15.1 Safety information
♦
Cleaning may only be carried out by adequately qualified persons, details see Table 1
♦
Observe the 5 rules of electrical safety, see 3.3
♦
The impeller must be at a standstill.
♦
Pay attention to the safety data sheet of the chemical substances transported with the fan.
Warning
Risk of ignition as a result of electrostatic charges.
Because of the MUB EX plastic parts in the housing, a damp cloth has to be used for cleaning to avoid the
risk of ignition as a result of electrostatic charges.
15.2 Procedure
Important
Keeping the fan clean extends its service life.
♦
Drain condensation off
♦
Only use compressed air if the fan is used for conveying air in the presence of gases/vapours without
hovering particles.
♦
If the fan is used in an environment with vapours of specific chemical substances, get information from
the chemical safety data sheet with a view to the recommended cleaning products.
♦
Install a filter monitor.
♦
Do not use steel brushes or sharp-edged objects.
♦
Do not use a high-pressure cleaner (steam jet cleaner) under any circumstances.
♦
Do not bend the fan blades when cleaning.
♦
When cleaning the impeller, pay attention to balance weights that have been positioned
♦
Keep the airways of the fan clear and clean them if necessary with a brush.
16
Deinstallation/dismantling
♦
Pay attention to the safety data sheet of the chemical substances transported with the fan.
Deinstall and dismantle the fan in reverse order of installation and electrical connection.
17
Disposal
♦
Ensure material is recycled. Observe national regulations.
♦
The device and the transport packaging are predominantly made from recyclable raw materials.
♦
Disassemble the fan into its components.
♦
Separate the parts according to:
• reusable material
• material groups to be disposed of (metal, plastics, electrical parts, etc.)