![SystemAir AR 1000DS Installation And Operating Instructions Manual Download Page 11](http://html.mh-extra.com/html/systemair/ar-1000ds/ar-1000ds_installation-and-operating-instructions-manual_1423202011.webp)
7
8
Electrical connection
Safety information
♦
Observe 2
♦
Prevent the ingress of water into the connection box.
Connection
♦
Check if the data on the nameplate matches the
connection data.
♦
Complete the electrical connection according to the
circuit diagram.
♦
Fans with EC- motors must be switched on/off via the
control input.
♦
Connect the cable end in a dry environment.
♦
Install a circuit breaker in the permanent electrical
installation, with a contact opening of at least 3 mm
at each pole.
Protective grounding wire
The protective grounding must have a cross-section equal to or greater than that of the phase conductor.
Residual current circuit breaker
All-current-sensitive residual current circuit breakers are required for use in alternating-current systems with 50/60
Hz, in combination with electronic devices such as EC motors, frequency converters or uninterruptible power supplies
(UPS).
Table 3 Description of electrical connections of the following fans: AW 200 EC sileo (#35854), AW 250 EC sileo
(#35855), AW 300 EC sileo (#35857), AW 350 EC sileo (#35859)AW 400 EC sileo (#35860), AW 450 EC sileo
(#35863)
Wire
no.
Connection
Color
Function/assignment
CON10
L
black or
brown
Power supply, see name plate for voltage range
CON11
N
blue
Neutral conductor
CON12
PE
green/
yellow
Protective conductor
1
GND
blue
GND-connection of the controller interface
2
0...10 V PWM
yellow
Controller input 0...10 V or PWM
3
10 V
red
Voltage output 10 V / Short-circuit-proof power supply for external
devices (e.g. poti)
I max=1.1mA:
AW 200 EC sileo (#35854)AW 250 EC sileo (#35855), AW 300 EC sileo
(#35857), AW 450 EC sileo (#35863)
I max=10mA:
AW 350 EC sileo (#35859)AW 400 EC sileo (#35860)
4
Tacho*
white
Speed output: Open Collector, 1 impulse per revolution, electrically
isolated, Isink_max = 10 mA
NC*
white 1
Status relais, open for failure
COM*
white 2
* Not available with every device
| 004