background image

D400-29-00

3

I56-580-04R

B. Test Module (System Sensor Model No. MOD400 or

MOD400R)

The MOD400 or MOD400R is used with a DMM or volt
meter to check the detector sensitivity as described in
the module’s manual.

C. Direct Heat Method (Hair dryer of 1000 - 1500 watts)

From the side of the detector, direct the heat toward the
sensor. Hold the heat source about 15 cm away to pre-
vent damage to the cover during testing.

NOTE:

If a detector goes into alarm, it will reset only if the
detector has cooled and if its power is momentari-
ly interrupted. Check the control panel being used
to determine whether the RESET switch (or some
other auxiliary device or control) momentarily cuts
off power to the detector loop.

Detectors that fail these tests should be cleaned as
described under MAINTENANCE and retested. If the detec-
tors still fail these tests they should be returned for repair.

Maintenance

The 5451 detector has been designed to be as maintenance-
free as possible. Normal air-borne dust, however, can accu-
mulate on the detector’s sensing elements and cause them
to become less sensitive. All detectors should be tested and
cleaned at least once a year, and those in dustier areas
should be tested and cleaned more often. Detectors must
also be cleaned and tested immediately after a fire.

Before cleaning, notify the proper authorities that the sys-
tem is undergoing maintenance and therefore the system
will temporarily be out of service. Disable the loop or sys-
tem undergoing maintenance to prevent unwanted alarms.

1. Remove detector from mounting base.

2. Use a vacuum cleaner to remove dust from the sensing

chamber.

3. Reinstall the detector.

4. Test detector as described under TESTING.

Summary of Contents for 5451

Page 1: ...this equipment IMPORTANT This detector must be tested and maintained regularly following NFPA 72 requirements The detector should be cleaned at least once a year General Description Model 5451 is a rate of rise with fixed temperature alarm thermal detector utilizing a state of the art dual thermistor sensing circuit These detectors are designed to provide open area protection with 50 foot spacing ...

Page 2: ...per Resistance The detector bases include a feature that when activated prevents removal of the detector without the use of a tool Refer to the installation instruction manual of the detector base to make use of this capability Testing Before testing notify the proper authorities that the heat detector system is undergoing maintenance and therefore the system will temporarily be out of service Dis...

Page 3: ...d be cleaned as described under MAINTENANCE and retested If the detec tors still fail these tests they should be returned for repair Maintenance The 5451 detector has been designed to be as maintenance free as possible Normal air borne dust however can accu mulate on the detector s sensing elements and cause them to become less sensitive All detectors should be tested and cleaned at least once a y...

Page 4: ...OR2 736 7672 for a Return Authorization number send defective units postage prepaid to System Sensor Repair Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modifications or alte...

Reviews: