9.4.3
Menu for air volume control
5.01
and
5.02
Parameter
Factory setting
User Setting
Start
PIN input
- - - - -
- - - - -
Language
GB
GB
Reset
OFF
OFF
Mode
5.01
5.02
Acontrol
1.14
1.14
Info
E1 Actual
712 m
3
h
712 m
3
h
E2 Actual
- - - - -
21.0
°
C
Setpoint1
530 m
3
h
530 m
3
h
Setpoint control
530 m
3
h
Modulation
0 %
0 %
Msco
OFF
OFF
Setting
Setpoint1
530 m
3
h
530 m
3
h
Setpoint2
- - - - -
- - - - -
Pband
530 m
3
h
530 m
3
h
Min. Speed
0 %
0 %
Max. Speed
100 %
100 %
Manual mode
OFF
OFF
Speed man.
100 %
100 %
T-Band SA
30.0 K
T-Start SA
15.0
°
C
P-Min SA
70.0 Pa
5.01
Air volume control
Events
Base setup
5.02
Volume control with setpoint depending on
outdoor temperature
Mode
5.01
5.02
E1 Analog In
DSG200
DSG200
E1 K-Factor
75
75
E1 Min.
- - - - -
- - - - -
E2 Function
E1 Max.
- - - - -
- - - - -
|
1E
|
external Setpoint
E1 Decimals
- - - - -
- - - - -
E1 Unit
- - - - -
- - - - -
|
2E
|
external manual mode
E1 Offset
0.0 Pa
0.0 Pa
E2 Function
OFF
6E
|
3E
|
Sensor average to E1
E2 Analog In
- - - - -
TF
E2 Min.
- - - - -
- - - - -
|
4E
|
Sensor comparison to E1
E2 Max.
- - - - -
- - - - -
E2 Decimals
- - - - -
- - - - -
|
5E
|
Sensor difference to E1
E2 Unit
- - - - -
- - - - -
E2 Offset
- - - - -
0.0 K
|
6E
|
Sensor for Setpoint
Further menus see chapters:
•
Controller Setup
•
IO Setup
•
Limits
•
Motor Setup
•
Diagnostic
|
7E
|
Measurement
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
35/67