1.0 APPLICATION 

 

Smoke  extract  roof  fans  are  designed  for  use  in  powered  smoke  and  heat  exhaust 

ventilating systems in the event of fire, and ventilating in normal conditions. Ventilated areas 

and emergency exits contribute to easier evacuation of people and equipment in the event 

of fire, and to faster and more efficient fire extinguishing; they protect the building structure 

and  equipment  against  excessive  temperatures  and  decrease  fire  escalation  to  the 

surrounding areas. 

 

  Fire resistance of fans: 400C, 120 min;  

  installation on roofs over heated buildings; 

  horizontal outlet (DVG-H) or vertical outlet (DVG-V); 

  EC-motor outside air stream; 

  daily ventilation of medium with temperature from -20 up to 120°C, supposing 

continuously operation, up to 80°C in standstill; 

  the fans DVG must not be mounted in explosion hazardous zones; 

  0-10V speed control input; 

  Modbus controllable; 

  Fire mode to disable motor and controller protection in case of fire. 

 

 

 

Not intended or unprofessional use can be dangerous for life of user or  
third person. It can lead to damage of the fan. The risk for this carries the 
operator alone. 

 

 
 

2.0 TECHNICAL DESCRIPTION 

 

Casing 

Electric motor with impeller is fastened to a sturdy supporting construction. The casing 

cover is made of see water resistant aluminium. 

Impeller 

Impeller of DVG fan is manufactured from galvanized steel. It is fastened with taper bush 

and secured screw directly on to the motor shaft. Dynamically balanced in accordance with 

ISO 1940 T1, class G6,3. 

Electric motor 

Fans are serial equipped with EC (electronically commutated) high efficiency electric motors 

for single-phase current 200 to 265V, 50/60Hz Hz (sizes 355 and 450), rsp. 342 to 506V, 

50/60Hz Hz (sizes 560, 630, 800). Protection class IP 54.  Insulation class F.  

Max. RPM: 1500 RPM, rsp. 900 RPM at DVG 800. 

Detailed description of controller connection and control possibilities please see in attached 

instructions of controllers. 

 

 

3.0 TRANSPORT AND STORAGE 

 

3.1 Transport 

 

Fans are delivered in wooden crates or cardboard boxes. It is recommended to leave the 

fans in original packing during transport to the place of installation as well as to load and 

unload  them  carefully  to  avoid  any  possible  damage.  The  fans  must  be  transported  in  a 

horizontal position only. During transport and loading/unloading the weight of the fan must 

be considered. 

Summary of Contents for DVG-H-EC F200

Page 1: ...maintenance of roof fans DVG EC Appendixes 1 Mounting of service switch Mounting of vertical outlets for DVG V 3 4 Accessories mounting 5 Bridges in controller and wiring schemes Controller Compacto i...

Page 2: ...allation 4 4 2 Safety instructions for installation commissioning maintenance and controlling 4 4 3 Installation of the fan 4 4 4 Instructions for installation 5 5 0 COMMISSIONING 6 6 0 APPROVAL 6 7 0...

Page 3: ...he risk for this carries the operator alone 2 0 TECHNICAL DESCRIPTION Casing Electric motor with impeller is fastened to a sturdy supporting construction The casing cover is made of see water resistan...

Page 4: ...protective guard EN 13857 After installation impeller must not be accessible anymore During installation commissioning maintenance and controlling unauthorized personal should not have access to the f...

Page 5: ...qualified electrician In case of unprofessional connection guarantee will not be valid The risk for this carries the operator alone Observe attached detailed instructions of motor and controller suppl...

Page 6: ...oints for leakage Check if foreign objects were left in the fan or in the connected ducts Check if protective elements are fitted Check the accuracy of the electric wiring and connections to the mains...

Page 7: ...not deviate from the starting values at installation In case that parameters deviate the electric motor or the impeller have to be replaced or repaired This must only be done by an authorised customer...

Page 8: ...acturer 9 0 GUARANTEE Guarantee will be valid only if transport storage installation connection and periodical maintenance have been executed in compliance with the above instructions and local regula...

Page 9: ...age des Revisionsschalters Montage der Umlenkungsbleche bei DVG V Appendix 1 Mounting of service switch Mounting of vertical outlets for DVG V Bilaga 1 Beslag av tj nste kopplar beslag av lodlinjeutta...

Page 10: ...Zubeh r Montage Appendix 3 Accessories mounting Bilaga 3 Tillbeh r installation 3 DVG H SSG F ASG F VKG F ASSG F DVG H VKG F ASSG F FDG F DVG H VKG F SSG F ASG F ASSG F DVG H VKG F SSGE F FDGE F ASG...

Page 11: ...Zubeh r Montage Appendix 4 Accessories mounting Bilaga 4 Tillbeh r installation 4 DVG V SSG F ASG F VKG F ASSG F DVG V VKG F ASSG F FDG F DVG V VKG F SSG F ASG F ASSG F DVG V VKG F SSGE F FDGE F ASG...

Page 12: ...6 7 at 3 controller and connect potentiometer R 1k according to wiring scheme For fan speed setting using AN1 input 0 10V remove bridge 9 10 6 7 at 3 controller and connect 0 10V input according to w...

Page 13: ...DVG 355 355 EC DVG 450 EC Wiring 1 230V 50 60Hz 27 11 2013...

Page 14: ...DVG 560 EC DVG 630 EC DVG 630 EC DVG 800 EC Wiring 3 400V 50 60Hz 27 11 2013 27 11 2013...

Page 15: ...03 2012 DVG EC overensstammer med bestammelserna i testrapporter fran LGAI Technological Center S A Bellaterra Barcelona nr 09 100216 502 av den 12 juni 2009 och nr 11 2673 1035 av den 14 juni 2011 D...

Reviews: