3.3.3 Damper
The function of the damper is to direct the airflow. When the unit is off, extract damper A and exhaust
damper C are closed and the Fire/Smoke damper B is open to make air flow directly to the outside. When
the unit is operating, extract and exhaust dampers are open and the Fire/Smoke damper is closed to make
air flow through the unit. For more information see chapter .
3.3.4 Drip tray
The drip tray is located under the evaporator/brine coil and collects the water condense that periodically
occur during the cooling operation. The drip tray is made of stainless steel and has a 32 mm connection
for connecting the drain pipe. The drip tray has an electrical heater to prevent the water condense from
freezing.
4 Unit control
4.1 Control panel
The SCP control panel is delivered with a 10 m cable that is connected to the panel and with a fast
coupling contact, connected to the Living HR unit. The contact is connected to the
Corrigo
controller in
the electrical connection box. The cable can be unscrewed in the back of the control panel (figure 4).
Fig. 4 The control panel
Living HR
Operation and Maintenance Instructions
209534
6
Systemair AB