24
Rev. 04GB1410
SYSTEMA S.p.A.
EOLO BLULINE
To display and modify the values of the parameters,
proceed as follows:
1. If an external push button is not available, con-
nect to the door KEY while the board
SCP674V010 is off.
2. Press the key to display the list of parameters;
3. Release the key as soon as the required param-
eter is displayed: now the display is blinking with
the value of the parameter;
4. Press again the key to modify the value of the pa-
rameter,
Logo
Parameter
Range
UM Default
SP
Manual burner power 0=rL; 100=rH;
da 0 a 99
%
100
/P
Presence of potentiometer:
/P=0= NO EXTERNAL SIGNAL, power supplied by the burner to the SP value set.
/P=1= EXTERNAL SIGNAL BURNER MODULATION
PT 10 K potentiometer;
BT bithermostat contact for the operation of the double stage burner. rL / rH
PLC signal 0 - 5 V.
0 - 1
-
0
ATTENTION: During the operation with (INET /P=0) do not link the external signal in J3B
rL
Minimum value PWM = Minimum Power delivered by the burner.
Values considering the model. (See Tab.6.4 pag 48)
from 0 to rH
%
Tab.6.4
rH
Maximum value PWM = Maximum Power delivered by the burner.
Values considering the model. (See Tab.6.4 pag 48)
from rL to 100
%
Tab.6.4
Y0
Pre-washing time
from 10 to 100
sec
10
Y1
BOOST time
from 0 to 100
sec
0
Y2
Value of PWM during the burner ignition, in the BOOST period.
from 0 to 100
%
50
HH Release firmware (ONLY READING)
-
-
-
Tab 2.1
2.1.3
AUXILIARY CONTROL FAN
AUXILIARY CONTROL FOR THE SUMMER VEN-
TILATION
By closing the contact in the connector
C_F1
at J9C,
you will enable the manual operation of the fans for
the summer ventilation FAN1.
FAN CONTROL FOR HORIZONTAL MOUNTING
(optional)
a)
Install the capillary thermostat 0-60 °C with the
probe positioned on the side of fans.
b)
Connect the contact N.O. thermostat capillary
connector
J9C
(contact C_F1).
2.1.5
DISPLAY/MODIFICATION OF INSTRUMENTS PARAMETERS
ATTENTION!! This procedure can be carried
out by a qualified technician and / or authori-
zed by the manufacturer.
To reset the operation, delete the alarm condition:
a) By performing a proper maintenance to fix it.
(This is to ensure the closure of the contact
J7C
).
b) Then
press the RT botton
placed on the board
for at least 4 seconds.
BURNER LOCK
In the absence of flame detection, the unit will at-
tempt ignition and, with negative response, it will be
placed in a state of LOCK UNSTABLE indicating on
the display (see warnings icons on the display).
To restart the locked burner, reapply power to the
mains board, or open and close the contact TA, or
press the
RT
button placed on the board, for at least
4 seconds.
5. Release the key when the desired value has
been reached
To go out from the procedure and memorize the
modifications wait 3 seconds without pressing any
key.