background image

[4.2]DETERMINE MOUNTINg LOCATION AND CONfIgURATION

On  ducts  wider  than  18  inches  it  is  recommended  that  the  detector  be 
mounted  downstream  of  a  bend,  obstruction  in  the  duct,  or  the  supply  or 
return air inlet. 

Exception:  Installation  of  duct  detectors  can  be  on  or  within  a  commercial 
packaged  rooftop  heating  and  air-conditioning  system,  fire/smoke  dampers 
and economizers. They may be mounted in either the supply and/or return air 
section as determined by local code.

Once a suitable location is selected, determine if the detector is to be mounted 
in  a  side-by-side  “rectangular”  configuration  or  a  top-over-bottom  “square” 
configuration as shown in Figure 2. If mounting in the square configuration, 
remove the rear attachment screw, rotate the unit at hinge, and replace the 
screw into the new attachment hole as shown in Figure 2. Do NOT remove the 
hinge screw during this process.   Final installation approval shall be based 
upon passing differential pressure and smoke entry tests described in the Mea-
surement Tests section.

fIgURE 2:

REMOVE SCREW AND PIVOT

DETECTOR AS SHOWN BELOW.

REPLACE SCREW

TO SECURE DETECTOR

IN PLACE.

H0550-00

[4.3]DRILL ThE MOUNTINg hOLES

Remove  the  paper  backing  from  the  mounting  template  supplied.  Affix  the 
template to the duct at the desired mounting location. Make sure the template 
lies flat and smooth on the duct. 

[4.3.1]fOR RECTANgULAR SIDE-By-SIDE MOUNTINg CONfIgURATION:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “B” for 
the rectangular configuration mounting tabs as shown on mounting template. 
Drill pilot holes at target “A” centers and cut two 1.375 inch diameter holes 
using a 

13

8

 inch hole saw or punch. Drill .156 inch diameter holes using a 

5

32

 

inch drill at target “B” centers.

[4.3.2]fOR SqUARE TOP-OVER-BOTTOM MOUNTINg CONfIgURATION:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “C” for 
the square configuration mounting tabs as shown on mounting template. Drill 
pilot holes at target “A” centers and cut two 1.375 inch diameter holes using 
a 1 

3

8

 inch hole saw or punch. Drill .156 inch diameter holes using a 

5

32

 inch 

drill at target “C” centers. If desired, drill an additional .156 inch hole at the 
location of one of the mounting tabs on the lower housing.

[4.4]SECURE ThE DUCT DETECTOR TO ThE DUCT

Use two (rectangular configuration) or three (square configuration) of the pro-
vided sheet metal screws to screw the duct detector to the duct.

CAUTION: Do not overtighten the screws.

[5]SAMPLINg TUBE INSTALLATION 
[5.1]SAMPLINg TUBE SELECTION

The  sampling  tube  must  be  purchased  separately.  Order  the  correct  length, 
as specified in Table 1, for width of the duct where it will be installed. The 
sampling tube length must extend at least 

2

/

3

 across the duct width for optimal 

performance.

The sampling tube is always installed with the air inlet holes facing into the 
air flow. To assist proper installation, the tube’s connector is marked with an 
arrow. Make sure the sampling tube is mounted so that the arrow points into 
the airflow as shown in Figure 3. Mounting the detector housing in a vertical 
orientation  is  acceptable  provided  that  the  air  flows  directly  into  the  sam-
pling tube holes as indicated in Figure 3. The sampling tube and exhaust tube 
can be mounted in either housing connection as long as the exhaust tube is 
mounted downstream from the sampling tube.

SS-300-018 

I56-3371-003R

fIgURE 1. ExPLODED VIEW Of DUCT SMOkE DETECTOR COMPONENTS:

H0569-00

EXHAUST TUBE

SENSOR HEAD

SENSOR MODULE COVER

WIRING COMPARTMENT COVER

WIRING COMPARTMENT

SENSOR MODULE

SAMPLING 

TUBE

NOTE: SENSOR HEAD IS ONLY 

INCLUDED ON SPECIFIED MODELS.

SOLD 

SEPERATELY

Reviews: