System Sensor 2300TB Installation And Maintenance Instructions Download Page 4

MAINTENANCE:

When removing the detector from a system of more than 1 detector per 
loop, an optional detector bypass plug can be inserted into the screw ter-
minal block in order to maintain the system’s continuity. Order accessory 
model number J2300TB.

NOTE:

  Before removing the detector, notify the proper authorities that the 

smoke detector system is undergoing maintenance and will tem-
porarily be out of service. Disable the zone or system undergoing 
maintenance to prevent unwanted alarms.

NOTE:

  Before removing the detector cover, note the position of the therm-

istors.  Make  sure  the  thermistors  are  seated  and  not  bent  over 
when the cover is replaced.

1. Remove the detector cover by placing a small-bladed screwdriver in the 

cover removal slot and twisting it slightly until the cover can be turned 
counterclockwise for removal.

2. Remove the screen by pulling it straight out. (See Figure 5).
     BE  CAREFUL  NOT  TO  DAMAGE  THE  THERMISTORS.  (See  note 

above). Vacuum the screen thoroughly.

3. Clean the black vaned chamber piece by vacuuming or blowing out dust 

and particles.

4. To re-install the screen, rotate the screen on the housing until it drops 

into the alignment slots. Carefully push the screen onto the base, mak-
ing sure it fits tightly to the chamber. Replacement screens are available 
(order part number RS23).

5. Replace the cover by gently rotating it clockwise until it locks in place. 

CHECK TO MAKE SURE THE THERMISTORS ARE IN AN UPRIGHT 
POSITION.

6. Reinstall  the  detector  into  the  system,  enable  system  operation,  and 

notify the proper authorities that the system is back on line.

�������������������

�������������������

����������������

������������������

���������������

���������������

�����

������������

Figure 5. Removal of cover and screen for 

cleaning.

S0185-00

WARNING

Limitations of Smoke Detectors:

This smoke detector is designed to 

activate and initiate

 emergency action, but will do so only when it is used in conjunction with an authorized fire alarm 

system. This detector must be installed in accordance with NFPA standard 72.

Smoke detectors will not work without power. 

AC or DC powered smoke detectors will not work if the power supply is cut off.

Smoke detectors will not sense fires which start where smoke does not reach the detectors.

 Smoldering fires typically do not generate a lot of heat 

which is needed to drive the smoke up to the ceiling where the smoke detector is usually located. For this reason, there may be large delays in detecting a 
smoldering fire with either an ionization type detector or a photoelectric type detector. Either one of them may alarm only after flaming has initiated which will 
generate the heat needed to drive the smoke to the ceiling.

Smoke from fires in chimneys, in walls, on roofs or on the other side of a closed door(s) may not reach the smoke detector and alarm it. A detector cannot 
detect a fire developing on another level of a building quickly or at all. For these reasons, detectors 

shall be located on every level and in every bedroom 

within a building.

Smoke detectors have sensing limitations, too.

 Ionization detectors and photoelectric detectors are required to pass fire tests of the flaming and smolder-

ing type. This is to ensure that both can detect a wide range of types of fires. Ionization detectors offer a broad range of fire sensing capability but they are 
somewhat better at detecting fast flaming fires than slow smoldering fires. Photoelectric detectors sense smoldering fires better than flaming fires which have 
little, if any, visible smoke. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is always best, and a 
given detector may not always provide early warning of a specific type of fire.

In general, detectors cannot be expected to provide warnings for fires resulting from inadequate fire protection practices, violent explosions, escaping gases 
which ignite, improper storage of flammable liquids like cleaning solvents which ignite, other similar safety hazards, arson, smoking in bed, children playing 
with matches or lighters, etc. Smoke detectors used in high air velocity conditions may have a delay in alarm due to dilution of smoke densities created by 
frequent and rapid air exchanges. Additionally, high air velocity environments may create increased dust contamination, demanding more frequent mainte-
nance.

Smoke detectors cannot last forever.

 Smoke detectors contain electronic parts. Even though smoke detectors are made to last over 10 years, any part 

can fail at any time. Therefore, smoke detectors shall be replaced after being in service for 10 years. The smoke detector system that this detector is used in 
must be tested regularly per NFPA 72. This smoke detector should be cleaned regularly per NFPA 72 or at least once a year.

D300-01-00                                                                             4                                                                              I56-490-05
                                                                                                                                                            © System Sensor 1994 

Summary of Contents for 2300TB

Page 1: ...rms a self test on its smoke sensing chamber and internal electronics every 40 seconds If this test fails the detector stops blinking the status LED in standby and the LED will remain off In alarm the LED will be latched on continuously until the detector is reset The detector provides an output for connection to an optional Remote Annunciator model RA400Z The Remote Annunciator mounts to a single...

Page 2: ...ll wiring should be installed in sepa rate grounded conduit do not mix fire system wiring in the same conduit as any other electrical wiring Twisted pair may be used to provide additional protection against extraneous electrical interference Wire connections are made by stripping about 1 4 inch of insulation from the end of the feed wire inserting the wire into the appropriate terminal and tighten...

Page 3: ...fore testing the detector look for the presence of the flashing LED If it does not flash power has been lost to the detector check the wiring or the unit is defective return for repair A TEST SWITCH 1 A recessed test switch is located on the detector housing See Figure 4 2 Push and hold the recessed test switch with a 0 1 inch maximum diameter tool such as an allen wrench or small screw driver 3 T...

Page 4: ...oke detector is usually located For this reason there may be large delays in detecting a smoldering fire with either an ionization type detector or a photoelectric type detector Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling Smoke from fires in chimneys in walls on roofs or on the other side of a closed door s may...

Reviews: