DH100ACDCI Ionization

Air Duct Smoke Detector

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

800/736-7672, FAX: 630-377-6495

Before Installing

Please thoroughly read the System Sensor 

Guide for Proper 

Use  of  Smoke  Detectors  in  Duct  Applications

  (A05-1004), 

which  provides  detailed  information  on  detector  spacing, 
placement, zoning, wiring, and special applications. Copies 
of this manual are available online at www.systemsensor.com 
or via System Sensor’s toll free fax-back service, Documents 
on Demand at 800/736-7672. NFPA Standards 72 and 90A 
should also be referenced for detailed information. 

NOTICE:

 This manual shall be left with the owner/user of 

this equipment.

IMPORTANT:

 This detector must be tested and maintained 

regularly  following  NFPA  72  requirements.  The  detector 
should be cleaned at least once a year.

Table of Contents                                                 Page

[1]General Description                                                      1
[2]Limitations of Duct Smoke Detectors                             1
[3]Exploded View of Duct Smoke Detector Components     2
[4]Contents of the Duct Smoke Detector Kit                       2
[5]Installation Sequence                                                    2
[6]Duct Smoke Detector Maintenance and Test Procedures 5
[7]Detector Cleaning Procedures                                       7
[8]Board Replacement                                                       8
[9]Specifications                                                               8
Warranty                                                                          8

[1] General Description

An HVAC system supplies conditioned air to virtually every 
area of a building. Smoke introduced into this air duct sys-
tem will be distributed to the entire building. Smoke detec-
tors designed for use in air duct systems are used to sense 
the presence of smoke in the duct. 
Model DH100ACDCI Air Duct Smoke Detectors utilizes ion-
ization technology for the detection of smoke. This smoke 
detection method, when combined with an efficient hous-
ing design, samples air passing through the duct and allows 
detection of a developing hazardous condition. When suf-
ficient  smoke  is  sensed,  an  alarm  signal  is  initiated  and 
appropriate action can be taken to shut off fans, blowers, 
change  over  air  handling  systems,  etc.  These  actions  can 
facilitate  the  management  of  toxic  smoke  and  fire  gases 
throughout the areas served by the duct system.
The  DH100ACDCI  detector  is  designed  to  operate  on  24 
VDC/VAC,  120  VAC,  or  240  VAC.  Alarm  and  supervisory 
relay  contacts  are  available  for  control  panel  interface 
(alarm initiation), HVAC control, and other auxiliary func-
tions. Auxiliary relays are also provided for fan shut down 
or signaling of up to 9 other detectors in the loop for mul-

tiple  fan  shut  down.  These  detectors  are  not  designed  for 
2-wire applications.
For testing, the alarm can be enabled by a magnet activated 
test switch or by the optional remote test station. The duct 
smoke  detector  latches  into  alarm  state  when  an  alarm 
occurs. A green LED flashes to indicate power, a red LED 
signals  local  alarm  indication,  and  optional  accessories 
offer a variety of annunciation capabilities.
The  DH100ACDCI  can  be  reset  by  a  momentary  power 
interruption, the reset button on the front cover, the control 
panel, or remote reset accessory. 

The DH100ACDCI incor-

porates  a  cover  tamper  feature  that  provides  a  trouble 
signal after 7 minutes if the cover is removed or improp-
erly installed.

 Proper installation of the cover removes the 

trouble condition.

[2] Limitations Of Duct Smoke Detectors 

WARNING

The National Fire Protection Association has established that 
DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE 
FOR OPEN AREA DETECTOR PROTECTION as a means of 
providing  life  safety.  Nor  are  they  a  substitute  for  early 
warning in a building’s regular fire detection system.
System  Sensor  supports  this  position  and  strongly  recom-
mends that the user read NFPA Standards 90A, 72, and 101. 
The  DH100ACDCI  Air  Duct  Smoke  Detectors  are  listed  per 
UL 268A.

WARNING

This device will not operate without electrical power. Fire 
situations may cause an interruption of power. The system 
safeguards should be discussed with your local fire protec-
tion specialist.

WARNING

This  device  will  not  sense  smoke  unless  the  ventilation 
system is operating and the cover is installed.

WARNING

For this detector to function properly, it MUST be installed 
according to the instructions in this manual. Furthermore, 
the  detector  MUST  be  protected  from  the  elements  and 
operated within ALL electrical and environmental specifi-
cations listed in this manual. Failure to comply with these 
requirements  may  prevent  the  detector  from  activating 
when smoke is present in the air duct.

Archived Document

Summary of Contents for InnovAir DH100ACDCI

Page 1: ...100ACDCI detector is designed to operate on 24 VDC VAC 120 VAC or 240 VAC Alarm and supervisory relay contacts are available for control panel interface alarm initiation HVAC control and other auxilia...

Page 2: ...mounting location Make sure the template lies flat and smooth on the duct Center punch holes A and B Drill the holes as indicated on the template 5 2 1 Sampling Tube Installation for Ducts Less Than 1...

Page 3: ...w moisture drainage away from the detector If the tube is shorter than the width of the air duct install the end cap into the sampling tube as shown in Figure 4 Sampling tubes over 3 ft long must be s...

Page 4: ...4 inch hole where the flange will be used 5 4 3 Modifications of Sampling Tubes There may be applications where duct widths are not what is specified for the installation In such cases it is permis si...

Page 5: ...hamber visually identify any obstructions Plug the exhaust and sampling tube holes to prevent ducted air from carrying smoke away from the detector head then blow smoke such as cigarette cotton wick o...

Page 6: ...ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM...

Page 7: ...x 10mA Max 7 5mA Max 30mA Max NOTE When a unit is powered at the 120VAC or 220 240VAC input any combination of accessories may be used such that the given accessory loads are 60 mA or less in the stan...

Page 8: ...20 VAC min Reset time with RTS451 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec Reset time by power down 0 6 sec max 0 6 sec max 0 6 sec max 0 6 sec max Power up time 34 sec max 34 sec max 3...

Reviews: