WFDTNRN Vane-type Waterflow Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

IMPORTANT

Please Read Carefully And Save

This instruction manual contains important information about the installation 
and operation of waterflow detectors. Purchasers who install waterflow detec-
tors for use by others must leave this manual or a copy of it with the user. 
Read all instructions carefully before beginning.

CAUTION

The model WFDTNRN is a vane-type waterflow detector for use in wet-pipe 
fire sprinkler systems only. Vane-type waterflow detectors shall not be used as 
the sole initiating device in both deluge and preaction systems; waterflow de-
tectors used in these types of systems may result in an unintended discharge 
caused by a surge, trapped air or a short retard time.

WARNING

Installation must be performed by qualified personnel and in accordance with 
all national and local codes and ordinances.

Shock hazard:

 Disconnect power source before servicing. Serious injury or 

death could result.

Risk of explosion:

 Not for use in hazardous locations. Serious injury or death 

could result.

PRINCIPLES OF OPERATION

Vane-type waterflow detectors mount to water filled pipes in fire sprinkler sys-
tems. Waterflow in the pipe deflects a vane. Deflection of the vane produces 
a switched output. All detectors will activate on a sustained flow of water 
greater than 10 gallons per minute (gpm) but will not activate if the flow rate 
is less than 4 gpm.

COMPATIBLE PIPE TEES/RISERS

Model WFDTNRN is supplied with 12 paddles. One paddle is provided for 
each size of the threaded, sweat or plastic tee. See 

Figure 1

 and approximate 

tee depth chart. Each paddle has an indication that shows the pipe size and 
type of tee to be used with.

FIGURE 1. MOUNTING DIMENSIONS

3-1/2"

2-5/8"

4"

TEE DEPTH

DESIGNED TO FIT WITHIN 2 X 4 STUD WALL CONSTRUCTION

PLASTIC VANE

TEE FITTING

INSTALLATION GAUGE

END OF PADDLE TREE MUST

FIT BETWEEN TOP OF TEE

AND BOTTOM OF FLANGE

TEE

ADAPTER

INSTALLATION GUIDELINES

Before installing any waterflow alarm device, be thoroughly familiar with:

NFPA 72: 

 Installation, Maintenance and Use of Local Protective Signalling 
Systems

NFPA 13: 

Installation of Sprinkler Systems, specifically Section 3.17

NFPA 25:

   Inspection, Testing and Maintenance of Sprinkler Systems, specifi-

cally Chapters 4 and 5, and Section 5.3.3.2

NFPA 13D: 

Standard for Residential Dwellings

NFPA 13R: 

Standard for Multifamily Dwellings

FIGURE 2. ASSEMBLY DIAGRAM

COVER

FLOW

COVER TAMPER

SWITCH (OPTIONAL P/N CTS)

TIMER

ASSEMBLY

(P/N FS-RT)

GASKET

ACTUATOR

LEVER

WATERFLOW

GROUND SCREW

MOUNTING

PLATE

PADDLE

1" NPT

THREAD

TAMPER PROOF

WRENCH (P/N WFDW)

FILISTER HEAD

SCREW

SPECIFICATIONS

Contact Ratings: 

10 A @ 125/250 VAC 

;  2.5 A @ 24 VDC 

Triggering Threshold Bandwidth (Flow Rate):  4 to 10 GPM
Static Pressure Rating: 

250 PSI (Max.)

Dimensions (Installed): 

4in H x 3½ in W x 6¾ in D

Operating Temperature Range: 

32°F to 150°F (0°C to 66°C)

Shipping Weight: 

2 lbs

Enclosure Rating: 

NEMA 4

U. S. Patent Number: 

5,213,205

I56-4044-004

W0388-01

W0390-00

APPROXIMATE TEE DEPTH REQUIREMENTS (SEE FIGURE 1)

Tee Depth

Threaded

Sweat

CPVC NIBCO/

SPEARS 

(no insert)

CPVC 

SPEARS 

(with insert)

CPVC/Tyco

1 × 1 × 1"

2

1

/

8

"

1

3

/

4

"

2

1

/

8

"

2

15

/

32

"

2

13

/

16

"

1

1

/

4

 × 1

1

/

4

 × 1"

2

1

/

2

"

2

1

/

8

"

N/A

N/A

N/A

1

1

/

2

 × 1

1

/

2

 × 1"

2

3

/

4

2

1

/

4

"

3"

3"

N/A

2 × 2 × 1"

3

1

/

4

"

2

3

/

4

"

N/A

N/A

N/A

  

I56-4044-004 

 

 11-09

Summary of Contents for WFDTNRN

Page 1: ...is supplied with 12 paddles One paddle is provided for each size of the threaded sweat or plastic tee See Figure 1 and approximate tee depth chart Each paddle has an indication that shows the pipe size and type of tee to be used with FIGURE 1 MOUNTING DIMENSIONS 3 1 2 2 5 8 4 TEE DEPTH DESIGNEDTO FITWITHIN 2 X 4 STUDWALL CONSTRUCTION PLASTICVANE TEE FITTING INSTALLATION GAUGE END OF PADDLETREE MUS...

Page 2: ...f wrench provided Move the actuator lever back and forth to check for binding If the vane binds remove the detector and correct the problem before proceeding CAUTION Be sure the direction of flow arrow and directional cover points in the correct direction otherwise a waterflow condition will go unreported See Figure 3 FIGURE 3 DIRECTIONAL COVER OPERATIONAL TESTING Always notify a central station m...

Page 3: ...ority having jurisdiction for leaks and replace if leaks occur Test detectors at least quarterly as described in Operational Testing to insure proper operation Test more often if required by the authority having jurisdic tion Under normal conditions System Sensor waterflow detectors should provide years of trouble free service However if the switch enclosure becomes faulty request Part No FS RT an...

Page 4: ...ectors have a normal service life of 10 15 years Hard water systems however may substantially reduce waterflow detector service life 4 Waterflow detectors are not a substitute for insurance Building owners should always insure property and lives being protected by sprinkler systems 5 If valves controlling the water supply to a sprinkler system are closed vane type wa terflow detectors will not wor...