1
I56-2877-006R
06-10
INSTALLATION AND MAINTENANCE INSTRUCTIONS
MP120K 120 VAC Adapter Mounting Plate
SPECIFICATIONS
General Specifications
Standard Operating Temperature:
–40°F to 151°F (–40°C to 66°C)
Humidity Range:
10 to 93% non-condensing (indoor products)
Nominal Voltage:
Regulated 120 VAC
Operating Voltage Range:
96-132 VAC
Current Draw From AC Line:
150 mA max.
MP120K may be used with any of the following products, at all horn and strobe settings:
P2R, P2RH, P2RK, P2RHK, P2W, P2WH, SR, SRH, SRK, SRHK, SW, SWH, PC2R, PC2RH, PC2RK, PC2RHK, PC2W, PC2WH, SCR, SCRH, SCRK, SCRHK, SCW,
SCWH, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P, P2R-P, P2W-P, P2RH-P, P2WH-P, SCR-P, SCW-P, SCRH-P, SCWH-P, PC2R-P, PC2W-P, PC2RH-P, PC2WH-P,
SR-SP, SRH-SP, P2R-SP, P2RH-SP, SCW-SP, SCWH-SP, PC2W-SP, PC2WH-SP, CHR, CHW, CHSR, CHSW
GENERAL DESCRIPTION
The MP120K mounting plate is designed to allow the use of 120 VAC to power
SpectrAlert Advance horns, strobes, horns/strobes, chimes, and chime/
strobes. The MP120K consists of a SpectrAlert Advance mounting plate that
has been fitted with a power supply that converts 120VAC to nominal 24V
FWR.
The MP120K must be installed using a 120 VAC power source. This unit
can only be used for non-synchronous applications; it will NOT work with
SpecrtAlert Sync•Circuit Modules.
NOTICE:
This manual shall be left with the owner/user of this equipment.
WIRING
This module has pig-tail wires and is intended to be wired without rigid con-
nections inside a standard electrical box.
Horn
Horn/strobe
Strobe Only
Two Wire System
Any Mix of Models
Wired for Tandem
Operation
120 VAC
Power
A0356-00
I56-2877-006R
FIGURE 1. NON-SYNCHRONIZED DEVICES; ANY COMBINATION OF MODELS POWERED BY A 2-WIRE CIRCUIT.
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
www.systemsensor.com