Signal levels exceeding 130% rated signal voltage can
damage the speaker. Consequently, an incorrect tap con-
nection may cause speaker damage. This means that if a
25V tap is selected when a 70.7V amplifier is being used,
speaker damage may result. Therefore, be sure to select
the proper taps for the amplifier voltage/input power
level combination being used.

2 W

1 W

1/2 W

   1/4 W

84

81

78

      75

UL

Reverberant

(dBA @ 10 ft.)

2 W

1 W

1/2 W

   1/4 W

87

84

81

      78

Anechoic

(dBA @ 10 ft.)

Installation

All wiring must be installed in compliance with the
National Electrical Code (NEC) and applicable local codes
as well as special requirements of the authority having
jurisdiction, using the proper wire size. This also includes
all applicable NFPA Standards, ANSI/UL 1480, UL 1971 and
NEC 760.

Electrical

1. Connect the speaker/strobe as shown in Figure 1. Keep

in mind that even though the speaker and strobe are a
single mechanical unit, they are electrically independent
and require separate power sources. 

NOTE:

Do NOT loop electrical wiring under terminal
screws. Wires connecting the device to the control
panel must be broken at the device terminal con-
nection in order to maintain electrical supervision.

NOTE:

Supply power for strobe must be continuous for 
proper operation.

2. See Figure 2 as an example of how to select a 

1

4

Watt

input when a 25 volt amplifier is being used. Notice that
the header, SW1, has two shunts. One shunt is used to
select either 25 or 70.7 volts input. The other shunt is
used to select input power of 

1

4

1

2

, 1 or 2 Watts. Table 1

lists the UL reverberant and anechoic output sound lev-
els for each power tap on the SP2 series speaker/strobes.

Figure 1. Electrical connections:

Figure 2. Voltage and Power Selection:

25.0V

70.7V

2W

1W

1/2W

1/4W

25.0V

70.7V

2W

1W

1/2W

1/4W

CORRECT

SW1

SW1

INCORRECT

INPUT FROM
AMPLIFIER

TO NEXT
SPEAKER OR EOL

TO NEXT
STROBE OR EOL

INPUT FROM
POWER SUPPLY

Table 1. Sound levels for each transformer

power tap: 

CAUTION

DC

FWR

DC

FWR

DC

FWR

50

61

43

60

38

60

 

 78

84

 67

82

 58

72

 145 170 123 159 102 141

169 220 140 191 115 174

15
15/75

 

56    65     49    64     44     62

    

150  199   150  207   150   198   

30
75
110

AVERAGE CURRENT (mA)

24V Models

20V

24V

30V

DC

FWR

DC

FWR

DC

FWR

135 204 135 208 135 185

 

183 201 183 219 183 216

350 440 340 460 330 480
460 560 450 570 420 620

PEAK CURRENT (mA)

24V Models

20V

24V

30V

DC

FWR

DC

FWR

DC

FWR

 97 129  116   152 147  198

97

135 116 164 147 211

 

 97 129  116   152 147  198 

190 240 230 280 290 380
190 230 220 290 290 370

IN RUSH CURRENT (mA)

24V Models

20V

24V

30V

Candela

Table 2. Current draw of strobes: 

D690-01-00

2

I56-1368-003R