System Sensor 7251DH Installation And Maintenance Instructions Manual Download Page 5

SS-400-000 

I56-3065-000R

2.   To  determine  that  smoke  is  capable  of  entering  the  sensing 

chamber,  a  visual  examination  should  be  conducted  to  note 
any obscurations around the sensing chamber. If a smoke test is 
required, smoke such as cigarette, cotton wick, or punk smoke 
may  be  blown  directly  at  the  smoke  detector  head.  It  is  im-
portant to plug the exhaust and sampling tube hole to prevent 
ducted air from blowing smoke away from the smoke detector 
head. Record all test records in the Detector Test Log (page 8).

CAUTION

Remember to remove the plugs after this test or the detector will 
not sense smoke in the air duct.

Figure 6. Sampling tube filter installation:

SAMPLING TUBE

FILTERS

SAMPLING TUBE

MOUNTING

SCREWS

DETECTOR HEAD

EXHAUST 

FILTER ADAPTER

DETECTOR BASE

INLET SAMPLING TUBE

FOAM GASKET

H0548-00

8.2 Alarm Tests

Before  replacing  the  duct  housing  cover,  the  detector  intercon-
nections  should  be  checked.  The  7251DH  may  be  checked  as 
follows:
A.  M02-04-00 Magnet Test
 

1. Make sure power is applied to the detector.

 

2.  Place  the  painted  surface  of  the  test  magnet  against  the 

housing next to the indentation molded onto the outside of 
the housing (see Figure 7).

 

3.  The LEDs on the detector should latch on as should any ac-

cessories (i.e. RA400ZA, RTS451), and the alarm condition 
should be verified at the control panel.

Figure 7. Testing detector

INDENTATION

TEST

MAGNET

PAINTED SIDE

TOWARD HOUSING

DUCT

DETECTOR

HOUSING

DETECTOR

HEAD

H0579-00

Figure 8. Detector head removal:

TWIST

COUNTERCLOCKWISE

TO REMOVE

DUCT

HOUSING

TWIST

CLOCKWISE

TO INSTALL

DETECTOR

HEAD

H0546-00

B. RTS451/RTS451KEY Remote Test Station

The  RTS451/RTS451KEY  Remote  Test  Station  facilitates  test  of  the 
alarm  capability  of  the  duct  smoke  detector  as  indicated  in  the 
RTS451/RTS451KEY  manual.  The  7251DH  duct  detector  cannot  be 
reset by the RTS451/RTS451KEY. It must be reset at the system control 
panel.
To install the RTS451/RTS451KEY test coil, connect the device as 
shown in Figure 11; wire runs must be limited to 25 ohms or less 
per  interconnecting  wire.  Place  the  coil  in  the  detector  housing 
with the arrow facing up and pointing toward the detector as in 
Figure 11. Attach the coil leads to the housing terminals as shown; 
polarity is not important. Firmly screw the bracket in place over 
the test coil. 

8.4 Trouble Test

The  capability  of  “TROUBLE”  detection  is  tested  by  removing 
the  detector  head  from  the  duct  housing.  The  detector  head  is 
removed by turning it counterclockwise about 10 degrees (Figure 
8). The system control panel should indicate a trouble condition. 
Reinserting the detector head should clear the trouble condition.

Step 9. Install the Cover

Install the cover using the four screws. Be certain filters are in-
stalled as specified in Step 7. Make sure that the cover fits into 
the base groove and that all gaskets are in their proper positions. 
Tighten the four cover screws to 10 in/lbs.

Step 10. Perform the Final System Check

Place the magnet in position as shown in Figure 7. The LEDs on 
the  detector  should  light.  Any  accessory  LED(s)  will  also  light. 
The system control panel should indicate an alarm condition.

Periodic Maintenance Requirements

Air  duct  smoke  detectors  should  be  maintained  at  least  once  a 
year. They should be maintained more often if the detector heads 
become  obviously  dirty  in  less  than  a  year.  The  detectors  must 
also be cleaned immediately after a fire (see cleaning section on 
Page 7). Failure to properly maintain air duct smoke detectors may 
cause unnecessary false alarms.
It is recommended that a permanent Detector Test Log be set up 
and maintained, with a record for each individual smoke detector 
in each building. Each detector should be clearly described, with 
information on the type of detector, the model number, the serial 
number (if any), the location, and the type of environment. Data 
entries should include test dates, type of test mode, test results, 
maintenance,  and  comments.  A  detector  test  log  is  included  in 
this manual.

firealarmresources.com

Summary of Contents for 7251DH

Page 1: ...Station Specifications Length 14 5 inches 36 7 cm Width 5 inches 12 7 cm Depth 3 5 inches 8 9 cm Weight 2 8 lbs 1 1 kg Operating Temperature Range 32 to 100 F 0 to 38 C Operating Humidity Range 10 to 93 Relative Humidity Duct Air Velocity 300 4000 ft min Voltage Range 15 32 VDC Peak Standby Current nominal 230uA at 24 VDC no communication 330uA at 24 VDC one communication every 5 sec with LED enab...

Page 2: ...uct Air Flow Direction and Velocity The 7251DH is designed to be used in air handling systems having air velocities of 300 to 4000 feet per minute Be sure to check en gineering specifications to ensure that the air velocity in the duct falls within these parameters If necessary an Alnor Model 6000 P velocity meter Dwyer 460 differential pressure gauge or their equivalent may be used to check the a...

Page 3: ... Figure 3B Installation of foam gaskets over sam pling tube bushings B Installation for Ducts More Than 8 Feet Wide NOTE To install inlet tubes in ducts more than 8 feet wide work must be performed inside the air duct Sampling of air in ducts wider than 8 feet is accomplished by using the ST 10 inlet sam pling tube Install the inlet tube as follows 1 Any tube over 3 feet long that doesn t protrude...

Page 4: ... EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE INLET TUBE INLET TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION EXHAUST TUBE INLET TUBE DETECTOR HOUSING A B C D HORIZONTAL MOUNTING OF HOUSING VERTICAL MOUNTING OF HOUSING Figure 5 Tube mounting configurations with varying air flow direction and orientation of detector housing Vertical as well as horizontal mounting is acceptable H0109 00 the a...

Page 5: ...all the RTS451 RTS451KEY test coil connect the device as shown in Figure 11 wire runs must be limited to 25 ohms or less per interconnecting wire Place the coil in the detector housing with the arrow facing up and pointing toward the detector as in Figure 11 Attach the coil leads to the housing terminals as shown polarity is not important Firmly screw the bracket in place over the test coil 8 4 Tr...

Page 6: ...ine Comm Line Alarm Initiation Loop Comm Line ULC Listed Control Panel 1st Detector in Loop 2nd Detector in Loop The RTS451 RTS451KEY test coil circuit requires an external 24VDC power supply which must be UL listed Figure 9C System wiring diagram for duct detectors using a ULC listed control panel Figure 9A Figure 9B H0542 00 DETECTOR HEAD TEST COIL H0292 00 Figure 11 RTS451 RTS451KEY test coil i...

Page 7: ...y vacuuming or blowing out dust and particles 5 Replace the sensing chamber cover aligning the arrow on the top with arrow on the printed circuit board 6 To replace the screen place it over the chamber assembly turning it until it snaps into place 7 Replace the cover using the LEDs to align the cover and then gently pushing it until it locks into place 8 Reinstall the detector 9 Test the detector ...

Page 8: ...T LOG Detector Identification Information Manufacturer Detector Model Serial Number Date Installed Description of Detector Location The Results and Maintenance Data Date Tested Test Description Test Results Maintenance Performed Comments firealarmresources com ...

Reviews: