background image

SS-300-017 

I56-3328-000

2D51A Photoelectric Smoke Detector 

for use with Innovair Flex 4-Wire Duct 

Smoke Detector Housings

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5

1-800-SENSOR2, FAX: 905-812-0771

www.systemsensor.ca

BEFORE INSTALLINg 

Please thoroughly read the System Sensor manual A05-1003, Applications 

Guide for System Smoke Detectors, which provides detailed information on 

detector spacing, placement, zoning, wiring, and special applications. Copies 

of this manual are available from System Sensor. 

NOTICE:

 This manual should be left with the owner/user of this equipment.

IMPORTANT:

 The detector must be tested and maintained regularly following 

CAN/ULC S536 requirements. The detector should be cleaned at least once 

a year.

gENERAL DESCRIPTION

The 2D51A photoelectronic detector uses a state-of-the-art optical sensing 

chamber. This detector is designed to provide protection in duct applications 

when installed with an Innovair Flex 4-wire duct smoke detector housing and 

to be used with ULC listed control panels only.
Two LEDs on each detector provide local visible alarm indication. Refer to 

Table 3 of the Model D4120A installation manual for LED status indications. 

Remote  LED  annunciator  capability  is  standard  and  may  be  implemented 

through a number of optional accessories. See applicable Innovair Flex duct 

smoke detector installation manual for more information.. The alarm can be 

reset only by a momentary power interruption. This detector may be tested by 

activating the internal reed switch with a magnet.

BASE SELECTION AND WIRINg gUIDE

Refer to the applicable Innovair Flex 4-wire duct smoke detector installation 

instructions for detector head and wiring instructions. 

INSTALLATION

NOTE:

 All wiring must conform to applicable local codes, ordinances, and 

regulations.

WARNING

Remove power from initiating-device circuits before installing detectors.

1.  Install detectors:
 

a. Place the detector into the detector base.

 

b.  Turn the detector clockwise until the detector drops into place.

 

c. Continue turning detector clockwise to lock it in place.

2.   Tamper Resistance: The detector bases can be made tamper resistant. 

When capability is enabled, detectors cannot be removed from the base 

without the use of a tool. See the detector base installation manual of 

the detector base for details in using this capability.

3.  After all detectors have been installed, apply power to the control unit.
4.  Test the detector using the magnet as described under TESTING.
5.  Reset the detector at the system control panel or on power board.
6.  Notify the proper authorities that the system is back on line.

CAUTION

Dust covers are an effective way to limit the entry of dust into smoke detector 

sensing  chambers.  However,  they  may  not  completely  prevent  airborne  dust 

particles from entering the detector. Therefore, System Sensor recommends the 

removal of detectors before beginning construction or other dust producing activ-

ity.

SPECIFICATIONS

Height: 

2.0 in

Diameter: 

4.1 in; 6.1 in

Weight: 

3.1 oz. (88 g)

Operating Temperature Range: 

–20°C to 70°C (–4°F to 158°F)

Operating Humidity Range: 

0% to 95% Relative Humidity Non-condensing

Latching Alarm: 

Reset by momentary power interruption

Be sure to remove the dust covers from any sensors that were left in place 

during construction as part of returning the system to service.

TESTINg

Before testing, notify the proper authorities that the smoke detector system 

is undergoing maintenance and will temporarily be out of service. Detectors 

must be tested after installation and as part of periodic maintenance. Test the 

2D51A as follows:

NOTE:

  Before  testing  the  detector,  check  to  ensure  the  the  power  board 

LEDs blink. If they do not, the detector may not have power or may not be 

installed properly (check the wiring), if it is defective, or the detector sensitiv-

ity is outside the listed limits return it for repair.

ALARM TESTS

1a.   Test/Reset Button - Press and hold the test button located on the power 

board cover for at least 2 seconds.

 

      OR

1b.   M02-04-00 Magnet Test - Place the painted surface of the magnet onto 

the MAGNET TEST location on the sensor cover of unit (Figure 1).

2.   The  red  alarm  LED  on  the  sensor  and  the  power  board  should  latch 

on, as should any accessories (i.e. RA400ZA, RTS451). Verify system 

control panel alarm status and control panel execution of all intended 

auxiliary functions (i.e fan shutdown, damper control, etc.). 

3.   The detector must be reset by the system control panel, front cover Test/

Reset button, or remote accessory.

4.   To reset using the Test/Reset button on the power board cover simply 

press and release.

RTS451/RTS451KEYA REMOTE TEST STATION

The RTS451/RTS451KEYA Remote Test Station facilitates test of the alarm 

capability  of  the  duct  smoke  detector  as  indicated  in  the  RTS451/RTS-

451KEYA  manual.  The  D4120A  duct  smoke  detector  can  be  reset  by  the 

RTS451/RTS451KEYA. If a system control panel is used, the panel itself may 

also require testing.
To  install  the  RTS451/RTS451KEYA,  connect  the  device  as  shown  in  the 

manual provided with the accessory; wire runs must be limited to 25 ohms or 

less per interconnecting wire. 

SMOKE RESPONSE TESTS

To determine if smoke is capable of entering the sensing chamber, visually 

identify any obstructions. Plug the exhaust and sampling tube holes to pre-

vent ducted air from carrying smoke away from the detector head, then blow 

smoke such as cigarette, cotton wick, or punk directly at the head to cause an 

alarm. REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST, OR THE 

DETECTOR WILL NOT FUNCTION PROPERLY.

SMOKE ENTRY USINg AEROSOL SMOKE

This test is intended for low-flow systems (100-500 FPM). If the air speed is 

greater than 500 FPM, use a conventional manometer to measure differen-

tial pressure between the sampling tubes, as described per the installation 

manual provided with the duct smoke detector. 
Drill a 

1

4

 inch hole 3 feet upstream from the duct smoke detector. With the air 

handler on, measure the air velocity with an anemometer. Air speed must be 

at least 100 FPM. Spray aerosol smoke* into the duct through the 

1

4

 inch hole 

Reviews: