background image

D690-03-00 

I56-2769-015R

Figure 1. Wiring 2-Wire produCTS:

+   

–   

 +

 –

INPUT 

FROM 

FACP

OR 

PRIOR 

DEVICE 

OUTPUT 

TO 

NEXT

DEVICE 

OR EOL

A0367-01

Figure 2. Wiring 4-Wire produCTS:

+

INPUT 

FROM 

FACP OR 

PRIOR 

STROBE

INPUT FROM

FACP OR PRIOR HORN

+

+

+

OUTPUT 

TO NEXT 

STROBE 

OR EOL

OUTPUT TO NEXT 

HORN OR EOL

A0366-00

Figure 3. SHorTing Spring:

SHORTING SPRING

A0368-00

NOTE:

 A shorting spring is provided between terminals 2 and 3 of the mount-

ing plate to enable wiring checks after the system has been wired, but prior 
to installation of the final product. This spring will automatically disengage 
when the product is installed, to enable supervision of the final system.

CandeLa SeLeCTion

Adjust the slide switch on the rear of the product to position the desired can-
dela setting in the small window on the front of the unit. All products meet 
the light output profiles specified in the appropriate UL Standards. For K series 
products used outdoors at low temperatures, listed candela ratings must be re-
duced in accordance with 

Table 2

. Use 

Table 1

 to determine the current draw 

for each candela setting. WIRING DIAGRAMS

NOTE:

 SpectrAlert products set at 15 and 15/75 candela automatically work 

on either 12V or 24V power supplies. The products are not listed for 12V op-
erating voltages when set to any other candela settings. For 4-Wire products, 
total current draw may be determined by adding current draw for the specific 
candela selection in Table 1 with the current draw for the specific horn selec-
tion in 

Table 3

TabLe 1. STrobe CurrenT draW (      ) For S, SC, p4 & pC4 SerieS: 

Candela

8–17.5 Volts

16–33 Volts

DC

FWR

DC

FWR

Standard Candela Range

15

123

128

66

71

15/75

142

148

77

81

30

NA

NA

94

96

75

NA

NA

158

153

95

NA

NA

181

176

110

NA

NA

202

195

115

NA

NA

210

205

High Candela Range

135

NA

NA

228

207

150

NA

NA

246

220

177

NA

NA

281

251

185

NA

NA

286

258

TabLe 2. CandeLa deraTing:

Listed Candela

Candela rating at –40°F

(K Series Outdoor Applications Only)

15

Do not use below 32°F

15/75

30
75

44

95

70

110

110

115

115

135

135

150

150

177

177

185

185

Horn SeLeCTion

Turn the rotary switch on the back of the product to the desired setting. For 
horn  and  4-wire  horn/strobe  products,  the  current  draw  for  each  setting  is 
listed in 

Table 3

. For 2-wire horn/strobe products (P2 series), current draws 

are listed in 

Tables 4

 and 

5

. The sound output measurement for each horn 

setting is shown in 

Table 6

.

TabLe 3. Horn CurrenT draW (     ) For H, p4 & pC4 SerieS:

Pos Sound Pattern dA Out

8–17.5 Volts

16–33 Volts

DC

FWR

DC

FWR

1 Temporal

High

57

55

69

75

2 Temporal

Medium

44

49

58

69

3 Temporal

Low

38

44

44

48

4 Non-temporal High

57

56

69

75

5 Non-temporal Medium

42

50

60

69

6 Non-temporal Low

41

44

50

50

7 Coded

High

57

55

69

75

8 Coded

Medium

44

51

56

69

9 Coded

Low

40

46

52

50

NOTE:

 In positions 7, 8, and 9, temporal coding must be provided by the NAC. 

If the NAC voltage is held constant, the horn output will remain constantly on. 
Positions 7, 8, and 9 are not available on 2-wire horn/strobe products.

ma  

ma  

Summary of Contents for SpectrAlert Advance Series

Page 1: ...pplications indoors and outdoors They are designed to be used in 12 or 24 volt DC or FWR full wave rectified systems These products are electrically backward compat ible with the previous generation of SpectrAlert notification appliances Horn strobe products are available in two versions The 2 wire products fit systems where a single NAC controls both horn and strobe The 4 wire products are in ten...

Page 2: ...for the specific candela selection in Table 1 with the current draw for the specific horn selec tion in Table 3 Table 1 Strobe Current Draw for S SC P4 PC4 Series Candela 8 17 5 Volts 16 33 Volts DC FWR DC FWR Standard Candela Range 15 123 128 66 71 15 75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High Candela Range 135 NA NA 228 207 150 NA N...

Page 3: ...n the ones supplied with the product 2 The wall mount box SA WBB or SA WBBW must be mounted with its internal post in the lower left corner as shown in Figure 8 3 Threaded holes are provided in the sides of the box for inch conduit adapters Knockout plugs in the back of the box can be used for inch rear entry Unused holes must be sealed Plugs and O Rings are provided with the box for this purpose ...

Page 4: ... limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture After phoning System Sensor s toll free number 800 SENSOR2 736 7672 for a Return Authorization number send defective units postage prepaid to System Sensor Returns Department RA __________...

Reviews: