background image

D100-101-00 

I56-2806-003R

Testing

Before testing, notify the proper authorities that the smoke 
detector system is undergoing maintenance and will tempo-
rarily be out of service. Disable the zone or system under-
going maintenance to prevent unwanted alarms. Detectors 
must  be  tested  after  installation  and  as  part  of  periodic 
maintenance. Test 2151 and 2151T as follows:

NOTE:

  Before  testing  the  detector,  check  to  ensure  the 

LEDs  blink.    If  they  do  not,  the  detector  has  lost  power  
(check the wiring), it is defective (return it for repair), or 
the detector sensitivity is outside the listed limits.
A.  Test Magnet (p/n M02-04-01 or M02-09-00)
  1.  Place  the  magnet  against  the  cover  in  the  location 

designated by the raised mark to activate the test fea-
ture (see Figure 1).

  2.  The LEDs should latch ON within 5 seconds indicat-

ing alarm and annunciating the panel.

LED Status

Indicators

Magnet Test

Marker

Test Magnet 

Position

Test Magnet 

Position

Magnet Test

Marker

SENS-RDR

Location

Figure 1. Bottom and side views showing position of test magnet:

B.  Test Module (SENS-RDR)
  Use  the  SENS-RDR  Sensitivity  Reader  to  measure  the 

sensitivity  of  the  detectors.  Please  refer  to  the  SENS-
RDR instruction manual for operating details.

C. Aerosol Generator (Gemini 501)
  Set the generator to represent 4% to 5%/ft. obscuration 

as described in the Gemini 501 Manual. Using the bowl- 
shaped applicator, apply aerosol until unit alarms.

D.  Direct  Heat  Method  (Hair  Dryer  of  1000-1500  watts) 

2151T only

  A hair dryer of 1000-1500 watts should be used to test 

the thermistors. Direct the heat toward either of the two 
thermistors,  holding  the  heat  source  approximately  12 
inches from the detector in order to avoid damaging the 
plastic housing. The detector will reset only after it has 
had sufficient time to cool. Make sure both thermistors 
are tested individually.

Notify the proper authorities that the system is back on line.
Detectors that fail these tests should be cleaned as described 
under  MAINTENANCE  and  retested.  If  the  detectors  still 
fail these tests, they should be returned for repair.

C0145-01

CAUTION

Dust covers are an effective way to limit the entry of dust 
into smoke detector sensing chambers. However, they may 
not completely prevent airborne dust particles from enter-
ing the detector. Therefore, System Sensor recommends the 
removal of detectors before beginning construction or other 
dust producing activity.

Be  sure  to  remove  the  dust  covers  from  any  sensors  that 
were left in place during construction as part of returning 
the system to service.

CAUTION

Smoke  detectors  are  not  to  be  used  with  detector  guards 
unless  the  combination  has  been  evaluated  and  found  
suitable for that purpose.

Summary of Contents for 2151

Page 1: ...s a variety of detector bases available for this smoke detector including 2 wire applications with and without relays and or current limiting resistors 4 wire and 120VAC applications Specifications Size Height 2 0 inches 51 mm installed in B401 Base Diameter 4 1 inches 104 mm installed in B401 Base 6 1 inches 155 mm installed in B110LP Base Weight 3 1 oz 88 g Operating Temperature Range 0 C to 49 ...

Page 2: ...ni 501 Set the generator to represent 4 to 5 ft obscuration as described in the Gemini 501 Manual Using the bowl shaped applicator apply aerosol until unit alarms D Direct Heat Method Hair Dryer of 1000 1500 watts 2151T only A hair dryer of 1000 1500 watts should be used to test the thermistors Direct the heat toward either of the two thermistors holding the heat source approximately 12 inches fro...

Page 3: ...with Step 4 oth erwise skip to Step 7 4 Remove the chamber cover screen assembly by pulling it straight out 5 Use a vacuum cleaner or compressed air to remove dust and debris from the sensing chamber 6 Reinstall the chamber cover screen assembly by slid ing the edge over the sensing chamber Turn until it is firmly in place 7 Replace the cover using the LEDs to align the cover and then gently pushi...

Page 4: ...n Authorization number send defective units Three Year Limited Warranty postage prepaid to System Sensor Repair Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modi fications or...

Reviews: