting 5 Hourly programming 4 15 0...

Page 25: ...iod 3 Time slot 1 period 3 4 47 0 50 0 1 Time slot 1 setpoint period 3 Time slot 1 period 3 4 48 0 4 Time slot 1 AC fan period 3 Time slot 1 period 3 4 49 0 1 Time slot 1 ECO mode period 3 Time slot 1...

Page 26: ...9 1 Time slot 3 start minute period 4 Time slot 3 period 4 4 94 0 50 0 1 Time slot 3 setpoint period 4 Time slot 3 period 4 4 95 0 4 Time slot 3 AC fan period 4 Time slot 3 period 4 4 96 0 1 Time slot...

Page 27: ...Pre configuration 0 4P Factory setting 1 Changeover 2 CO 3 HO 4 255 0 50 0 1 Basic setpoint 0 500 0 0 50 0 C Factory setting 21 0 C 256 0 15 0 1 Setpoint offset 0 150 0 0 15 0 C Factory setting 0 C 2...

Page 28: ...50 0 C Example 21 5 C 215 516 0 1 Heat output 0 Open 1 Closed 517 0 1 Cold output 0 Open 1 Closed 518 0 10 0 1 Ventilation status 0 100 0 10 V Manual 256 156 0xFF00 0xFF64 Automatic with value in vol...

Page 29: ......

Page 30: ...ersedes None As part of our ongoing product improvement programme our products are subject to change without prior notice Non contractual photos Systemair AC SAS Route de Verneuil 27570 Tilli res sur...

Reviews: