SPECIFICATIONS

Wire Gauge for Terminals:  

22 AWG (0.64 mm, 0.34 mm

2

) to 14 AWG (1.6 mm, 2.08 mm

2

)

Operating Voltage Range: 

10.2 to 32 VDC (12 or 24VDC nominal)

Maximum Standby Current:  

7 mA @ 32 VDC, 11 mA @ 24 VDC, 20 mA @ 12 VDC, 50 mA @ 10.2 VDC

Maximum Alarm Current (LED on):  11 mA @ 32 VDC, 15 mA @ 24 VDC, 24 mA @ 12 VDC, 54 mA @10.2 VDC

Operating Humidity Range: 

0% to 95% Relative Humidity, Non-condensing

Operating Temperature Range: 

UL-Listed for use from 32°F to 100°F (0°C to 37.8°C)

Application Temperature Range: 

20°C to +55°C (-4°F to 131°F)

Adjustment Angle: 

20 degrees vertical, 50 degrees horizontal 

Sensitivity Levels: 

Level 1 25%, Level 2 30%, Level 3 40%, Level 4 50% Automatically set at start up

Fault Condition (Trouble): 

Long-term drift reference out of 20% range, beam blockage or detector out of alignment, imager saturated.

Alignment Aid: 

LED directional arrows 

Alarm Indicator:  

Local red LED and remote output

I56-6654-000

QUICK START GUIDE

 

OSI-RE-SS  

Smoke Detection System

This guide provides information on how to install the OSI-RE-SS Smoke Detec-
tion System.
Extensive product and critical product security information can be found 
in the OSI-RE-SS Installation Guide (Document No. E56-6654) available at  

www.systemsensoreurope.com/products/category/beam-smoke-detectors/

.

The OSI-RE-SS system consists of an Imager and a reflector.
The products shall be powered from a EN54-4 certified AC/DC Power convert-
ers to be in compliance for CE certification. 

FIGURE 1. IMAGER AND REFLECTOR

 

C2051-00, C2052-00

DETERMINE THE POSITIONS OF THE IMAGER AND REFLECTOR 

COMPONENTS

Make sure that the intended mounting locations meet the following criteria 
(See Figure 2.): 

•  Detector spacing must comply with local codes and standards
•  Reflector must be located within the Field of View (FOV) of the Imager
•  Clear path between the reflector and Imager
•  Mounted well above the head-height of people and obstructions
•  Avoid direct sunlight onto the units

The Imager and reflector should be placed within a recommended distance 
below the ceiling. (See Figure 3.) This value will vary according to regional 
specifications, geometry, and specific requirements for the installation. The 
distance for flat ceilings and basic spacing requirements (S) is shown in the 
following table.

Standard

Distance from Ceiling

Maximum Spacing (S)

NFPA 72

300 mm (12 in.) minimum

18.3 m (60 ft)

AS1670.1

25 to 600 mm (1 to 23.6 in.)

14 m (45.9 ft)

BS5839.1

25 to 600 mm (1 to 23.6 in.)

15 m (49.2 ft)

GB50166

300 to 1000 mm (11.8 to 39.4 in.)

14 m (45.9 ft)

For full information on spacing requirements, please refer to your local codes 
and standards.

FIGURE 2. MOUNTING LOCATIONS

 

12” minimum

(0.3m)

10’ (3.0m)

minimum

Typical

30’ (9.1m) maximum

To First

Detectors

1/2 S

S

Wall

C2053-00

FIGURE 3. MOUNTING LOCATIONS

Ex. Distances according to NFPA 72 (S524 in Canadian applications).

 

 

1/2 S maximum

Reflector

Tx/Rx

S

Tx/Rx

Reflector

16 ft. (5m) minimum

328 ft. (100m) maximum

1/4 S

maximum

C2054-00

Pittway Tecnologica S.r.l.,

Via Caboto 19/3,

34147 TRIESTE, Italy

  

I56-6654-000 

 

 13/10/2020