_____________________________________________________________________________________________________
Maxi 1100-2000
Operation- and maintenance instructions
204414
Systemair AB
7
Navigating the menus
The start display (the display normally shown) is at the root of the menu tree.
Pressing DOWN
▼
will move you through the menu choices, in this the lowest level. UP
▲
will move
you back through the choices.
To enter a higher menu level, use UP or DOWN to place the display marker opposite the menu you
wish to access and press RIGHT
►
.
If you have sufficient log on privileges the display will change to the menu you have chosen.
At each level there may be several new menus through which you may move using the UP/DOWN
buttons.
Sometimes there are further sub menus linked to a menu or menu item. This is indicated by an arrow
symbol at the right-hand edge of the display. To choose one, use RIGHT
►
again. To back down to a
lower menu level, use LEFT
◄
.
Alarms
Alarm button (
pos.1
in
fig. 2
) opens the alarm queue. By pressing this button and active and non-
acknowledged alarms will be displayed in the menu window. The LED for alarms (
pos.2
in
fig. 2
) is
blinking if there are non-acknowledged alarms and shine steadily if the alarms are still active but have
been acknowledged. If there are multiple alarms use UP/DOWN buttons to move between them. An
alarm can be acknowledged or blocked by using OK and UP/DOWN buttons. To abort and go back to
the start menu select Cancel and press the LEFT button.
For alarm settings see the Commissioning protocol in the installation description (
page 35 and 36
).
Extra stop function
For some alarm types such as electric heating high temperature limit and water heating frost
protection it would be dangerous to not stop the unit on alarm. Therefore, for such alarm types, the
program will always reset the stop function to Active even if the operator should choose Inactive.
It is unfortunately not possible to remove the display text concerning the stop function for these alarm
types. This since the available program space demands that all alarms are treated in the same way in
the display.
Starting up the unit.
Control that all external equipment are connected.
Switch on fuses (
pos.12
and
13
,
fig. 3 & 4
) in the unit.
Switch on the supply voltage.
Set present time and date, set the control temperature and program the week schedule. Do the
necessary settings for extra functions if any.