background image

B200SR-LF-WH/B200SR-LF-IV TERMINALS

No. Function

1.  Not Used

2.  Positive (+) Comm. Line In and Out

3.  Negative (-) Comm. Line In and Out

4.  External Supply Positive (+)

5.  External Supply Negative (-)

6.  Sounder Base Interconnect  

MOUNTING

Mount the B200SR-LF-WH/B200SR-LF-IV mounting plate directly to an electri-
cal box. The plate will mount directly to 4" square (with and without plaster 
ring), 4" octagon, 3

1

/

2

" octagon, single gang or double gang junction boxes.

1. Connect field wiring to terminals, as shown in Figure 1 and 2.
2. Attach the mounting plate to the junction box as shown in Figure 3.
3.  To mount the sounder base, hook the tab on the sounder base to the groove 

on the mounting plate.

4.  Then, swing the sounder base into position to engage the pins on the  

product with the terminals on the mounting plate.

5. Secure the sounder base by tightening the mounting screws.

6.  Install a compatible smoke sensor as described in the installation manual 

for the sensor.

CAUTION

Do not over tighten mounting plate screws; this may cause mounting plate 
to flex.

FIGURE 3: MOUNTING

 

Location of jumper–

remove to enable 

continuous tone

 C0891-10

TAMPER RESISTANT FEATURE

NOTE: Do not use the tamper-resist feature if the removal tool is to be used. 
This detector base includes a tamper-resist feature that prevents its removal 
from the base without the use of a tool. To activate this feature, break the tab 
from the detector base as shown in Figure 4A. Then, install the detector. To 
remove the detector from the base once the tamper-resist feature has been 
activated, insert a small-bladed screwdriver into the slot from the top and 
press down on the lever (see Figure 4B). This allows the detector to be rotated 
counterclockwise for removal. The tamper-resist feature can be defeated by 
breaking and removing the plastic lever from the base. However, this prevents 
the feature from being used again.

TESTING AND MAINTENANCE

Sensors and bases must be tested after installation and as an integral part of 
a periodic maintenance program. Test the B200SR-LF-WH/B200SR-LF-IV as 
follows: 

NOTE: Before testing, notify the proper authorities that the smoke sensor 
system is undergoing maintenance and, therefore, will be temporarily out of 
service. Disable the system undergoing maintenance to prevent unwanted 
alarms.
1.  If configured as in Figure 5 and 6, reverse the polarity of the external 24VDC 

supply. If configured as in Figure 6, turn on the Intelligent Relay Module. 
All B200SR-LF-WH/B200SR-LF-IV bases on the loop should sound.

2.  Latch the sensor LED on from the control panel. That individual sensor’s 

B200SR-LF-WH/B200SR-LF-IV should sound.

When performing maintenance on connected smoke sensors, carefully note 
the location and address of each removed sensor.

FIGURE 4A. ACTIVATING THE TAMPER-RESIST FEATURE

PLASTIC LEVER

BREAK TAB AT

DOTTED LINE BY

TWISTING TOWARD

CENTER OF BASE.

   C0144B-01

USE SMALL-BLADED

SCREWDRIVER TO

PUSH PLASTIC LEVER

IN DIRECTION OF

ARROW.

 

 C0144B-01

FIGURE 4B. REMOVING THE DETECTOR HEAD FROM THE BASE

SLOT

SLOT

C1082-00

  

I56-4152-005 

 

 02/01/2018

Reviews: