System Sensor ExitPoint PF24VA Installation And Maintenance Instructions Download Page 1

D690-06-00  1 I56-3071-000

PF24VA Directional Sounder with Voice Messaging

INSTALLATION AND MAINTENANCE INSTRUCTIONS

6581 Kitimat Road, Unit 6

Mississauga, Ontario. L5N-3T5

www.systemsensor.ca

General Description

Before installing, please read the Directional Sound Ap-

plications Guide, available through System Sensor. The 

installation must meet the requirements of the authority 

having jurisdiction, CAN/ULC S524 and CSA C22.1. Di-

rectional sounders are used as supplemental signals on a 

fire alarm system to aid in the evacuation of building occu

-

pants. Although directional sounders may be connected to 

notification appliance circuits (NAC) for fire alarm service, 

they are not a replacement for audible or visible notification 

appliances as required by the authority having jurisdiction.
The directional sounder can be installed in systems us-

ing 24 Volt DC regulated power supplies only. It is not ap-

proved for use with FWR unregulated power supplies.
Directional sound is a broadband, multi-frequency sound. 

The sound source is easily and quickly located by build-

ing occupants, making it ideal for rapid building evacua-

tion. The sounder incorporates four different speed settings 

which consist of broadband noise. The four speed settings 

can be used to create an egress pathway out of a build-

ing. The speed setting should be set faster for units installed 

at the perimeter exit. In addition to the broadband noise, 

the sounder is capable of playing an alert message in the 

form of a recorded voice message or other audible signals. 

These messages will instruct the occupant of what action 

to take as they approach the directional sounder. The voice 

messages include: exit here, stairs up, stairs down, or area 

of refuge. 
Speed settings are made via DIP switches on the back 

of the sounder. 

Specifications

Mechanical

Input terminals: 

12 – 24 AWG

Sounder size: 

4 inches (101mm)

Grille Size: 

7

/

8

˝ (127mm)

Electrical

Voltage Input: 

Regulated 24 Volts DC

Operation Voltage Range: 

16 to 33 Volts

Operating Humidity Range: 

10% to 93% relative humidity non-condensing

Frequency range: 

707 Hz to 11314 Hz

Operating Temperature range: 

32° to 120°F (0° to 49°C)

Power: 

Selectable Low, Med-Low, Medium, Medium-High, High

Listings: ULC

NOTICE:

 This manual should be left with the owner/user of the equipment.

Power Supply Considerations for  

Directional Sounders

Panels  typically  supply  DC  filtered  voltage  or  FWR  (full-

wave rectified) voltage. This device is only compatible with 

DC filtered supplies and must not be used with panel sup

-

plies that are FWR. Be certain the sum of all the device 

currents do not exceed the current capability of the panel 

power supply. Calculations are based on using the device 

current found in 

Table 1

 and must be the current specified 

for the installed settings of the device.

Wire Sizes

The last device on the circuit must have sufficient voltage 

to operate the device within its rated voltage range. When 

calculating the voltage available to the last device, it is 

necessary to consider the voltage drop due to the resis-

tance of the wire. The thicker the wire, the less the voltage 

drop. Generally, for purposes of determining the wire size 

necessary for the system, it is best to consider all of the 

devices as “lumped” on the end of the supply circuit (simu-

lates “worst case”).
Typical wire size resistance:
18 AWG solid:  Approximately 8 ohms/1,000 ft.

16 AWG solid:  Approximately 5 ohms/1,000 ft.

14 AWG solid:  Approximately 3 ohms/1,000 ft.

12 AWG solid:  Approximately 2 ohms/1,000 ft.
Example: Assume you have 10 devices on a zone and 

each requires 50mA average and 2000 ft. of 14 AWG wir-

ing (total length = ou return). The voltage at the 

end of the loop is 0.050 Amps per device × 10 devices × 3 

ohms/1000 ft. × 2000 ft. = 3 volts drop.

Reviews: