Airflow adjustment & balancing

BALANCING THE AIRFLOWS IS CRUCIAL TO ENSURE OPTIMAL OPERATION OF THE UNIT. IF THE AIRFLOW IS NOT PROPERLY BALANCED, THE 
FOLLOWING ISSUES MAY OCCUR:

•  SIGNIFICANT POSITIVE OR NEGATIVE PRESSURE INSIDE THE HOUSE
•  UNIT’S EFFICIENCY MAY BE NEGATIVELY AFFECTED
•  UNIT’S DEFROST MAY NOT WORK EFFECTIVELY
•  CAN LEAD TO AIR LEAKS OR BACKDRAFTING OF ANY COMBUSTION APPLIANCES.

The airflow adjustment and balancing procedure consists of adjusting the fresh airflow to make sure it meets the requirements for the building and then 
balance the system to make sure there is an equal amount of stale air being exhausted. In the case that the airflow is not exactly the same, it is 
recommended to have a higher stale airflow of up to 10% in colder climates to ensure that the temperature of the fresh airflow coming from the outside 
is as close to the room temperature as possible.

GENERAL PREPARATION:

Before performing the adjustment and balancing for unit, make sure to check the following:

•  Seal all the ductwork
•  Fully open all dampers (if present)
•  Turn off all other exhaust appliances such as range hood, dryers, bathroom fans, etc.
•  If performing balancing during cold weather, make sure the unit is not operating in defrost mode.
•  If the installation type is Simplified or Partially Dedicated, make sure that the furnace/air handler blower is operating at normal speed during 

the balancing sequence.

•  When reading with a mechanical type manometer (Magnehelic), make sure the manometer is placed on a level surface

For optimal performance, ERV unit should be re-balanced after a major renovation or after the installation of extra grilles or registers.

• 

In cold climates, continuous excessive positive pressure inside the house may drive moisture inside the external walls of the 
house. Moisture present inside the external wall may condense if the outside temperature is cold enough and can cause damage 
to structural components. A symptom of excessive positive pressure inside a house is frozen door locks.

•  Continuous excessive negative pressure can have undesirable effects. In some geographic locations, negative pressure can 

increase the infiltration of soil gases such as methane and radon. Negative pressure is also undesirable where combustion 
equipment is present and may cause back drafting of the combustion gases.

ADJUSTING AIRFLOWS USING INTEGRATED BALANCING SYSTEM

Adjustable dampers are integrated into the Fresh Air to Building and the Stale Air to Outside duct connections. Those dampers replace the installation of 
separate back draft and balancing dampers in the duct line.

The integrated dampers are preset at the fully opened position. In order to reduce the amount of airflow, turn the adjustable lever using a flat screw driver 
by turning it counter clock wise. Turning the lever clockwise may damage the plastic screw head. Follow the balancing steps to properly adjust the airflow.

Summary of Contents for fantech FIT 120E

Page 1: ...y at any time and without notice any or all of its products features designs components and specifications to maintain their technological leadership position Please visit our website www fantech net...

Page 2: ...combustion equipment i e Gas Furnaces Oil Furnaces Wood Stoves etc Products are designed and manufactured to provide reliable performance but they are not guaranteed to be 100 free of defects Even re...

Page 3: ...ng the ducting to the weatherhood 9 INTERIOR DUCTING INSTALLATION General Tips 10 Installing duct to ERV 10 Supply Exhaust air grilles location 10 ERV INSTALLATION 11 Mounting 12 AIRFLOW ADJUSTMENT BA...

Page 4: ...20 CFM if no 0 1 CFM 0 47 L s 1 L s 2 13 CFM Room Count Method DETERMINING YOUR AIRFLOW REQUIREMENT ASHRAE method Ventilation Air requirements Floor area Bedrooms 1 2 3 4 5 Ft2 m2 CFM L s CFM L s CFM...

Page 5: ...The ERV s airflow must be balanced after installation using the procedure found in the section AIRFLOW BALANCING Suggested installation for Hydronic baseboard Infloor heating Electric baseboard Mini s...

Page 6: ...ace interlock Stale air to outside Fresh air from outside Fresh air to living areas Fantech energy recovery ventilators ERV that use a supply fan shutdown for frost preven tion do not include an outdo...

Page 7: ...n for frost preven tion do not include an outdoor air motorized damper If you are using a simplified instal lation i e connecting the ERV supply air duct to a furnace s return air duct the ERV must op...

Page 8: ...implified installation Option 1 is recommended Suggested installation for When bathroom and kitchen already have local exhaust system May be suitable for retrofitting Benefits Least expensive installa...

Page 9: ...er which acts as a vapor barrier must be completely sealed to the outer wall and the ERV using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will seal the inn...

Page 10: ...ible duct to prevent leakage between the ducting and the duct connection In the case of solid ducting slide duct over duct connection screw in place and seal Supply air grilles location In homes witho...

Page 11: ...sate drain if included must be installed so that the condensate drains and is protected from freezing The attic is easily accessible for equipment maintenance and inspection Connecting appliances to t...

Page 12: ...he bracket is straight Mounting MOUNTING BRACKET 4 Install the unit by sliding the unit in the guide of the ceiling bracket We recommend placing the duct on the unit at this stage of the unit s instal...

Page 13: ...a washer provided in the top 4 corners of the unit and tighten 3 Install a spring on each chain Hook the spring in the links so a loop is created in the chain The spring will then support the unit s w...

Page 14: ...perating at normal speed during the balancing sequence When reading with a mechanical type manometer Magnehelic make sure the manometer is placed on a level surface For optimal performance ERV unit sh...

Page 15: ...airflow velocity should be measured on a section of steel ducting Reading should also be taken at a minimum distance of 457 mm 18 from the unit or elbow Measurement should also be made prior to any t...

Page 16: ...LCD ECO mode selects the best operating mode and speed for the season minimizing energy use associated with ventilation Set preferred indoor relative humidity range and ventilation mode for day and ni...

Page 17: ...stem Use in bathroom kitchen laundry room WALL CONTROLS CONT D MDEH SERIES FEATURES CONNECT TO MDEH1 Rotary dial Dehumidistat Multiple units can be used We recommend setting the relative humidity abov...

Page 18: ...18 Wiring diagram Observe polarity on all accessory controls where applicable...

Page 19: ...CTION TO A COOLING SYSTEM On some newer furnaces and older thermostats energizing the R and G terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on the co...

Page 20: ...restricting airflow Check duct installation Improper speed control setting Increase the speed of the ERV i e change unit control from REDUCED to NORMAL speed ERV airflow improperly balanced Have cont...

Page 21: ...he filter 3 Remove the core from the unit 4 With one of your core s air inlets facing down place it in a large sink bathtub or shower 5 Pour clean tap water through the face of the core facing upwards...

Page 22: ...damages incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to sup...

Page 23: ...rtiellement ou enti rement en tout moment et sans pr avis les caract ristiques la conception les composants et les sp cifications de ses produits afin de conserver sa position de leader de technologie...

Page 24: ...ffage vacuation fournaise gaz fournaise mazout po le bois etc Les produits sont con us et fabriqu s pour fournir une performance fiable mais ils ne sont pas garantis 100 sans d faut M me les produits...

Page 25: ...uits avec hottes 31 INSTALLATION DES CONDUITS INT RIEURS Conseils pratiques 32 Installation des conduits sur le VRE 32 Emplacement des grilles d approvisionnement et d vacuation 32 INSTALLATION DU VRE...

Page 26: ...de la derni re colonne Si oui ajoutez 10 L s 20 pi3 min Sinon 0 1 pi3 min 0 47 L s 1 L s 2 13 pi3 min M thode compte de pi ces D TERMINER VOS BESOINS DE VENTILATION M thode ASHRAE D bit d air recomman...

Page 27: ...ge du pr sent manuel d installation Installation sugg r pour Plinthe eau chaude Chauffage de planch Plinthe lectriques Thermopompe mural bibloc Avantages Fourni la meilleure r partition de l air frais...

Page 28: ...onduit peuvent tre diff rents selon le mod le Fournaise air puls Air vici vacu l ext rieur Air frais provenant de l ext rieur Les ventilateurs r cup rateurs d nergie VRE de Fantech qui utilisent un ar...

Page 29: ...ation synchronis de la fournaise Air frais distribu l int rieur Air vici vacu l ext rieur Air frais provenant de l ext rieur L appareil est quilibr vitesse normale et pendant que le ventilateur de la...

Page 30: ...ernisation Avantages Type d installation le moins dispendieux mettre en place RACCORDEMENT DIRECT du FLUX D AIR D APPROVISIONNEMENT du VRE la BOUCHE DE REPRISE D AIR DE LA FOURNAISE Air vici vacu l ex...

Page 31: ...tre compl tement scell sur le mur ext rieur et le VRE l aide de ruban ou de produit de calfeutrage D posez un cordon de produit de calfeutrage de premi re qualit du mastic d isolation acoustique de pr...

Page 32: ...es crochets Ensuite installez un attache c ble par dessus le conduit flexible afin de pr venir des fuites entre le conduit et le collet Dans le cas d un conduit galvanis faites le glisser sur le colle...

Page 33: ...tre install de telle sorte que les drains de condensat et est prot g contre le gel Le grenier est facilement accessible pour l entretien du mat riel et de l inspection Il n est pas recommander de rac...

Page 34: ...n caoutchouc Assurez le support est droit 5 Installez l appareil en faisant glisser l unit dans le guide Nous vous recommandons de placer le conduit de l unit ce stade de l installation de l unit 3 En...

Page 35: ...s sup rieurs du VRE et serrez 3 Installez un ressort sur chaque cha ne Accrochez le ressort de sorte qu une boucle est cr e dans la cha ne Le ressort supportera le poids du VRE et absorbera les vibrat...

Page 36: ...son froide assurez vous que l appareil ne fonctionne pas en mode de d givrage Si le type d installation est Simplifi ou partiellement Simplifi assurez vous que le ventilateur de la fournaise op re dur...

Page 37: ...ez le d bit d air dans un conduit d acier au moins 457mm 18 po de l appareil ou d un coude et avant toute connexion avec un autre conduit Les mesures devraient tre prises avant toute transition dans l...

Page 38: ...ent et la vitesse optimaux pour la saison minimisant la consommation nerg tique associ e la ventilation R glage de la plage d humidit int rieure relative et du mode de ventilation favoris pour le jour...

Page 39: ...salle de bains la cuisine et la salle de lavage COMMANDES MURALES SUITE S RIE MDEH CARACT RISTIQUES RELIER MDEH1 D shumidistat molette Plusieurs commandes peuvent tre utilis es Nous recommandons de fi...

Page 40: ...40 Sch mas lectroniques Respectez la polarit sur tous les accessoires de contr les Le cas ch ant...

Page 41: ...ion de la borne Y du thermostat et cons quemment la mise sous tension du syst me de refroidissement Si votre syst me est muni d un tel type de thermostat vous devez respecter le c blage de verrouillag...

Page 42: ...VRE i e changez la vitesse de l appareil de vitesse R DUITE vitesse NORMALE avec le contr le D s quilibre du d bit d air du VRE Demandez au contracteur d quilibrer le VRE Les conduits ont tomb ou ne s...

Page 43: ...s d air de votre noyau r cup rateur d nergie vers le bas placez le dans un grand vier baignoire ou douche 5 Versez de l eau du robinet travers la face du noyau jusqu ce qu elle soit clair lors de la s...

Page 44: ...codes en vigueur dans sa r gion Les pi ces y compris les pi ces de rechange pos es ult rieurement sont garanties pendant 5 ans partir de la date d achat de l appareil Les moteurs des ventilateurs sont...

Page 45: ...RV CTRL Replacement H F 428252 6 Auto Transformer 411963 7 Collar 5 Oval w Stop 412826 8 Collar 5 Oval wo Stop 412827 9 Screw Set Slotted 8 32 x 5 16 412836 10 Cap w Tab Plastic Tapered 412839 11 Damp...

Page 46: ...46 Note...

Page 47: ...47 Note...

Page 48: ...make technical changes For updated documentation please refer to www fantech net Fantech Fantech se r serve le droit de faire des changements techniques Pour de la documentation jour s il vous pla t...

Reviews: