Transportation and Storage
The temperature range must be: -30...50 °C
Make sure that the damper blade is in the closed position during transportation and protected from weather
disruptions. The storage of the damper must be indoors.
Assessed Performance
19
CE
1396
Systemair Production a.s.
Hlavná 371, 900 43 Kalinkovo, Slovakia
1396-CPR-0177
F-B90
EN 15650 : 2010
Fire damper
Nominal activation conditions/sensitivity
Pass
Response delay (response time)
Closure wihin period of 2 minutes
Operational reliability
Manual
: 50 cycles
Motorized
: 10200 cycles and 10000 cycles (modulated)
Fire resistance:
Duct on one or both sides:
EI90 (v
e
- h
o
i↔o)S
Grille on both sides:
EI90 (v
e
- i↔o)S
&
EI120 (v
e
- i↔o)
Resistivity depends on installation method and situation
• integrity
E
maintenance of the cross section
(under E)
mechanical stability
(under E)
• insulation
I
• smoke leakage
S
Durability of response delay
Preserved
Durability of operational reliability
Preserved (20.200 cycles)