System Sensor 2D51A Installation And Maintenance Instructions Download Page 2

for five seconds. Wait two minutes for the duct smoke detector to alarm. If the 

duct smoke detector alarms, air is flowing through the detector. Remove the 

duct smoke detector cover and blow out the residual aerosol smoke from the 

chamber and reset the duct smoke detector. Use duct tape to seal the aerosol 

smoke entry hole.
*Aerosol smoke can be purchased from Home Safeguard Industries, model 

25S Smoke Detector Tester, Malibu, CA. Phone: 310/457-5813.  When used 

properly, the canned smoke agent will cause the smoke detector to go into 

alarm.  Refer to the manufacturer’s published instructions for proper use of 

the canned smoke agent.

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary 

by manufacturer.  Misuse or overuse to these products may have long term 

adverse  effects  on  the  smoke  detector.    Consult  the  canned  smoke  agent 

manufacturer’s  published  instructions  for  any  further  warnings  or  caution 

statements.

SENSITIvITY vERIFICATION

The sensitivity of the sensor is confirmed to be operating within its allowable 

range each time the sensor and power board LEDs blink every 5 seconds. 

Note in a maintenance condition the sensor LEDs will blink red every 5 sec-

onds and power board will blink amber. The maintenance condition indicates 

that the sensor is operating outside its original factory preset sensitivity and 

shall be cleaned or replaced. This is a valid UL test.
Notify the proper authorities that the system is back on line.
Detectors that fail these tests should be cleaned as described below and re-

tested. If the detectors still fail these tests, they should be returned for repair.

CLEANINg

Before  removing  the  detector,  notify  the  proper  authorities  that  the  smoke 

detector  system  is  undergoing  maintenance  and  will  be  temporarily  out  of 

service. Disable the zone or system undergoing maintenance to prevent un-

wanted alarms.
1.  Remove the sensor to be cleaned from the system.
2.   Remove the sensor cover by pressing firmly on each of the four removal 

tabs that hold the cover in place.

3.   Vacuum the screen carefully without removing it. If further cleaning is 

required continue with Step 4, otherwise skip to Step 7.

4.  Remove the chamber cover/screen assembly by pulling it straight out.

FIgURE 1. CO-LOCATED INNOvAIR FLEx DUCT SMOKE DETECTOR:

SENSOR UNIT

TEST MAGNET 

POSITION

LED STATUS INDICATORS

POWER BOARD UNIT

H0614-00

5.   Use  a  vacuum  cleaner  or  compressed  air  to  remove  dust  and  debris 

from the sensing chamber.

6.   Reinstall the chamber cover/screen assembly by sliding the edge over 

the sensing chamber. Turn until it is firmly in place.

7.   Replace the cover using the LEDs to align the cover and then gently 

pushing it until it locks into place. 

8.  Reinstall the detector.

REINSTALLATION

1.  Reinstall the detector in its housing.
2.  Restore system power. 
3.  Perform Detector Check.
4.   Notify the proper authorities testing has been completed and the smoke 

detector system is back in operation.

FIgURE 2:

SENSOR 

COVER

SENSING 

CHAMBER 

COVER AND 

SCREEN

SENSOR 

CHAMBER

COVER 

REMOVAL 

TABS

C1009-00

SS-300-017 

I56-3328-000 

 

 

©2008 System Sensor 

System Sensor warrants its enclosed smoke detector to be free from defects in materials 

and workmanship under normal use and service for a period of three years from date 

of manufacture. System Sensor makes no other express warranty for this smoke detec-

tor. No agent, representative, dealer, or employee of the Company has the authority to 

increase or alter the obligations or limitations of this Warranty. The Company’s obligation 

of this Warranty shall be limited to the repair or replacement of any part of the smoke 

detector which is found to be defective in materials or workmanship under normal use 

and  service  during  the  three  year  period  commencing  with  the  date  of  manufacture. 

After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return 

Authorization number, send defective units postage prepaid to: System Sensor, Repair 

THREE-YEAR LIMITED WARRANTY

Department, RA #__________, 6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5. 

Please  include  a  note  describing  the  malfunction  and  suspected  cause  of  failure.  The 

Company shall not be obligated to repair or replace units which are found to be defective 

because  of  damage,  unreasonable  use,  modifications,  or  alterations  occurring  after  the 

date of manufacture. In no case shall the Company be liable for any consequential or inci-

dental damages for breach of this or any other Warranty, expressed or implied whatsoever, 

even if the loss or damage is caused by the Company’s negligence or fault. Some states do 

not allow the exclusion or limitation of incidental or consequential damages, so the above 

limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, 

and you may also have other rights which vary from state to state.

Please refer to insert for the Limitations of Fire Alarm Systems

Reviews: