TControl Easy DX-Air Curtain (Item No. 189421) 

Room thermostat for DX air curtain

 

 

 

 

SYSTEMAIR GmbH German

[email protected]

 ode

http://www.systemair.de

 

 

Issue date: 03.11.2020

  

 

 

 

 

 

 

 

 

 

 

Page 6 / 11 

 

The analog 0..10 V output for the EC fan in automatic mode outputs the voltage value according to the control value of the controller. For manual 

switching, the following voltage values apply to the EC output: 

Fan stage 

Voltage 

Parameter 

OFF 

0V 

 

(Speed level 1) LOW  

3,3 V 

Reg. 0x124,  default = 33 

(Speed level 2) Medium  

5,2 V 

Reg. 0x125,  default = 52 

(Speed level 3) High  

7,5 V 

Reg. 0x126,  default = 75 

°F/°C selective

 

Temp display range is 32 °F..99 °F, respectively 0 °C..50 °C (factory default is °C). 

Temperature offset correction (Register address 0x0107)

 

An adaptation of the measured temperature measured value takes place with the help of the offset correction with which the thermal power loss 

can be compensated. 

Set the Temperature set point range (Register address 0x0110 – 0x0112)

 

Press 

“▲”or “▼” key

 to adjust the temperature set point range. Factory default (°C) is 16 °C..30 °C

When °F has been selected Temp range is 

60 °F..86 °F. 

Key lock selection (Register address 0x010D)

 

If a key is pressed that is locked, the lock symbol 

 will appear for 2s and blink 2x but no further action is taken. 

Power failure – Restart selection (Register address 0x010C)

 

On the LCD, there are three symbols 

   

   

 that define how the thermostat will restart after a power failure:  

 Keep thermostat switched OFF  

 Switch thermostat to last state before power failure (Record and Memorize) 

 Turn the thermostat ON  

Storage during power loss

 

The status will be kept in EEPROM, while the power failure, so no data will be lost.  

The setpoint is not saved. The standard setpoint after power-on reset applies, register address 271 (0x010F). 

 

Occupancy (OCC) 

If the input is configured for an Occupancy sensor. If the sensor indicates “UnOccupied” the current setpoint will be replaced by the Eco Mode 

Setpoint Temp. The display will show the leaf symbol and the lettering ECO to indicate the ECO mode. Once the room occupancy is detected 

again the previously used Setpoint will be restored and the leaf symbol will not be showing any more.  

Sensor failure alarm

 

In case the room NTC temp sensor is open or short, thermostat switches fan to medium and the valve to 50% (5V output, 50%). The display will 

show (blinking) error code: “E1” 

Thermostat will allow to control fan manually as well as the valve output using the “▲”or “▼” keys. Every operation 

of the “▲”or “▼” key

s will decrement / increment the output voltage by 1V = 10%  AND the PWM by 10%. The percentage is shown in the display.  

 

 

Summary of Contents for 189421

Page 1: ...n with any equipment that in case of a failure may threaten directly or indirectly human health or life or result in danger to human beings animals or assets Ensure all power is disconnected before installing Do not connect to live operating equipment CAUTION Risk of electric shock due to live components within the enclosure especially devices with mains voltage supply usually between 90 265 V Ple...

Page 2: ... limited in time are TECHNICAL DATA Measuring values temperature Output voltage terminal 1 2 2x 0 10 V for heating and cooling min load 10 kΩ terminal 1 3 terminal 1 4 2x 0 10 V for fan min load 10 kΩ Output switch contact terminal 6 8 Cooling 250 V max load 3 A terminal 7 8 Heating 250 V max load 3 A Network technology RS485 Modbus RTU half duplex baud rate 4 800 9 600 19 200 or 38 400 parity non...

Page 3: ...or DX air curtain SYSTEMAIR GmbH Germany info systemair de oder http www systemair de Issue date 03 11 2020 Page 3 11 CONNECTION PLAN Terminal 4 is designed for an additional 2nd fan and outputs the same actuating signal in parallel with terminal 3 DISPLAY PANEL ...

Page 4: ... parameter can be increased decreased using the or keys With the Mode Key the display will move on to the next parameter Once the end of the table is reached the parameter setting will be exited to normal operation Nr Parameter Beschreibung Standardeinstellung 1 Language setting 0 Deutsch 1 Englisch 0 2 Unit system temperature 0 C 1 F 0 3 Sensor configuration 0 internal sensor 1 external sensor NT...

Page 5: ...n the floor Pressing the button once switches the display on and the device to ECO mode In ECO mode it controls the room temperature to the setpoint predefined by register 275 and 276 0x0113 0x0114 The display will show the average of both ECO Setpoint Temperatures 25 18 2 21 5 and the leaf symbol to indicate the ECO mode In ECO mode the setpoint is fixed and the device does not react to any butto...

Page 6: ...ill appear for 2s and blink 2x but no further action is taken Power failure Restart selection Register address 0x010C On the LCD there are three symbols that define how the thermostat will restart after a power failure Keep thermostat switched OFF Switch thermostat to last state before power failure Record and Memorize Turn the thermostat ON Storage during power loss The status will be kept in EEP...

Page 7: ... Low 0b00000010 Stage Medium 0b00000100 Stage High 0b00001000 Auto OFF 0b00001001 Auto Low 0b00001010 Auto Medium 0b00001100 Auto High 5 0x0005 Read only Output valve actuator heating cooling 0 100 0 0 Off 100 On 8 0x0008 Read only external temperature sensor C 200 1000 20 0 100 0 C 0 1 C 9 0x0009 Read only failure status 0x00 no failure 0x01 control loop temperature sensor alarm 0x02 external tem...

Page 8: ...eep off after power on reset 1 return to last stFate after power failure 2 switch on after power on reset 1 269 0x010D Read write Key lock 0x00 unlocked 0x01 lock on off 0x02 lock mode 0x04 lock clock 0x08 lock fan speed 0x10 lock temp setting 0x1F lock all keystrokes Once a locked key is pressed the LOCK symbol shall be displayed and blink twice 0 270 0x010E Read write Display Settings 0b00000001...

Page 9: ...283 0x011B Read write Deadband 1 100 0 1 10 0 C F 0 1 C F 10 284 0x011C Read write Heating Proportional Band Xp_heat 1 100 0 1 10 0 C F 0 1 C F 20 285 0x011D Read write Heating Integration Time Tn_heat 0 255 0 255 Minutes 1 0 min 30 286 0x011E Read write Cooling Proportional Band Xp_cool 1 100 0 1 10 0 C F 0 1 C F 20 287 0x011F Read write Cooling Integration Time Tn_cool 0 255 0 255 Minutes 1 0 mi...

Page 10: ...mperature 0 500 0 50 0 C 0 1 C 0 514 0x0202 Read write Controller mode Comfort 0b0000 0000 controller off Frost protection active 0b0000 0001 controller auto mode heating cooling 0b0000 0010 controller heating mode only 0b0000 0011 controller cooling mode only 0b0000 0100 ventilating PI loop controls fan stages only valves closed 0 Controller mode ECO 0b0001 0000 controller off Frost protection ac...

Page 11: ...systemair de Issue date 03 11 2020 Page 11 11 MOUNTING ADVICE DIMENSIONS MM For installing or maintenance please make sure the power is disconnected Fix the thermostat base plate to the wall through the four screw holes with distance between axes of 60 mm Fasten base plate and front cover Do not press the panel in order to protect LCD ...

Reviews: