Rectangular cooling battery for cold water

Installation and Service

Document in original language

172391-EN_GB

2013-10-10 A002

Summary of Contents for PGK

Page 1: ...PGK Rectangular cooling battery for cold water Installation and Service Document in original language 172391 EN_GB 2013 10 10 A002...

Page 2: ...nts 1 Product information 1 2 Dimensions 1 3 Installation 2 3 1 Installing the unit 2 3 2 Water connections 2 3 3 Droplet eliminator 4 4 Capacity 5 4 1 3 rows 5 4 2 4 rows 6 5 Maintenance 8 5 1 Cleani...

Page 3: ...x250 4 2 0 538 288 120 176 43 3 4 1 36 DE 50x25 PGK 500x300 3 2 0 538 338 175 176 43 3 4 1 23 DE 50x30 PGK 500x300 4 2 0 538 338 175 176 43 3 4 1 64 DE 50x30 PGK 600x300 3 2 0 638 338 170 176 43 3 4 1...

Page 4: ...f screws or slip joints The condensate outlet pos C in figure 2 should be connected across a water trap in order to avoid air leakage Note The size of the outlet should be such that no water will rema...

Page 5: ...with a drain connection pos A and the outlet with an air purging connection pos B 4 After the system has been filled with water check the duct cooler and its connections to ensure that there is no wat...

Page 6: ...f air flow Remove the drip tray from underneath Push the droplet eliminator up until the holder secures it in position Fig 5 Carefully check that the air flow is in the direction of the arrow on the d...

Page 7: ...0 17 5 4 6 0 18 9 7 1800 121 30 45 19 8 7 6 0 30 23 4 PGK 500 300 3 2 0 1080 33 25 50 16 5 3 1 0 12 3 3 1080 37 30 45 17 6 5 6 0 22 9 7 1620 66 25 50 17 0 4 4 0 17 6 3 1620 74 30 45 18 9 7 5 0 30 16 0...

Page 8: ...14 8 5486 117 25 50 17 5 14 1 0 56 8 6 5486 140 30 45 19 8 22 5 0 89 20 3 PGK 1000 500 3 2 0 3429 36 25 50 15 9 10 6 0 42 4 1 3429 43 30 45 17 3 18 4 0 73 11 2 5144 72 25 50 16 8 14 4 0 57 7 1 5144 8...

Page 9: ...0 4 2 0 1296 49 25 50 15 9 5 5 0 22 4 1296 49 30 45 17 8 8 1 0 32 9 1944 95 25 50 16 7 7 5 0 30 8 1944 95 30 45 19 0 11 0 0 44 15 2592 153 25 50 17 4 9 3 0 37 11 2592 153 30 45 19 8 13 6 0 54 23 PGK 6...

Page 10: ...ate outlet and blank off the connection so that any remaining condensate will not run out Remove the drip tray by releasing the excentric lock on the front Lower the drip tray about 2 3 cm and then mo...