SystemAir K 100 EC Installation,Operation And Maintenance Instruction Download Page 9

2

Use the fast clamps (A) to attach the duct to the product.
Systemair recommends to use FK fast clamps to attach
the duct to the product. The FK fast clamps are available
as an accessory.

Refer to

13 Accessory overview page 30

.

A

3

Tighten the fast clamps (A) around the duct and the
product with the supplied screws. Make sure that there is
a distance between the duct and the product to decrease
vibrations transmitted from the product to the duct
system.

4

If you install the product near a duct bend, do these
steps to prevent vibrations, unwanted noise and de-
creased air pressure:

a.

Measure the distance (A) between the product and
the duct bend.

b.

Make sure that the distance (A) is a minimum of 2.5
x the diameter (B) of the duct system. For circular
ducts, (B) is the nominal diameter. For rectangular
ducts, (B) is the hydraulic diameter.

A

A

B

5

Electrical connection

5.1

To do before the electrical
connection

• Make sure that the electrical connection agrees with the

product specification on the motor name plate.

• Make sure that the environment for electrical connection

is clean and dry.

• Make sure that the wiring diagram that is included with the

supply of the product agrees with the terminals in the con-
nection box.

5.2

To connect the product to the
power supply

• Complete the electrical connection for the motor. Refer to

the motor wiring diagram that is included with the product.

• Make sure that the cross section of the protective earthing

is equal to or larger than the cross section of the phase
conductor.

• Install a circuit breaker in the permanent electrical installa-

tion, with a contact opening of a minimum 3 mm at each
pole.

• If a residual current device (RCD) is installed, make sure

that it is an all-current sensitive RCD. Consider if the prod-
uct has a frequency converter, uninterruptible power sup-
ply (UPS), or an EC motor. EC motors have a leakage
current to earth that is <=3.5 mA.

5.3

Speed controller for EC
motors

• EC motors are controlled through a stepless 0–10 V signal.

• Do not use power supply for the speed controller.

• Refer to

12.3 Wiring diagrams page 18

and the instruction

manual for the external speed controller.

5.4

Motor protection for EC
motors

EC motors have an integrated motor protection. Reset the
motor protection by disconnecting the fan from power supply
for 60 seconds.

5.5

Speed controller for AC
motors

Note:

The speed controller alternatives are different for different
motor types. Make sure that your motor is compatible with
the speed controller type before you use it.

The speed can be controlled by voltage reduction using a
transformer. It is also possible to control the fan speed with
frequency converter if the installed frequency converter has
built in all-pole sine filter and shielded cables are not needed.

7

Summary of Contents for K 100 EC

Page 1: ...Installation Operation and Maintenance instruction EN K Circular duct fan AC EC KV Circular duct fan for wall AC EC Prio Circular duct fan AC EC...

Page 2: ...8 6 Commissioning 8 6 1 To do before the commissioning 8 6 2 To do the commissioning 8 7 Operation 9 7 1 To start a product with an EC motor 9 7 2 To start a product with an AC motor 9 7 3 To stop th...

Page 3: ...cable for ambient temperatures of between 25 C and 70 C K fans KV fans and prio fans are made for installation in cir cular duct systems The product is not applicable for transportation of air that co...

Page 4: ...nnable code 1 6 Find more information about the product on the System air documentation portal1 7 Country of production 8 Airflow direction arrow 9 Scannable code 1 10 Weight kg 11 Serial number part...

Page 5: ...d or maintained The product is repaired with parts that are not original spare parts from Systemair The product is used together with accessories that are not original accessories from Systemair The p...

Page 6: ...rmation about your product The product is not to be used by persons including chil dren with reduced physical sensory or mental capabil ities or lack of experience and knowledge unless they have been...

Page 7: ...information on the name plate and the motor name plate agrees with the operation conditions Install the product in a location where there is space for commissioning troubleshooting and maintenance Mak...

Page 8: ...K 200 EC 1 2 183 5 K 250 EC 1 2 183 5 K 315 EC 1 2 222 4 3 To install the KV fans 1 Attach the product to the wall or the ceiling with the 4 supplied screws 4 4 To install the prio fans 1 Install pend...

Page 9: ...lectrical connection for the motor Refer to the motor wiring diagram that is included with the product Make sure that the cross section of the protective earthing is equal to or larger than the cross...

Page 10: ...sure that the safety devices are correctly installed Make sure that there are no blockages in the air inlet and the air outlet Make sure that installation material and unwanted objects are removed fro...

Page 11: ...To start a product with an AC motor 1 Set the installed safety switch in the ON position 2 Install the external speed controller Refer to the instruc tion manual for the installed speed controller 7...

Page 12: ...cable connections for damage Make sure that the cable glands are tight against the cables X X If flexible connections are installed examine them for damage X X 1 The unusual operation conditions are c...

Page 13: ...il the product operates smoothly Refer to 6 Commissioning page 8 The air output is not sufficient The fan impeller does not turn in the correct direction Make sure that the electrical connection is co...

Page 14: ...al blockage Remove the blockage Phase loss occurs If the motor is a 3 phase motor make sure that no phase is missing The motor does not rotate A component in the power supply is defective Do a check o...

Page 15: ...lectrical connection and installation 2 Recycle the product parts and the packaging at an appli cable disposal location 3 Obey the local and national requirements for disposal 11 Warranty For warranty...

Page 16: ...12 2 Product dimensions 12 2 1 Product dimensions for K fans Note If the unit of measure is not specified the dimensions are given in millimetres G H F B D C E A B A B C D E F G H K 100 M sileo 218 9...

Page 17: ...8 40 88 K 250 EC sileo 336 249 27 30 5 202 144 5 40 88 K 315 M EC 408 314 27 32 5 220 160 5 40 88 K 315 L EC 408 314 27 37 5 225 160 5 40 88 12 2 2 Product dimensions for KV fans Note If the unit of m...

Page 18: ...utside EU A B C D E F G H KV 100 XL EC sileo 5 125 26 99 246 40 304 334 KV 125 XL EC sileo 5 127 26 124 246 40 304 334 KV 150 EC sileo 5 113 25 149 286 40 344 374 KV 160 EC sileo 5 113 25 159 286 40 3...

Page 19: ...60 407 45 314 322 prio 355 EC 45 100 459 15 335 10 60 632 45 353 407 prio 400 EC 45 100 459 15 266 10 60 493 45 399 407 F A B J C K L D E G H I A B C D E F G H I J K L prio 450 65 107 812 18 5 315 12...

Page 20: ...N L K 125 M sileo KV 125 M sileo K fans KV fans 1 phase 230 V K 100 XL sileo KV 100 XL sileo BN BU BK GY C N L K 125 XL sileo KV 125 XL sileo K 150 M sileo KV 150 M sileo K 150 XL sileo KV 150 XL sile...

Page 21: ...meter is installed on the terminal block from the factory Remove the internal potentiometer when you use an external speed controller for the EC fan K fans KV fans 1 phase 230 V K 100 EC sileo KV 100...

Page 22: ...1 14 Alarm For operation the relay is energized connections 11 and 14 are bridged For fault the relay is de energized diagnostics faults Contact rating maximum AC 250 V 2 A B External potentiometer C...

Page 23: ...hen you select the speed controller type Products that are used with this speed controller must have a built in overheating protec tion and must be designed for thyristor speed control L the connectio...

Page 24: ...ormer knob is in one of the positions 1 5 B Mains supply C Earth D Fan E Thermostat F Motor protection If the motor protection is not in use Tk must be looped together FRQ5S E 6A Frequency converter w...

Page 25: ...fixed steps The steps are adjusted by using the control knob on the front of the unit RTRD2 7 N L1 L2 L3 L3 L2 L1 N PE U V W PE V W U TB TB TK TK RT L L N 230 V AC RT FS FS Y M 3 0 1 A A A B C D F E A...

Page 26: ...0 1 5 4 2 3 C B D E G F RTRDU 0 1 A A A A If the function is not necessary the terminals must be bridged B Contact rating 230 V AC maximum 1 A C Time switch D OFF ON E OFF ON only by reset F Mains su...

Page 27: ...asic EC Basic 230V AC 1 IN Vac 2 IN Vac 4 Out 5 GND 10V 0 10V GND MTV 1 10 MTV 1 010 1 IN Vac 2 IN Vac 4 Out 5 Out 10V 0 10V GND 230V AC S 5EC FRQ MTP 10 GND 10V A 10V 0 10V GND EC Vent EC Vent IN RPM...

Page 28: ...y NO Relay NC 10V 0 10V GND Din1 12 3 6 Wiring diagrams for demand control for EC motors EC Basic EC Basic T for temperature control EC Basic 230V AC 1 IN Vac 2 IN Vac 4 Out 5 GND 10V 0 10V GND EC Bas...

Page 29: ...stem has 2 units The control board CB and the room unit RU Connect the fan to the control board and remove the internal potentiometer EC Vent IN RPM PWM IN 10V OUT PWN GND TACH optional 10V 0 10V PWM...

Page 30: ...GND A D PT1000 24V N out N in L out L in IN3 IN2 IN2 A Mains supply 230 V 1 AC 10 A B Analogue sensor for example pressure sensor C Analogue sensor for example pressure sensor type PT1000 D Digital s...

Page 31: ...System neutral Mains supply 24 V AC Signal neutral Signal neutral Output minimum 0 10V Output maximum 0 10V PCA 1000D2 Pressure controller For constant air volume control CAV or variable air volume co...

Page 32: ...FFR Filter cassette 5 FK fast clamp 6 Fan 7 LDC Silencer 8 CWK Water cooling battery 9 VBC Water heating battery 10 CB and CBM Electrical duct heaters 11 SPI Iris damper 12 Balance S supply air diffu...

Page 33: ...ve electromagnetic compatibility EMC 2014 30 EU EN 62233 2008 Measurement methods for electromagnetic fields of household appliances and similar apparatus with regard to human exposure EN 61000 6 2 20...

Page 34: ...2233 2008 Measurement methods for electromagnetic fields of household appliances and similar apparatus with regard to human exposure EN 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 2 Generi...

Page 35: ...33...

Page 36: ...air AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously agreed specifications Systemair Sverige AB...