Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
Outdoor sensor
placed in
intake channel
(intake duct)
No
Set
if the outdoor sensor is
placed in the intake duct or not.
Choose between
No
and
Yes
Preset is
No
.
→
Support
control
Support control
Active:
No
EAF running
during Support
contr.:
Yes
When using the control
function room control or
extract air temperature
control, it is possible to
utilize support-heating and/or
support-cooling. Minimum
running time is settable 0…720
minutes. (factory setting 20
minutes). Choose between
“Active: Yes or No”.
(For start and stop temperatures
see the "Temperature" menu)
Min.
run time
for support
ctrl:
60 min
Set
the minimum running time
in minutes for support control
→
CO2/VOC
Control
CO2/VOC active
Never
Type:
Fan
Min.
time:
60
min
In applications with varying
occupancy the fan speeds
can be controlled by the air
quality as measured by a
CO2/VOC-sensor. See encl.
corrigo manual (CD) for det.
explanation
Set
active to
Never
,
Always
or
If time channel off
.
Set what should be regulated.
Select type
Fan
Set
the min. time the unit is
activated by the CO2/VOC
demand function
Activation
level
1/2–speed:
800
ppm
1/1–speed:
1000 ppm
diff:
160 ppm
Set
the activation level at 1/2
speed
Set
the activation level at 1/1
speed
Set
allowed diff. value
→
Fire function
Fire damper
function
Not active
Operation when
alarm
Stopped
Set
fire damper to
Normally
closed/Normally
open/Not active.
Set
behaviour of the unit
when fire alarm is triggered
Stopped/Continuous
run/Normal run/Only
SAF/Only EAF
.
Operation and Maintenance Instructions
132616
19
Systemair Sverige AB