background image

SpectrAlert Selectable Output
CH24 Series Wall Chime/Strobes
for Fire Protective Signaling Systems

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

NOTICE: 

This  manual  shall  be  left  with  the  owner/user  of  this 

equipment.

General Description

The  SpectrAlert  CH24  series  strobe  can  be  installed  in  systems 
using  24-volt  panels  having  DC  or  full-wave  rectified  (FWR) 
power supplies. The strobes can also be installed in applications 
requiring synchronization (MDL required) or applications that do 
not  require  synchronization  (no  module  required).  Please  note 
that the chime section is not synchronizable with the MDL.
The SpectrAlert CH24 series chime/strobes are designed to meet 
the  requirements  of  most  agencies  governing  these  devices, 
including: NFPA, ADA, The National Fire Alarm Code, UL, CSFM, 
MEA. Also, check with your local Authority Having Jurisdiction 
for other codes or standards that may apply.

Note:    The  SpectrAlert  CH24  Series  Chime/Strobe  must  be 

powered  from  a  non-coded  power  supply.  This  appli-
ance is not intended for use with a coded power sup-
ply.

Fire Alarm Considerations

Temporal and Non-Temporal Coded Signals:

The  American  National  Standards  Institute  and  the  National 
Fire Alarm Code require that all horns used for building evacu-
ation installed after July 1, 1996, must produce Temporal Coded 
Signals. Signals other than those used for evacuation purposes do 
not have to produce the Temporal Coded Signal. 

Power Supply Considerations For Strobes

Panels  typically  supply  DC  filtered  voltage  or  FWR  (full-wave 
rectified) voltage. The system design engineer must calculate the 
number of units used in a zone based on the  type of panel sup-

D900-24-00                                                                                              1                                                                                          I56-0936-003R

For use with the following models: CH24 and CH24W

U.S. Patent Nos. 5,593,569; 5.914,665; 5,850,178; 5,598,139; 6,049,446; 6,127,935

Specifications: Chime

Mechanica

l

Input Terminals:           12 to 18 AWG (3.31 to 0.82 mm

2

)

Overall Dimensions:     6.9

 × 5.0

   

 

 

Electrical

Voltage Input:              DC or Full-Wave Rectified 8-33 volts
Operating
Temperature Range:      32° to 120°F (0° to 49°C) 

 

 

                                    

 

 

 

 

 

Listings:                       UL S4011 Private Mode (Chime/Strobe), 
                                   UL S5512 (Strobe)

Specifications: Strobe

Voltage Range:                         Regulated 24 DC/FWR
Operational Voltage Range:       16-33 Volts
Synchronous Applications
with MDL Module:                   17-33 Volts
Flash Rate:                               1 flash per second
Selectable Light Outputs:          All  candelas  are  selectable  via  a 
manual slide switch. 15/75 is listed at 15 candela per UL 1971 but 
will provide 75 candela on axis (straight ahead). 15, 30, 75, or 110 
are rated for that candela.

ply. Be certain the sum of all the device currents do not exceed 
the  current  capability  of  the  panel.  Calculations  are  based  on 
using the device current found in Table 3 and must be the current 
specified for the type of panel power supply used. 

Wire Sizes

The designer must be sure that the last device on the circuit has 
sufficient  voltage  to  operate  the  device  within  its  rated  voltage. 
When  calculating  the  voltage  available  to  the  last  device,  it  is 
necessary to consider the voltage drop due to the resistance of the 
wire. The thicker the wire, the less the voltage drop. Generally, for 
purposes of determining the wire size necessary for the system, 
it is best to consider all of the devices as “lumped” on the end of 
the supply circuit (simulates “worst case”).
Typical wire size resistance:
18 AWG solid: 

Approximately 8 ohms/1,000 ft.

16 AWG solid: 

Approximately 5 ohms/1,000 ft. 

14 AWG solid: 

Approximately 3 ohms/1,000 ft.

12 AWG solid: 

Approximately 2 ohms/1,000 ft.

Example:  Assume  you  have  10  devices  on  a  zone  and  each 
requires  50  mA  average  and  2000  Ft.  of  14  AWG  wiring  (total 
length=ou return). The voltage at the end of the loop 
is 0.050 amps per device 

×

 10 devices 

×

 3 ohms/1,000 ft. 

×

 2000 

ft =3 volts drop.
The same number of devices using 12 AWG wire will produce only 
2 volts drop. The same devices using 18 AWG wire will produce 
8 volts drop. Consult your panel manufacturer’s specifications, as 
well as SpectrAlert’s operating voltage range to determine accept-
able voltage drop.
Note: If class “A” wiring is installed, the wire length may be up to 
4 times the single wire length in this calculation.

Note for Strobes: Do not exceed 1) 16-33 Voltage range limit, 2) Maximum number of 70 strobe lights when connecting the MDL Sync module with a maximum line imped-
ance of 4 Ohms per loop and 3) Maximum line impedance as required by the fire alarm control manufacturer.

firealarmresources.com

Reviews: