inSTallaTion anD mainTenanCe inSTruCTionS

Selectable output Strobes, and Horn Strobes

General DeSCripTion

The System Sensor series of notification appli-

ances offers a range of strobes and horn/strobes, 

for indoor wall and ceiling applications. They are 

designed to be used in 24 volt DC or FWR (full 

wave rectified) systems.  To provide coverage for 

the broadest range of applications, products are of-

fered with three selectable candela settings using a 

rotary switch on the back of the unit.  The strobe 

is designed to meet the requirements of UL 1638. 

The horn is designed to meet the requirements of 

UL 464.  High and low volume and temporal 3 or 

continuous tone are also selected on the back of the 

device using a rotary switch.  Not compatible for 

use with MDL or MDL3 synchronization modules or 

coded power supplies.

For ceiling installations, use ceiling trim ring model 
number SYS-CTP for clear lens devices or SYS-CTPR 
for red lens devices.

fire alarm SYSTem ConSiDeraTionS

The National Fire Alarm Code, NFPA 72, requires 

that all horns, used for building evacuation pro-

duce temporal coded signals. Signals other than 

those used for evacuation purposes do not have 

to produce the temporal coded signal. System Sen-

sor recommends spacing notification appliances in 

compliance with NFPA 72.

for use with the following models: 

SYS-HS, SYS-ST, SYS-HSr, SYS-STr

loop DeSiGn anD wirinG

The system designer must make sure that the total cur-
rent drawn by the devices on the loop does not exceed 
the current capability of the panel supply, and that the 
last device on the circuit is operated within its rated 
voltage. The current draw information for making 
these calculations can be found in the tables within 
this manual.

When calculating the voltage available to the last de-
vice, it is necessary to consider the voltage drop due 
to the resistance of the wire. The thicker the wire, the 
smaller the voltage drop. Wire resistance tables can 
be obtained from electrical handbooks. Note that if 
Class A wiring is installed, the wire length may be up 
to twice as long as it would be for circuits that are not 
fault tolerant.

Product Specifications

Operating Temperature:

32°F to 120°F (0°C to 49°C)

Humidity Range:

10 to 93% Non-condensing

Strobe Flash Rate:

1 flash per second

Nominal Voltage:

Regulated 24V DC/FWR

Operating Voltage Range:

16 to 33V (24V nominal)

Input terminal wire gauge:

14 to 18 AWG

DimenSionS for proDuCTS anD aCCeSSorieS

 NOTICE: This manual shall be left with the owner/user of this equipment.

mounTinG box opTionS

2×4, 4×4, single-gang, double-gang, 4˝ octagon, 105mm×150mm, 65mm round, 86mm×86mm, 

60mm×60mm.

WALL PRODUCTS

LENGTH

WIDITH

DEPTH

Strobes and Horn/Strobes (including lens)

5.15 in

5 in

1.5 in

131 mm

127 mm

38 mm

SYS-CTP and SYS-CTPR (Ceiling Trim Plate) 

6.8 in diameter (173 mm)

1.5 in (38 mm)

Xi’an System Sensor Electronics, Ltd.

28 Tuan Jie South Road, Xi’an Hi-Tech

Development Zone, 710075, Xi’an, China

Tel: (86)29 85387800

SS-120-003 

1 I56-3690-000R

I56-3690-000R

fiGure 1. mounTinG plaTe inSTallaTion:

A0433-00

*MOUNTING SCREWS

NOT SUPPLIED

Summary of Contents for SYS-HS

Page 1: ...conforme al NFPA 72 Dise o del circuito y cableado El dise ador del sistema debe asegurarse de que el consumo total de corriente de los dispositivos en el circuito no exceda la capacidad de corriente...

Page 2: ...je La placa de montaje es compatible con las cajas que se muestran en la Figura 3 2 Conecte el cableado del equipo a los termina les ubicados en la parte posterior del producto como se muestra en la F...

Page 3: ...tes rojas Selecci n de buj a y sirena Ajuste el indicador giratorio en la parte posterior del producto para establecer la configuraci n de bu j a deseada Ajuste el otro indicador giratorio para selecc...

Page 4: ...es a os desde la fecha de fabricaci n que el detec tor de humo que se entrega no tiene defectos en los materiales ni en la fabricaci n si el producto tiene un uso y un servicio normales Xi an System S...

Page 5: ...he total cur rent drawn by the devices on the loop does not exceed the current capability of the panel supply and that the last device on the circuit is operated within its rated voltage The current d...

Page 6: ...s are NOT supplied The mount ing plate is compatible with the boxes shown in Figure 3 2 Connect field wiring to terminals located on back of product as shown in Figure 2 SS 120 003 2 I56 3690 000R 3 T...

Page 7: ...tting Adjust the other rotary dial for the horn selection The selec tions are high or low volume and continuous or temporal tone A0439 00 A0438 00 A0437 00 A0436 00 Figura 5 round trim ring for ceilin...

Page 8: ...visual stimuli with seizures such as persons with epilepsy should avoid prolonged exposure to environments in which strobe signals including this strobe are activated The signal strobe cannot operate...

Reviews: