ADJUSTING AIR FLOW
CHANGING THE AIR VOLUME VIA
REPROGRAMMING CONTROL
The settings are managed via the function
buttons on the control. Speed 1 can be pro-
grammed between 1.6 - 5 V and speed 2
between 2 - 8 V. Speed 3 is always 10 V.
The speeds can overlap each other. Upon
delivery the settings are 2 V for speed 1
and 5 V for speed 2.
Activate programming mode
All settings must be made in programming
mode.
Keep buttons
A
and
B
depressed for 5 se-
conds. The programming mode is indicated
by the LEDs flashing once.
Button C selects which speed to set. Press
until LED 1 lights continuously to set speed
1 or LED 2 to set speed 2.
Attention!
If no button is pressed for 30 seconds,
programming mode is exited and the
previously set voltages remain.
Set voltage is indicated by flashing LEDs for
buttons A and B. The LEDs flash with indica-
ting change from factory setting to selected
speed.
Button B - Used to increase the speed one
increment. Button A - Used to decrease the
speed one increment. Stepping is incre-
mented in half volt units. The set voltage is
indicated by the LEDs for buttons A and B
by a number of flashes according to table 1
for speed 1 or table 2 for speed 2.
Save settings
Once programming is complete, save the
settings by holding in buttons
A
and
B
for 5
seconds. Saved programming is indicated
by the LEDs flashing 5 times.
991.0566.818/126376/2019-02-27