background image

 

 

1)  Motor operated damper 

discharge 

2)  Motor operated damper inlet 
3) Cable runs 
 

 

 

1) 

Моторизованный

 

клапан

вытяжка

 

2) 

Моторизованный

 

клапан

приток

 

3) 

Кабели

 

 
 

 
 

 

 

 

 

  

 

 

Рис

. 6

 

Рис

. 7 

  

The roof grill is screwd through flange on separate construction 

 

Min. height roof construction (lowest place): 

200 mm 

Max. exterior measurements roof costruction:  1095 x 495 mm 
Min. interior measurements roof construction:  1000 x 400 mm 

 

The roof contruction can be made of wooden timberframe and resistant 
plywood. Construction to be covered by roof covering.

 

 

 

Фланцы

 

крышной

 

решетки

 

крепятся

 

на

 

отдельной

 

конструкции

 

Минимальная

 

высота

 

конструкции

 (

нижняя

 

точка

)  200 

мм

 

Максимальные

 

внешние

 

габариты

 

конструкции

 

1095 x 495 

мм

 

Минимальные

 

внутренние

 

габариты

 

конструкции

  1000 x 400 

мм

 

 

Конструкция

 

может

 

быть

 

изготовлена

 

из

 

деревянной

 

рамы

 

и

 

прочной

 

фанеры

Конструкция

 

должны

 

быть

 

покрыта

 

кровельным

 

материалом

 

 

 

I

NLET

-/

EXHAUST DAMPER 

(additional equipment)

 

The unit is prepared for connecting motor-operated 
dampers in inlet and exhaust duct, i.e. on the middle 
opening on each side of the unit. (fig. 6). The damper is 
supplied for mounting in standard Ø315 mm spiro duct 
and should be mounted as close to the ventilation unit as 
possible. This to make the electrical connection between 
the unit and the damper, as simple as possible. 
 

R

OOF TERMINATION GRILL 

(additional equipment)

 

Roof unit is produced in black plastic with underlying 
sheet steel. Mount the roof unit as a lid on separate 
construction on the roof. Construction to be covered by 
roof covering. To be connected to standard spiro duct (2 x 
Ø250 and 1 x Ø315 mm). The roof grill is screwed through 
flange on separate construction (fig. 7). 
 
 
 
 
 
 
 
 
 
 
 

 

П

РИТОЧНЫЙ

/

В

ЫТЯЖНОЙ

 

КЛАПАНЫ

 (

Принадлежность

Агрегат

 

предусматривает

 

подключение

 

моторизованных

 

клапанов

 

на

 

приточном

 

и

 

вытяжном

 

воздуховодах

т

.

е

на

 

подсоединительных

 

отверстиях

расположенных

 

посередине

 

боковых

 

сторон

 

агрегата

 

(

рис

.6). 

Клапаны

 

предназначены

 

для

 

монтажа

 

на

 

стандартных

 Ø315 

воздуховодах

 

и

 

устанавливаются

 

как

 

можно

 

ближе

 

к

 

самому

 

агрегату

Это

 

упрощает

 

электрическое

 

подключение

 

привода

 

клапана

 

к

 

агрегату

 

К

РЫШНАЯ

 

РЕШЕТКА

 (

Принадлежность

Крышная

 

решетка

 

изготовлена

 

из

 

листовой

 

стали

 

покрытой

 

черным

 

пластиком

Устанавливается

 

крышная

 

решетка

 

как

 

колпак

 

на

 

отдельной

 

конструкции

 

на

 

крыше

Конструкция

 

должна

 

быть

 

покрыта

 

крвельным

 

материалом

Для

 

подсоединения

 

стандартных

 

круглых

 

воздуховодов

 2

х

Ø250 

мм

 

и

 

1

х

Ø315 

мм

Фланцы

 

крышной

 

решетки

 

крепятся

 

на

 

отдельной

 

конструкции

 (

рис

. 7)  

 

 

 

5

 

Summary of Contents for MAXI 1500

Page 1: ...391984 30 08 2004 AT KMB MAXI 1500 2000 Installation instructions...

Page 2: ...page 5 Wall grill page 6 Controller page 6 ELECTRICAL CONNECTION Mains supply service switch page 7 Controller page 7 Bypass section page 8 Damper on inlet and exhaust page 8 Changing the fan speed p...

Page 3: ...t for cleaning Minimum free space for removing the inspection doors is 0 5 m but to obtain acceptable working conditions min 1 0 m is recommended CONNECTING THE TWO SECTIONS The unit is supplied in tw...

Page 4: ...ackets on the attenuator are first screwed on to the MAXI unit Then tighten to the sound attenuator by means of the 4 pcs M8 bolts supplied fig 4 The sound attenuator can also be connected to the extr...

Page 5: ...for connecting motor operated dampers in inlet and exhaust duct i e on the middle opening on each side of the unit fig 6 The damper is supplied for mounting in standard 315 mm spiro duct and should b...

Page 6: ...s 1050 x 520 mm This opening can be used to get the MAXI unit and ducts into the building To fix the grill to the wall loosen frontplate and screw the back plate to the wall fig 8 ABS MAXI 1100 2000 1...

Page 7: ...pplied by installer on mains supply to the unit Note Remember to connect the two unit sections by means of external extension lead and connector The units requires cable main fuses for 3 x 415V 25 A m...

Page 8: ...ock no 4 in the junction box in the unit must be removed 3 1 5 2 230 2 11 3 5 4 In the unit 1 Block 4 terminal 2 4 2 B 2 Block 4 terminal 4 4 4 3 Block 4 terminal 6 4 6 B Damper motor inlet damper B I...

Page 9: ...speed NOTE Only wires marked 2 must be moved 1 2 2 3X400 415 13 CHANGING THE FAN SPEED transformer controlled As a standard the unit for 3x400 V wil have 400 V on full speed and 230 V on helf speed Fu...

Page 10: ...drain If the unit is installed hanging under the ceiling use the drain pipe located beside the junction box inspection door If the unit is installed in standing position use the drain pipe on the exh...

Page 11: ...ilding rooms been cleaned before commissioning the system 4 Are all louvres diffusers and grills in the duct system open 5 Is the unit supplied in accordance with voltage of the building 415 V 3AC 6 I...

Page 12: ...of heating element in operation MAXI 1 2 SETTING SEQUENCE 1 TIME SETTING CALIBRATION OF TEMPERATURES 1 SET CONTRAST SET CONTRAST Press once and SET CONTRAST is displayed Adjust contrast in display by...

Page 13: ...itch between INLET AIR LOW and INLET AIR HIGH to keep max ROOM TEMPERATURE according to setting cooling with outdoor air when real room temperature is higher than set ROOM TEMPERATURE ROOM TEMPERATURE...

Page 14: ...to 3 C factory setting 3 C When outdoor temperature is low condensate water inside the exchanger block might freeze If temperature in exhaust air after the exchanger block is lower than setting on DE...

Page 15: ...Electrical wiring diagrams MAXI 1500 2000 are located in the ventilation unit MAXI 1500 2000 Specifications may be changed without notice Distributed by 15...