System Sensor TEMPORAL TONE SOUNDER BASE B501BHT Installation And Maintenance Instructions Download Page 3

D550-06-00 

I56-1367-004R

Figure 4. Wiring diagram:

Detector Activates Sounder Base(s) - (Complies with UL268)

UL has approved grouping for up to six B501BHT base with 
horn units. When wired as a group, any detector in the group 
that  has  its  LED’s  latched  on  by  the  panel  will  cause  other 
B501BHT  units  in  the  group  to  sound.  This  type  of  “local” 
grouping  is  accomplished  by  wiring  the  grouped  devices  to-

INTELLIGENT

MONITOR

MODULE

(+) 2

(–) 1

6

7

U.L.

LISTED

EOL

RESISTOR

47K

U.L.

LISTED

EOL

RELAY

24V

5

4

1

2

3

5

4

1

2

3

5

4

1

2

3

(+) COMM.

(–) COMM.

(–) POWER

(+) POWER

U.L. LISTED COMP

A

T

IBLE

CONTROL

 P

ANEL

EXTERNA

L

24V SUPPL

Y

CLASS A OPTIONAL WIRING

CLASS A OPTIONAL WIRING

*

GROUPING OF UP TO 6 MODEL B501BHT TEMPORAL TONE SOUNDER BASES.

OPTIONAL SOUNDER INTERCONNECT

*

gether using terminal 5, Sounder Base Interconnect, as shown 
in the diagram.

NOTE:

 Since a local grouping of horns is not supervised, the 

groups can only be used as a supplementary evacuation system. 
It is not acceptable to group horns for primary alarm signaling.

C0474-00

UL LISTED 

COMPATIBLE 

CONTROL 

PANEL

INTELLIGENT 

MONITOR 

MODULE

INTELLIGENT 

RELAY 

MODULE

FIRST 

SOUNDER 

BASE

(+) POWER

(–) POWER

LAST 

SOUNDER 

BASE

(–) COMM.

(+) COMM.

UL 

LISTED 

EOL 

RELAY 

24V

UL LISTED 

EOL 

RESISTOR 

47k

UL LISTED 

24V SUPPLY

SLC

(+)

(–) 

THIS IS A STANDARD RELAY 

MODULE CONFIGURED TO 

REVERSE THE POWER

OPTIONAL SOUNDER INTERCONNECT

*

*

GROUPING OF UP TO 6 MODEL B501BHT TEMPORAL TONE SOUNDER BASES.

Figure 5. Wiring diagram:

Detector Activates Sounder Base(s); Intelligent Relay Module Ac-
tivates All Sounder Bases - (Complies with UL 268 and UL 464)

UL has approved grouping of up to six B501BHT bases with 
horn units.  When wired as a group, any detector in the group 
that  has  its  LED’s  latched  on  by  the  panel  will  cause  other 
B501BHT  units  in  the  group  to  sound.    This  type  of  “local” 

C0968-00

grouping  is  accomplished  by  wiring  the  grouped  devices  to-
gether using terminal 5, Sounder Base Interconnect, as shown 
in the diagram.  

NOTE:

  Since a local grouping of horns is not supervised, the 

groups can only be used as a supplementary evacuation sys-
tem.    It  is  not  acceptable  to  group  horns  for  primary  alarm 
signaling.