System Sensor B501AP-IV Installation Instructions Download Page 1

Pittway Tecnologica S.r.l., Via Caboto 19/3, 34147 Trieste, Italy

© System Sensor 2009    

I56-2668-002

1

D550-33-00

B501AP / B524HTR

1

2

3

4

60 mm

SHIELD

102 mm

Notes:  
1.  The B524HTR requires an external power supply to drive the heater resistors
2.  Ensure all terminals are fully screwed home prior to installation of the sensor
3.  A  self  adhesive  address  tag  is  available  for  use  with  the  B524HTR,  which 

is  stuck  to  the  side  of  the  base,  and  labelled  as  appropriate  to  allow  the 
sensor  address  to  be  determined  without  removal  of  the  sensor  head

B501AP (-IV, -BK)

Address Tag 

Height 

22.5 mm

Weight 

39 g

INSTALLATION INSTRUCTIONS FOR B501AP (-IV, -BK) AND 

B524HTR INTELLIGENT SENSOR BASES 

Before  installing  bases,  please  thoroughly  read  System  Sensor’s  Guide  to 
Intelligent Fire Systems, which gives information on sensor spacing, placement, 
zones and applications.  Copies are available from System Sensor at no charge.
GENERAL DESCRIPTION
These bases are designed for use with all System Sensor 500, 200, 200+ and 
200  Advanced  intelligent  ranges  of  sensors  and  their  variants  (

Note:  If  the 

B524HTR is used with 200 Advanced Isolator sensors, the isolator feature will not 
function.  The standard B501AP is white, an 

IV suffix indicates the base is ivory in 

colour, a 

BK suffix indicates the base is black.  Please refer to the control panel 

manufacturer for compatibility information.
INSTALLATION
Mounting
The sensor base should be mounted using pan headed screws, with a maximum 
diameter  of  4mm,  and  with  a  maximum  head  diameter  of  8mm.    If  required, 
suitable junction boxes may be used.  Standard mounting hole centres are 60mm, 
however the B501AP offers from 50mm to 60mm and the B524HTR from 51mm 
to 60mm.
The  B501AP  features  knock-outs  in  the  side  of  the  base  to  allow  the  access 
of  surface  mounted  cabling.    Match  the  markings  on  the  knock-outs  to  ensure 
perpendicular or opposed points (either blank or marked 

I or II).

Wiring
All wiring should be installed in compliance with local codes and standards, and 
the authority having jurisdiction.
The  base  terminals  are  designed  to  accept  cables  with  cross  sectional  areas 
between 0.75mm² and 2.5mm².  Reference should always be made to the control 
panel specifications for acceptable cable parameters.
Note:  To ensure supervision of contacts, the wire run must be broken.  Do not loop 
the wire under the terminals.
See diagrams opposite for wiring details.
Tamper Resist Feature
B500 bases also include a tamper resist feature, which when activated prevents 
removal of the sensor head without the use of a tool.
To activate this feature, break off the tab on the base prior to installing the sensor 
(figure 1a).  To remove the sensor once this tamper resist is activated, place a 
small bladed screwdriver into the slot on the side of the base, push the lever away 
from the sensor and rotate the sensor anti clockwise (see figure 1b).
Note:  Do not activate the feature if a head removal tool is to be used; this feature 
is not reversible without damaging the base.

REMOTE ANNUNCIATOR OPTION
The RA100Z Remote Annunciator LED is available as an optional accessory.  This 
unit has a rectangular plate, which fits US single gang light switch boxes.
If a different remote annunciator is to be used, ensure that it is suitably rated for 
operation with System Sensor intelligent sensors:  22.5V, 10.8mA at 24VDC supply.

Figure 1a:  Activation of Tamper Resist Feature

Plastic Lever

Break tab at dotted line by twisting 
towards centre of base

Figure 1b: Removing Sensor Head From Base

Use a small bladed screwdriver to push 
plastic in the direction of the arrow.

B501AP (-IV, -BK) BASE
If the sensor address needs to be visible without the removal of the sensor head, 
break off the address tag from inside the base and place in the slot on the outside 
of the base as required.
The tamper resist tab is located in the wall of the base between terminals 2 and 4.

Compatib

le Contr

ol P

anel

Remote Indicator  

22.5V Nominal

Terminal 

1:  Loop (-) In and Out  and Remote Annunciator (-)

Terminal 

4:  Loop (+) Out

Terminal 

2:  Loop (+) In

Terminal 

3:  Remote Annunciator (+)

B524HTR HEATER BASE
This base contains an anti-condensation heater and is suitable for low temperature 
applications.
B524HTR Specifications:
Diameter: 

103 mm

Height: 

36 mm

Weight: 

92 g

Maximum Voltage: 

32 V (dc or ac)

Power at 24V: 

1.9 W

Maximum permissible peak power: 4W
Equivalent heating resistor value:  300 Ohms
Operating temperature: 

-30°C to +60°C

Operating humidity range:  10% to 93% Relative Humidity (Non-condensing)

60 mm

Address Tag

Z3 A55

Tamper Resist Tab

Terminal Strip

(See Table)

Terminal 

PCB 

Label 

Connection 

HTR+ 

HTR+:  Heater Power Supply 

HTR- 

HTR-:  Heater Power Supply 

Not Used (Shield) 

L+ 

Loop + 

L- 

Loop - 

LR+ 

Remote Annun 

 

ENGLISH

1

2

3

4

-

-

-

+

+

+