SystemAir SAVE-P VSR 150/B User Manual Download Page 18

14

Troubleshooting

5

Troubleshooting

If problems should occur, please check the items below before calling your service representative.

Fans do not start

1. Check the control panel for alarms.

2. Check that all fuses and fast couplings are connected (main power supply and fast couplings for supply and extract

air fans).

3. Check the week schedule. Fans may be set to

OFF

in the Schedule airflow settings menu.

Reduced airflow

1. Check the control panel for alarms. Some alarms can reduce the airflow to

LOW

if active.

2. The unit could be in defrost mode. This reduces the fan speed and in some cases shuts down the supply air fan com-

pletely during the defrosting cycle. The fans go back to normal after defrosting. There should be a defrosting function
icon visible on the home screen if defrosting is active.

3. Speed of fans is linearly reduced when the outdoor air temperature is below 0°C and an outdoor airflow compensa-

tion function is enabled.

4. Check if temporary user mode that reduces airflow is not activated, for example

Away

,

Holiday

, etc. Also check dig-

ital inputs

Central Vacuum Cleaner

and

Cooker Hood

.

5. Check the airflow settings in the control panel.

6. Check week schedule settings (chapter 3.2.8).

7. Check filters. Is change of filters required?

8. Check diffusers/louvres. Is cleaning of diffusers/louvres required?

9. Check fans and heat exchange block. Is cleaning required?

10.Check if the buildings air intake and roof unit (exhaust) have been clogged.

11.Check visible duct runs for damage and/or build up of dust/pollution.

12.Check diffuser/louvre openings.

The unit cannot be controlled (control functions are stuck

1. Reset control functions by disconnecting mains power for at least 10 seconds.

2. Check the modular contact connection between the control panel and the main printed circuit board.

Low supply air temperature

1. Check the control panel for alarms.

2. Check the active user functions on the control panel if defrosting function is running.

3. Check set supply air temperature on the control panel.

4. Check if

ECO

mode is activated on the control panel (it is a power saving function and prevents the heater from

activating).

5. Check if user modes

Holiday

,

Away

or

Crowded

are activated on the control panel or via a hardwired switch.

6. Check the analogue inputs in the service menu to verify that the temperature sensors are functioning correctly.

7. In case of installed electrical/other re-heater battery: Check if the overheat protection thermostat is still active. If

necessary, reset by pressing the red button on the front plate of the electrical re-heater.

8. Check if the extract filter must be changed.

9. Check if the unit has a re-heater battery connected. At very cold outdoor conditions an electrical or water heating

battery might be necessary. A re-heater battery can be acquired as an accessory.

Noise/vibrations

1. Clean fan impellers.

2. Check that the screws holding the fans are tightened.

3. Check that the anti vibration lists are fitted to the mounting bracket and to the back of the unit.

4. Check that the rotor belt is not slipping if the unit has rotating heat exchanger.

271400 | v1.0

Summary of Contents for SAVE-P VSR 150/B

Page 1: ...Document in original language 271400 v1 0 SAVE P VSR 150 B User Manual GB...

Page 2: ...stemair UAB All rights reserved E OE Systemair UAB reserves the rights to change their products without notice This also applies to products already ordered as long as it does not affect the previousl...

Page 3: ...To change the temperature 7 3 2 7 To change the airflow 7 3 2 8 To set a week schedule 8 4 Maintenance 9 4 1 Maintenance Schedule 9 4 2 To access internal components 9 4 3 To change filters 10 4 3 1...

Page 4: ......

Page 5: ...temair will require these in the case of a warranty claim 1 3 Type label Before calling your service representative make a note of the specification and production number from the type label which can...

Page 6: ...AVE LIGHT control panel Fig 2 Explanation of symbols SAVE LIGHT is a basic control panel for SAVE series resi dential air handling units SAVE LIGHT allows to change airflow levels and indicates when a...

Page 7: ...nsation when the unit has been stopped 3 1 3 To cancel sleep mode Press any button to cancel the sleep mode SAVE LIGHT returns to the sleep mode after 3 minutes of inactivity All control panel lights...

Page 8: ...e number and the second number indicates a total number of pages available Many options show up in a form of the pop up window Select the option from the displayed list in the pop up window and press...

Page 9: ...ick information screen shows the following information 1 Time 2 Outdoor temperature 3 Current User mode Alarm 4 Fan speed off Minimum Low Normal High Maximum 5 Supply air temperature 6 Relative humidi...

Page 10: ...irflow setting in Week Schedule Manual Manual selection of airflow levels The unit can be set run at one out of four available airflow speeds Off Low Normal High Note The fan can be set to OFF by acti...

Page 11: ...ttings of all modes can be modified in Service menu 3 2 6 To change the temperature Touch the thermometer symbol on the home screen to open the temperature settings window Use up and down arrows to in...

Page 12: ...Use arrow buttons and to increase or decrease value Confirm with OK button Note Scheduled time can start but never end at midnight 00 00 The latest END TIME period is 23 59 Scheduled time cannot go to...

Page 13: ...1 Maintenance Schedule Task 6 months 1 year 3 years When necessary General inspection X Filter change X X Fan cleaning X Heat exchanger cleaning X X Belt replacement X Checking and cleaning louvres d...

Page 14: ...e new filters Make sure that the correct filter types are inserted 5 Remount and fasten the filter cover plates and connect the unit to mains 6 Reset the filter time See chapter 4 3 1 4 3 1 To reset t...

Page 15: ...if not secured Make sure that small children are not beneath the unit when the heat exchanger is removed Caution Beware of sharp edges during mounting and maintenance Use protective gloves Even if the...

Page 16: ...eeded 4 Clean the fans with a cloth or a soft brush Do not use water White spirit can be used to remove obstinate deposits Allow the fans to dry properly before remounting 5 Remount the fans Don t for...

Page 17: ...ouvres can be done as necessary 4 7 2 Checking the outdoor air intake Leaves and pollution could plug up the air intake grille and reduce the capacity Check the air intake grille and clean as necessar...

Page 18: ...11 Check visible duct runs for damage and or build up of dust pollution 12 Check diffuser louvre openings The unit cannot be controlled control functions are stuck 1 Reset control functions by discon...

Page 19: ...230V 1 50Hz 7 Disposal and recycling This product is compliant with the European WEEE Directive and related national waste legislation When disposing the unit follow your local rules and regulations...

Page 20: ...SAVE P VSR 150 B User Manual 271400 en_GB 2021 04 30 v1 0 Systemair UAB Lin st 101 LT 20174 Ukmerg LITHUANIA Phone 370 340 60165 Fax 370 340 60166 www systemair com...

Reviews: