background image

D900-22-00 

I56-1453-012R

Wire Sizes

The designer must be sure that the last device on the circuit 
has sufficient voltage to operate the device within its rated 
voltage. When calculating the voltage available to the last 
device, it is necessary to consider the voltage drop due to 
the resistance of the wire. The thicker the wire, the less the 
voltage  drop.  Generally,  for  purposes  of  determining  the 
wire size necessary for the system, it is best to consider all 
of the devices as “lumped” on the end of the supply circuit 
(simulates “worst case”).
Typical wire size resistance:
18 AWG solid: Approximately 8 ohms/1,000 ft. 
16 AWG solid: Approximately 5 ohms/1,000 ft. 
14 AWG solid: Approximately 3 ohms/1,000 ft. 
12 AWG solid: Approximately 2 ohms/1,000 ft.

Example:

 Assume you have 10 devices on a zone and 

each requires 50 mA average and 2000 Ft. of 14 AWG wir-
ing (total length=oureturn).  The voltage at the 
end of the loop is 0.050 amps per device x 10 devices x 3 
ohms/1,000 ft. x 2000 ft =3 volts drop.
The same number of devices using 12 AWG wire will pro-
duce  only  2  volts  drop.  The  same  devices  using  18  AWG 
wire will produce 8 volts drop. Consult your panel manu-
facturer’s specifications, as well as SpectrAlert’s operating 
voltage range to determine acceptable voltage drop.

NOTE:

 If class “A” wiring is installed, the wire length may 

be up to 4 times the single wire length in this calculation.

Figure 1A: Current Draw Measurements (RMS)

NOTE:

 All SC and PC strobes were only tested at the 16-33 

Volt-FWR/DC  limits.  This  does  not  include  the  80%  low 
end or 110% high end voltage limits.

Candela

FWR Max. Operating 

Current – Strobe

(mA RMS)

DC Max. Operating 

Current – Strobe

(mA RMS)

15

68

64

15/75

77

78

30

107

113

75

197

205

95

239

274

115

298

325

177

399

489

Figure 1B: Horn Sound Measurements (dBA)

Selectable Horn Tones

16-33V

Temporal

Low
Volume

Electromechanical

75

3000 Hz Interrupted

75

High
Volume

Electromechanical

80

3000 Hz Interrupted

81

Non-
Temporal

Low
Volume

Electromechanical

79

3000 Hz Interrupted

79

High
Volume

Electromechanical

84

3000 Hz Interrupted

86

Figure 1C: Horn Current Draw Measurements (RMS)

Selectable Horn Tones

16-33 (VDC)

16-33 (VFWR)

Temporal

Low
Volume

Electromechanical

23

23

3000 Hz Interrupted

33

23

High
Volume

Electromechanical

53

44

3000 Hz Interrupted

57

40

Non-
Temporal

Low
Volume

Electromechanical

37

29

3000 Hz Interrupted

32

33

High
Volume

Electromechanical

49

49

3000 Hz Interrupted

56

58

NOTE:

 Regulated 24 VDC, max operating current 57.0 mA 

24 V FWR, max operating current 57.5 mA

NOTE:

 24VDC 2-wire horn/strobe current is shown in Figure 

1D. Current draw for other horn/strobe power supplies can 
be calculated by adding the strobe current draw (Figure 1A) 
for chosen candela setting to the horn current draw (Figure 
1C) for chosen setting.

Temporal

Non-Temporal

Low Volume

High Volume

Low Volume

High Volume

Candela Setting

Electromechanical

3000 Hz

Electromechanical

3000 Hz

Electromechanical

3000 Hz

Electromechanical

3000 Hz

15

73

73

76

78

75

75

81

86

15/75

89

89

91

92

89

90

96

98

30

126

125

128

128

125

125

131

134

75

225

222

222

222

219

219

221

222

95

272

270

271

271

266

265

269

270

115

297

297

296

296

291

290

292

293

177

512

504

501

496

491

493

491

496

Figure 1D: 24V DC Horn/Strobe Current Draw 
Measurements (mA RMS)

firealarmresources.com

Reviews: