background image

  3 

I56-4168-003 

  

11-30

TABLE 1. TERMINAL DESIGNATIONS

TERMINAL 

BLOCK

T1

External Power – Powers Aspirating Smoke Detector

T2

Not used.

T3

RS 485 Rx 
Rx and Tx can be wired in a half duplex configuration

T4

RS 485 Tx

Rx and Tx can be wired in a half duplex configuration

T5

Alert Relay – Maintains state on loss of power

T6

Action1 Relay – Maintains state on loss of power

T7

Action2 Relay – Maintains state on loss of power

T8

Fire1 Relay – Maintains state on loss of power

T9

Fire2 Relay – Maintains state on loss of power

T10

Minor Fault Relay – Maintains state on loss of power

T11

Urgent Relay – Always reverts to reset on loss of power

T12

Isolate Relay – Maintains state on loss of power

T13

External Monitor 

CABLING REQUIREMENTS

The FAAST XT system provides a series of Euro style pluggable terminals, 
located behind the left side door of the unit. Refer to Table 1 for the proper 
electrical connections to the unit. Refer to Figure 4 for a typical connection for 
monitoring the FAAST XT system at a Fire Alarm Control Panel (FACP).

FIGURE 3. POWER AND ALARM CONNECTION BLOCK

FIGURE 4. FACP WIRING DIAGRAM

SYSTEM POWERING

The following procedure describes how to initially power up the FAAST XT system.

1.  Unplug the unit’s power connector to the unit before turning on the 

power.

2.  Turn on the power.
3.  Check the voltage at the connector. Make sure it is within the required 

voltage range.

4.  If wiring is not connected to the external monitor terminal, install a 

47k

 resistor (provided with the unit) into the terminal block and fit it 

into the T6 terminal.

5.  If the voltage is within the proper range, reconnect the power connector 

to the unit.

6.  Verify the system fan starts up and air begins to flow out of the exhaust 

port. The user interface will provide the device status.

7.  Connect a computer, with PipeIQ installed, to the unit using either the 

USB connection on the front of the device, or the Ethernet port located in 
the left side wiring door. (See the ‘Connecting to FAAST XT’ for detailed 
connection instructions.)

8.  Use the PipeIQ software to set up the unit configuration required for the 

particular application.

9.  The PC may now be disconnected unless a permanent networked con-

nection is desired. 

10.  The device will establish an airflow baseline during the first five minutes 

of operation. After five minutes, the airflow level display will provide the 
true measured airflow status. The device will give visual indication of 
the baselining period on the LCD screen.

N.C.

N.O.

C.

Fire2 Relay

 

Contact

s

(T9)

Fire Panel (FACP) typical connection 

FAAST XT

Fire Alarm Aspiration Sensing Technology®

for monitoring of device

Alarm

Short = Fire

Open = Fault

EOL

N.C.

N.O.

C.

Fire1 Relay

 

Contact

s

(T8)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Action2

 

Rela

y

Contacts 

(T7)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Action1

Rela

y

Contacts 

(T6)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Alert Relay 

Contacts 

(T5)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Isolate Relay 

Contact

s

(T12

)

Supervisory

Short = Isolate

Open = Fault

N.C.

N.O.

C.

Urgent Relay 

Contacts

(T11

)

Short = Urgent Fault
Open = Fault

N.C.

N.O.

C.

Minor Relay 

Contacts 

(T10)

Short = Minor Fault

Open = Fault

FACP

Supervisory

Supervisory

EOL

EOL

EOL

EOL

EOL

EOL

EOL

External

Monitor

(T13

)

N.C.

B.

B.

A.

N.O.

(Reset)

Panel 

Remote 

Reset

C. 

47k

Ω

ASP114-01

ASP18-24

firealarmresources.com

Summary of Contents for FAAST 9400X

Page 1: ...CONFIGURE YOUR PC Your PC will need to be sitting on the same local area network as the FAAST XT device in order to establish communication Change your PC s IP address to 192 168 1 15 by 1 Accessing your network setting in your PC s control panel 2 Open Local Area Connection settings and select Properties 3 Select Internet Protocol Version 4 TCP IPv4 and then select Properties 4 Select Use the fol...

Page 2: ...here are some circumstances where it may be necessary to connect a pipe to the exhaust port to divert the exhaust away from the location of the unit Add ing as little as 2ft of exhaust pipe also acts as a muffler for the fan ensuring quieter operation The output ports are tapered the same as the input ports to provide fast easy push fit connection of an exhaust pipe to the unit Perform the followi...

Page 3: ... T6 terminal 5 If the voltage is within the proper range reconnect the power connector to the unit 6 Verify the system fan starts up and air begins to flow out of the exhaust port The user interface will provide the device status 7 Connect a computer with PipeIQ installed to the unit using either the USB connection on the front of the device or the Ethernet port located in the left side wiring doo...

Page 4: ...e obligated to repair or replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other warranty expressed or implied whatsoever even if the loss or damage is caused by the Company s negligence or f...

Reviews: