background image

inSTaLLaTion and mainTenanCe inSTrUCTionS

Selectable output Chimes and Chime/Strobes

3825 Ohio Avenue, St. Charles, Illinois 60174

800/736-7672, FAX: 630/377-6495

www.systemsensor.com

D690-04-00 

I56-2783-003R

.

SpeCiFiCaTionS

General Specifications

Standard Operating Temperature: 

32°F to 120°F (0°C to 49°C)

Humidity Range: 

10 to 93% non-condensing

Strobe Flash Rate: 

1 flash per second

Nominal Voltage: 

Regulated 12DC/FWR or regulated 24DC/FWR1

Operating Voltage Range: 

8 to 17.5 V (12V nominal) or 16 to 33 V (24 nominal)

Operating Voltage with MDL: 

9 to 17.5 V (12V nominal) or 17 to 33 V (24 V nominal)

1CHS

 produ

cts will operate at 12 V nominal only for 15 & 15/75 cd.

Mechanical Specifications

Input terminal wire gauge: 

   

12 to 18 AWG

Chime/strobe dimensions (including lens): 5.6˝L×4.7˝W×2.5˝D (142 mm L×119 mm W×64 mm D)
Chime dimensions: 

   

5.6˝L×4.7˝W×1.3˝D (142 mm L×119 mm W×33 mm D)

GeneraL deSCripTion

Chimes and chime/strobes are private mode notification appliances used to 
alert trained personnel to investigate possible emergency situations and take 
appropriate action. SpectrAlert Advance chimes and chime/strobes are electri-
cally backward compatible with the previous generation of notification appli-
ances. While they are specifically designed for use on the wall, the products 
are listed to be used on the wall or ceiling. SpectrAlert products are designed 
to be used in either 12 or 24 volt DC or full wave rectified (FWR) systems. If 
required, the MDL module may be used in order to provide synchronization.

NOTICE:

 This manual shall be left with the owner/user of this equipment.

Fire aLarm SYSTem ConSideraTionS

The  National  Fire  Alarm  Code,  NFPA  72,  requires  that  all  horns,  used  for 
building evacuation installed after July 1, 1996, produce temporal coded sig-
nals. Signals other than those used for evacuation purposes do not have to 
produce the temporal coded signal.

poWer SUppLY ConSideraTionS

Panels typically supply DC filtered voltage or FWR (full wave rectified) volt-
age. The system design engineer must calculate the number of units used on 
a loop based on the type of panel supply. Be certain the sum of all the device 
currents does not exceed the current capability of the panel. Calculations are 
based on using the device current found in the subsequent charts and must 
be compatible with the current specified for the panel or power supply used.

NOTE:

 SpectrAlert chimes and chime/strobes must be powered from a non-

coded power supply.

Wire SizeS

The  designer  must  be  sure  that  the  last  device  on  the  circuit  has  sufficient 
voltage to operate the device within its rated voltage. When calculating the 
voltage available to the last device, it is necessary to consider the voltage drop 
due to the resistance of the wire. The thicker the wire, the smaller the volt-
age drop. Generally, for purposes of determining the wire size necessary for 
the system, it is best to consider all of the devices as “lumped” on the end of 
the supply circuit to simulate worst case. For the most accurate voltage drop 
calculations use the System Sensor voltage drop calculator available on the 
web or CD-ROM.

approximaTe Wire reSiSTanCe:

18 AWG solid: 8 ohms/1000 ft.
16 AWG solid: 5 ohms/1000 ft.
14 AWG solid: 3 ohms/1000 ft.
12 AWG solid: 2 ohms/1000 ft.
NOTE: If Class A wiring is installed, the wire length may be up to twice as 
long as on non-fault tolerant circuits.

CandeLa SeLeCTion For ChS SerieS modeLS

For  strobe  candela  selection,  adjust  the  slide  switch  located  on  the  rear  of 
the product while watching the viewing window under the reflector on the 
front of the unit. Use Table 1 to determine current draw at various candela 
and chime tone settings. Tables 2 and 3 can be used to determine strobe light 
output at various viewing angles.

NOTE: SpectrAlert products set at 15 and 15/75 candela automatically work 
on either 12V or 24V power supplies. The products are not listed for 12V op-
erating voltages when set to any other candela settings.

I56-2783-00

3R

For use with the following models: CHSR, CHSW, CHR, CHW

Summary of Contents for SpectrAlert Advance CHSR

Page 1: ...ls typically supply DC filtered voltage or FWR full wave rectified volt age The system design engineer must calculate the number of units used on a loop based on the type of panel supply Be certain the sum of all the device currents does not exceed the current capability of the panel Calculations are based on using the device current found in the subsequent charts and must be compatible with the c...

Page 2: ... Input 8 17 5 Volts 16 33 Volts 15 15 75 15 15 75 30 75 95 110 115 1 Second Chime High 128 150 72 82 98 158 183 202 210 1 Second Chime Low 127 150 71 81 97 157 182 202 210 1 4 Second Chime High 129 149 72 82 99 160 183 203 211 1 4 Second Chime Low 128 149 71 81 97 154 179 196 205 Temporal Chime High 128 148 71 81 97 157 179 199 206 Temporal Chime Low 125 147 71 81 97 156 180 200 206 5 Second Whoop...

Page 3: ...ination of the wiring terminals of the mounting plate 4 To attach product to mounting plate hook tabs on the product housing into the grooves on mounting plate Then swing product into position to engage the pins on the product with the terminals on the mounting plate Make sure that the tabs on the back of the product housing fully engage with the mounting plate 5 Secure product by tightening the s...

Page 4: ...from date of manufacture System Sensor makes no other express warranty for this product No agent representative dealer or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty The Company s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defec tive in materials or workmanship un...

Reviews: