Troubleshooting

Note:

If you cannot find a solution to your problem in this section, speak to Systemair technical support.

Problem

Cause

Solution

The product does not operate smoothly.

The fan impeller is not correctly
balanced.

Speak to Systemair technical support.

There is dirt on the fan impeller.

Clean the fan impeller carefully. Refer
to

8.2 To clean the product page 9

.

The fan impeller has damages or
deformations because the transported
air contains aggressive media.

Speak to Systemair technical support.

The fan impeller does not turn in the
correct direction.

Make sure that the electrical connection
is correctly done.

The fan impeller has deformations
because of too high temperatures.

• Replace the fan impeller.

• Make sure that the temperature of

the transported air is not higher than
the value on the name plate.

There are unusually strong vibrations in
the product or the duct system.

Make sure that the product is correctly
installed. Do a check of the duct system.

The product is operated in a resonant
frequency range.

Increase or decrease the fan speed
until the product operates smoothly.
Refer to

6 Commissioning page 7

.

The air output is not sufficient.

The fan impeller does not turn in the
correct direction.

Make sure that the electrical connection
is correctly done.

The electrical connection is not
correctly done.

Make sure that the electrical connection
agrees with the wiring diagrams.

The air pressure is too low because of
incorrect installation.

Do the necessary changes in the duct
system and installed components to
increase the air pressure. Refer to

6

Commissioning page 7

.

The airflow shutters are closed or not
fully open.

Adjust the airflow shutters.

There is blockage in the air inlet or the
duct system.

Remove the blockage.

The product is not applicable for the
installation location.

Make sure that the product is applicable
for the installation location.

The motor power is decreased because
of too high temperature in the motor.

Note:

This is applicable for EC motors only.

• Do a check of the ambient

temperature.

• Make sure that the space around the

motor is sufficient to keep the
temperature down.

There is unusual noise when the
product starts or operates.

There is strain in the connections of the
duct system.

Loosen the connections, align the parts
of the duct system correctly and tighten
the connections.

10

Summary of Contents for AxZent 400

Page 1: ...Installation Operation and Maintenance instruction AxZent Thermo Centrifugal fan AC AxZent Thermo Centrifugal fan EC...

Page 2: ...or AC motors 6 5 6 To install motor protection for AC motors 7 6 Commissioning 7 6 1 To do before the commissioning 7 6 2 To do the commissioning 7 7 Operation 8 7 1 To start a product with an EC moto...

Page 3: ...t systems The product can also be installed with free suction or free dis charge together with a protection grille The product is not applicable for transportation of air that contains explosive flamm...

Page 4: ...uct name AxZent Dimension 400 450 500 560 630 Motor type EC Electronically commutated 1 phase EC L Electronically commutated 3 phase E4 4 pole AC motor 1 phase DV 4 pole AC motor 3 phase D2 2 pole AC...

Page 5: ...adjacent area during all work on the product Make sure that you know how to stop the product quickly in an emergency Use applicable safety devices and personal protective equipment during all work on...

Page 6: ...duct outdoors it is necessary to in stall a weather protection roof To decrease vibrations transmitted from the product to the duct system Systemair recommends to install vi bration dampers fast clamp...

Page 7: ...ect in the fan housing b Install the product correctly in relation to the airflow 2 Install the product with accessories that decrease vibra tions in the product and the duct system a If you install t...

Page 8: ...ductor Install a circuit breaker in the permanent electrical installa tion with a contact opening of a minimum 3 mm at each pole If a residual current device RCD is installed make sure that it is an a...

Page 9: ...sure that the safety devices are correctly installed Make sure that there are no blockages in the air inlet and the air outlet Make sure that installation material and unwanted objects are removed fro...

Page 10: ...d with the 0 10 V signal speed con troller If an external speed controller is not installed ad just the fan speed directly with the integrated potentiometer 7 2 To start a product with an AC motor 1 S...

Page 11: ...protective equipment and the me chanical protective equipment operates correctly X X Make sure that you can read the name plates of the product X X Examine all cable connections for damage Make sure...

Page 12: ...l the product operates smoothly Refer to 6 Commissioning page 7 The air output is not sufficient The fan impeller does not turn in the correct direction Make sure that the electrical connection is cor...

Page 13: ...al blockage Remove the blockage Phase loss occurs If the motor is a 3 phase motor make sure that no phase is missing The motor does not rotate A component in the power supply is defective Do a check o...

Page 14: ...lectrical connection and installation 2 Recycle the product parts and the packaging at an appli cable disposal location 3 Obey the local and national requirements for disposal 11 Warranty For warranty...

Page 15: ...r to 1 5 Name plate page 2 for more information Motor data Refer to the motor name plate or the technical documentation from the motor manufacturer 12 2 Product dimensions A E B C D F G H AxZent 400 A...

Page 16: ...The wires in the motor cables have these colours Wire Colour 10V Red 0 10V PWM Yellow GND Blue 12 3 1 Wiring diagrams for speed controllers for EC motors Note An internal potentiometer is installed on...

Page 17: ...Vac 2 IN Vac 4 Out 5 GND 10V 0 10V GND MTV 1 10 MTV 1 010 1 IN Vac 2 IN Vac 4 Out 5 Out 10V 0 10V GND 230V AC S 5EC FRQ MTP 10 GND 10V A 10V 0 10V GND EC Vent EC Vent IN RPM PWM IN 10V OUT PWN GND TAC...

Page 18: ...diagrams for ON OFF controls for EC motors CO2RT R D CO2RT R D 24V AC Supply Neutral Common Relay NO Relay NC 10V 0 10V GND Din1 IR24 P IR24 P 24V AC or DC 24V Neutral Common Relay NO Relay NC 10V 0 1...

Page 19: ...5 MPR Mounting ring for vertical installation through a roof 6 WSD Weather protection roof 7 LRK Airflow shutter 8 GFL Counter flange 9 MFA Mounting foot 10 FSD Spring vibration damper for horizontal...

Page 20: ...ty EMC 2014 30 EU DIN EN IEC 61000 6 1 2019 11 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for residential commercial and light industrial environments DIN EN IEC 61000 6 4 2...

Page 21: ...y for residential commercial and light industrial environments DIN EN IEC 61000 6 4 2019 11 Electromagnetic compatibility EMC Part 6 4 Generic standards Immunity for industrial environments The Restri...

Page 22: ...rves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously agreed specifications Systemair GmbH Seeh fer Str 45 9...

Reviews: