background image

D500-08-00

4

I56-512-07R

In no case should more than 2 air inlet holes be cut off the
tube. There must be a minimum of 10 holes in the tube
exposed to the air stream.

B. Installation for Ducts More Than 8 Feet Wide

NOTE:

To  install inlet tubes in ducts more than 8 feet
wide, work must be performed inside the air duct.
Sampling of air in ducts wider than 8 feet is accom-
plished by using the ST-10 inlet sampling tube.

Install the inlet tube as follows:
1. Drill a 3/4-inch hole in the duct directly opposite the

hole already drilled for the inlet tube.

2. Slide the inlet tube with the flange into the right hous-

ing bushing. Position the tube so that the arrows point
into the air flow. Secure the tube flange to the housing
bushing with the two #6 self-tapping screws.

3. From inside the duct, couple the other section of the

inlet tube to the section already installed using the 1/2-
inch conduit fitting supplied. Make sure the holes on
both of the air inlet tubes are lined up facing the air flow.

4. Trim the end of the tube protruding through the duct so

that 1 to 2 inches of the tube extends outside the duct.
Plug this end with the tube end cap and tape closed any
holes in the protruding section of the tube. Be sure to
seal the duct when the tube protrudes.

5. Any tube (over 3 feet long) that doesn’t protrude

through the duct (on the side opposite the housing)
must be supported by other means.

WARNING

AIR FLOW

DIRECTION

DUCT
DETECTOR
HOUSING

DOTS INDICATE POSITION OF

SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DUCT
DETECTOR
HOUSING

INLET

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

INLET

TUBE

EXHAUST

TUBE

INLET

TUBE

EXHAUST

TUBE

DUCT
DETECTOR
HOUSING

AIR FLOW

DIRECTION

EXHAUST

TUBE

INLET

TUBE

DUCT
DETECTOR
HOUSING

Figure 4. Tube mounting configurations with varying air flow direction and orientation of detector housing.

Vertical as well as horizontal mounting is acceptable.

A78-1812-01

NOTE:

An alternate method to using the ST-10 is to use
two ST-5 inlet tubes. Remove the flange from one
of the tubes and install as described above. After
the installation, use electrician’s tape to close off
some of the sampling holes so that there are a total
of 12 holes spaced as evenly as possible across the
width of the duct.

NOTE:

Air currents inside the duct may cause excessive
vibration. This vibration can slowly open the seal
around the tube and permit air to escape. To pre-
vent this from occurring, a 3-inch floor flange,
available at most plumbing supply houses, may be
used. This flange/connector mounting technique
makes the initial installation easier because a 1-
inch to 1-1/4-inch hole may be drilled where the
flange/connector will be used. It is easier to push
the inlet tube through the larger hole.

Modification of Inlet Sampling Tubes

There may be applications where duct widths are not what
is specified for the installation. In such cases, it is permis-
sible to modify an inlet sampling tube that is longer than
necessary to span the duct width.

Summary of Contents for DH500

Page 1: ...ng hazardous condition When sufficient smoke is sensed an alarm signal is initiated at the fire control panel monitoring the detector and appropriate action can be taken to shut off fans and Specifications Length 14 5 inches 36 7 cm Width 5 inches 12 7 cm Depth 3 5 inches 8 9 cm Weight 2 8 lbs 1 1 kg Operating Temperature Range 32 to 120 F 0 to 49 C Operating Humidity Range 10 to 93 Relative Humid...

Page 2: ...tial pressure gauge or their equivalent may be used to check the air velocity in the duct A78 2093 00 SAMPLING TUBE FILTERS CONDUIT HOLES DUCT DETECTOR HOUSING TERMINAL STRIP DUCT DETECTOR COVER SAMPLING TUBE MOUNTING SCREWS DETECTOR HEAD SUPPLIED SEPARATELY EXHAUST FILTER ADAPTER DETECTOR BASE INLET SAMPLING TUBE SUPPLIED SEPARATELY O RINGS FOAM GASKETS HOUSING MOUNTING SCREWS TEST MAGNET TUBE EN...

Page 3: ...ations of tube mounting configurations with respect to air flow A Installation for Ducts Less Than 8 Feet Wide 1 If the inlet tube is longer than the width of the air duct drill a 3 4 inch hole in the duct directly opposite the hole already cut for the inlet tube If the inlet tube is shorter than the width of the air duct install the end cap into the inlet tube see Figure 3 2 Slide the inlet tube ...

Page 4: ...rted by other means WARNING AIR FLOW DIRECTION DUCT DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DUCT DETECTOR HOUSING INLET TUBE EXHAUST TUBE AIR FLOW DIRECTION INLET TUBE EXHAUST TUBE INLET TUBE EXHAUST TUBE DUCT DETECTOR HOUSING AIR FLOW DIRECTION EXHAUST TUBE INLET TUBE DUCT DETECTOR HOUSING Figure 4 Tube mounting configurations with varying air flow direct...

Page 5: ...nder the plate and tightening the clamping plate screw Step 6 Install the Filters Most duct installations are subject to dust accumulation System filters remove a large percentage of this contamina tion but cannot remove all of it Dust inside the duct detec tor causes problems First very fine particles of dust can enter the detector sensing chamber and cause the unit to go into alarm Second the ac...

Page 6: ... UNIT 95mA CURRENT DRAW 4 5 3 2 1 Unused Remote Test RA400Z RTS451 RTS451KEY RA400Z or RTS451 RTS451KEY Comm Line Comm Line Alarm Initiation Loop Comm Line UL Listed Control Panel 1st Detector in Loop 2nd Detector in Loop The RTS451 RTS451KEY test coil circuit requires an external 24VDC power supply which must be UL listed Figure 5C System wiring diagram for duct detectors using a UL listed contro...

Page 7: ...not sense smoke in the air duct 7 2 Alarm Tests Before replacing the duct housing cover the detector inter connections should be checked The DH500 may be checked as follows A M02 04 00 Magnet Test 1 Make sure power is applied to the detector 2 Place the painted surface of the test magnet against the housing next to the rib molded onto the outside of the housing see Figure 7 3 The LEDs on the detec...

Page 8: ...n their prop er positions Tighten the four cover screws to 10 in lbs Step 9 Perform the Final System Check Place the magnet in position as shown in Figure 7 The LEDs on the detector should light Any accessory LED s will also light The system control panel should indicate an alarm condition Periodic Maintenance Requirements Air duct smoke detectors should be maintained at least once a year They sho...

Page 9: ...n by aligning arrow on top with the field test slot on the base of the detector Push screen into place Screen should fit tightly to chamber Ionization Units 9 Remove the detector cover and screen assembly by depressing the three lock prongs on the top of the cover and rotating the cover counterclockwise The CRT400 Cover Removal Tool makes cover removal easier See Figure 11 10 Carefully pull the sc...

Page 10: ...mote LED RA400ZA Remote Test Station RTS451 RTS451KEY Piezo Alert Sounder PA400 Replacement Filters F36 05 00 Magnet M02 04 00 End Plug For Sampling Tube P48 21 00 Installation Kit Parts bag A2650 01 Ionization Replacement Screen RS14 Sensitivity Test Kit MOD400 Ionization Cover Removal Tool CRT400 Programming Specifications Requirements for Intelligent System Control Panels The 1551 and 2551 mode...

Page 11: ... 7672 for a Return Authorization number send defective units postage prepaid to System Sensor Repair Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modifications or alterations...

Page 12: ...___________ ______________________________ ________ ____________ ________ ______________ ______________________________ ________ ____________ ________ ______________ ______________________________ ________ ____________ ________ ______________ ______________________________ ________ ____________ ________ ______________ ______________________________ ________ ____________ ________ ______________ ___...

Reviews: