System Sensor BEAM200 Installation And Maintenance Instructions Manual Download Page 2

D400-74-00 

I56-2289-005R

remotely connected to the remote Alarm and Trouble outputs. These outputs 
mimic the functions of the detector’s red and yellow LEDs. In addition to these 
indicators, there is a dual digital display that reads 00 to 99. This display is 
used to indicate the signal strength of the beam in alignment mode and to 
indicate  the  sensitivity  setting  of  the  detector  in  percent  obscuration  when 
setting the sensitivity of the detector. No additional equipment is needed for 
alignment of the beam.

SPECIAL APPLICATIONS

Due to the inherent capabilities of projected type beam detectors they are often 
installed in locations where spot-type detection is impractical. Projected type 
beam  smoke  detectors  are  ideally  suited  for  environmental  conditions  that 
might include high ceilings, dusty and dirty environments, or environments 
that experience temperature extremes. Often these conditions present special 
problems for the installation of spot-type detectors and even greater problems 
for their proper maintenance. Due to the inherent flexibility of mounting loca-
tions and large coverage area of projected type beam detectors often the condi-
tions above can be addressed or minimized.

Some examples of applications for beam detectors might include freezers, air-
craft hangars, cold storage warehouses, shipping warehouses, enclosed park-
ing facilities, sporting arenas and stadiums, concert halls, barns, or stables. 
Some  of  these  environments  might  be  considered  to  hostile  for  spot-type 
smoke detectors. If the environment is considered to be hostile then the colder 
alarm threshold settings should be used.

Before  installing  the  transmitter/receiver  unit  or  reflector  in  these  types  of 
applications special consideration should be given to Ensure proper operation 
of the beam detector. The beam detector should not be installed in environ-
ments  where  there  is  no  temperature  control  and  condensation  or  icing  is 
likely. Condensation or icing of the reflector surface or the outer surface of 
the transmitter/receiver unit will obscure the light beam resulting in a false 
alarm. If elevated humidity levels and rapidly changing temperatures can be 
expected then condensation will likely form and the application should not be 
considered acceptable for the beam detector. The beam detector should not be 
installed in locations where the transmitter/receiver unit, the reflector, or the 
optical pathway between them may be exposed to outdoor conditions such as 
rain, snow, sleet, or fog. These conditions will impair the proper operation of 
the detector and must be avoided.

APPROvED ACCESSORIES

The following accessories can be purchased separately for use with this beam 
detector.

BEAMLRK

The BEAMLRK allows System Sensor reflected beam detectors to be installed 
at separations between 230 and 328 feet (70 to 100 meters). At these distances, 
four 8˝×8˝ reflectors must be used to provide enough reflected infrared light. 
This kit includes 3 additional reflectors with new test scale legends. The re-
flector included with the transmitter/receiver unit is the fourth reflector to be 
used. This kit is not compatible with the multi-mount kit (BEAMMMK).

BEAMMMK

The  BEAMMMK  allows  System  Sensor  reflected  beam  detectors  and  reflec-
tors to be mounted to either a vertical wall or the ceiling. The kit allows for 
additional alignment range in cases where the detector and reflector cannot 
be mounted within 10° of each other. The kit includes the hardware neces-
sary  to  mount  either  a  single  transmitter/receiver  unit  or  a  single  reflector. 
(To mount the transmitter/receiver the surface mount kit, BEAMSMK, must 
also be used). If the transmitter/receiver and the reflector require additional 
alignment range two kits are required. The kit is not compatible with the long-
range reflector kit (BEAMLRK). 

BEAMSMK

The BEAMSMK allows System Sensor reflected beam detectors to be mounted 
when surface wiring is used. This kit must be used when mounting the trans-
mitter/receiver unit with the multi-mount kit (BEAMMMK).

6500-MMK

The 6500-MMK provides a heavy-duty multi-mount bracket for installations 
prone to building movement or vibration.  It offers similar tilt and swivel flex-
ibility found on the BEAMMMK.  (To mount the transmitter/receiver to the 
6500-MMK, the surface mount kit, 6500-SMK, must be used).

6500-SMK

The  6500-SMK  allows  the  transmitter/receiver  to  be  mounted  to  the  6500-
MMK heavy duty multi-mount kit

BEAMHK

The BEAMHK allows the transmitter/receiver unit to operate in environments 
prone to the formation of condensation. Condensation forming on the beam 
detector unit may result in trouble or false alarm conditions. BEAMHK will 
lessen the likelihood of condensation by maintaining the unit at a temperature 
that is slightly higher than the surrounding air. Please refer to the BEAMHK 
installation manual for operation instructions.

BEAMHKR

The BEAMHKR allows the reflector to operate in environments prone to the 
formation of condensation. Condensation forming on the reflector may result 
in trouble or false alarm conditions. BEAMHKR will lessen the likelihood of 
condensation  by  maintaining  the  reflector  at  a  temperature  that  is  slightly 
higher than surrounding air. The kit requires a 24V power supply. When used 
with the long-range reflector kit (BEAMLRK), it is necessary to purchase and 
install four BEAMHKR kits. Please refer to the BEAMHKR installation manual 
for operation instructions.

RTS451/KEY or RTS151/KEY

The remote test accessory, allows for the beam detector to be tested remotely. 
The test accessory provides test and reset functions and green and red LED’s 
that mimic the LED’s on the detector.

PARTS LIST
Description 

Quantity

Transmitter/Receiver Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Paintable Trim Ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Reflector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Plug-in Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Isolator Shunts  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Instruction Manual  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Orange Sticky Paper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

PARTS DIAgRAM (NOT TO SCALE)

TERMINAL BLOCK

ISOLATOR

SHUNT

PAINTABLE TRIM RING

C0306-01

DETECTOR PLACEMENT

This section of the manual discusses the placement of projected beam detec-
tors. Though this information is based upon industry expertise, it is intended 
to be used only as a technical guide. Always comply with the requirements of 
applicable codes and standards such as, NFPA 72, National Fire Alarm Code, 
as well as directives of the Authority Having Jurisdiction (AHJ). For general 
information  on  the  placement  of  detectors,  read  System  Sensor’s  Projected 
Beam Detector Application Guide.

Projected beam detectors are usually located with their beams parallel to the 
ceiling. However, they can be mounted vertically or at any angle to protect the 
area involved. Since beam detectors sense the smoke buildup over a distance, 
they are ideal for locations with high ceilings. They can also be mounted on a 
wall or ceiling below the level of a spot type detector, reducing the effects of 
air stratification. Some typical locations would include large areas with high 
ceilings such as atriums, warehouses, and factories. 

NOTE: Projected beam smoke detectors should always be mounted to stable 
mounting surfaces. See the MOUNTING LOCATION section for details.

Summary of Contents for BEAM200

Page 1: ...1 communication every 5 sec LED flashing SLC 24 V Max Alarm LED on 8 5mA Max Max Trouble LED on 4 5mA Max Max Alignment 20mA Max External Supply BEAM200S only VOLTAGE 15 to 32 VDC CURRENT 0 5A Max Remote Output alarm VOLTAGE 15 to 32 VDC NOTE Output voltage same as device input voltage CURRENT 15mA maximum 6mA minimum NOTE Output current is limited by 2 2Kohm resistor I56 2289 005R 3825 Ohio Avenu...

Page 2: ... The kit includes the hardware neces sary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receiver the surface mount kit BEAMSMK must also be used If the transmitter receiver and the reflector require additional alignment range two kits are required The kit is not compatible with the long range reflector kit BEAMLRK BEAMSMK The BEAMSMK allows Syste...

Page 3: ...ures size and shape of the room and bays occupancy and uses of the area ceiling height ceiling shape surface and obstructions ventilation ambi ent environment burning characteristics of the combustible materials present and the configuration of the contents in the area to be protected Figure 3 Sloped ceiling shed type S 3 FT 0 9M MAX S 1 2 S MAX Tx Rx REFLECTOR C0256 00 Figure 4 Sloped ceiling pea...

Page 4: ...detector will not be able to distinguish these reflections from those of the re flector and the protected space will be compromised Panes of glass will also absorb some of the light as it passes through it This absorption of light will reduce the acceptable installed distance between the detector and the reflector In cases where operation through panes of glass cannot be avoided some spe cific ins...

Page 5: ...r alignment of the product If the detector and reflector are mounted per Mounting Loca tions and Mounting Instructions sections of this manual and the alignment procedures are executed properly false alarms and nuisance trouble signals will be minimized Pre Alignment Checklist Ensure that both the detector and reflector are mounted securely to stable surfaces Ensure that all wiring is correct Ensu...

Page 6: ...ncrease the electronic gain 4 Once satisfied that it is not possible to achieve a higher reading on the display depress the alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not...

Page 7: ...t the isolator is disabled This is the default state Sensitivity Selection The detector has six sensitivity selections Each of these selections is only acceptable over a specific distance separation between the detector and the reflector per UL268 The chart below is used to determine which selections are acceptable for your installed distance The sensitivity of the detector can be set only when th...

Page 8: ...m of 1 minute 3 Place the blocking material over the reflector lining it up with the graduated marks that are 10 more than the detectors setting in obscuration The detector should enter alarm within 1 minute Figure 14 Reflector Test Card Procedure LINE UP EDGE OF TEST CARD WITH APPROPRIATE OBSCURATION LEVEL MOVE TEST CARD TO DESIRED AMOUNT OF OBSCURATION C0267 00 4 The detector can be reset with t...

Page 9: ...h to work Maintenance NOTE Before cleaning the detector notify the proper authorities that the smoke detector system is undergoing maintenance and therefore the system will be temporarily out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms 1 Carefully clean the outer housing lens face A damp soft cloth with a mild soap may be used Avoid products with solvent...

Page 10: ...er Range Off 2 Quick Blinks Blink Blink Off Increase of Reflected Signal Inspect line of sight between detector and reflector for reflective objects in the pathway Trouble Beam Blockage Response Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initialization alignment exit...

Page 11: ...Scale 1 1 D400 74 00 11 I56 2289 005R Appendix II Detector Drilling Template 4 345 6 190 157 mm 110 mm ...

Page 12: ...D400 74 00 12 I56 2289 005R ...

Page 13: ...Appendix III Reflector Drilling Template Scale 1 1 5 512 140mm 8 465 215mm D400 74 00 13 I56 2289 005R ...

Page 14: ...D400 74 00 14 I56 2289 005R ...

Page 15: ...o not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state Three Year Limited Warranty FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 Thi...

Reviews: