System Sensor 2112/24R Installation And Maintenance Instructions Download Page 2

D200-83-00

2

I56-1239-01

Figure 2. Surface mounting of 2112/24R and

2112/24TR smoke detector on 3

1

/

2

-inch and 4-inch

octagonal box:

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

;;;;;;;;;;;;;;;;;;;;;;;;

A78-2563-01

Figure 3. 2112/24R and 2112/24TR smoke detector mounting bracket:

A78-2333-04

If the LED stops blinking, the unit should be removed for

maintenance and inspection.

Mounting

Each 2112/24R and 2112/24TR detector is supplied with a

mounting bracket that permits the detector to be mounted:

1. To a single gang box, or

2. Directly to a 3-1/2 inch or 4 inch octagonal box, or

3. To a 4 inch square electrical box by using a plaster ring.

Tamper-resistant Feature

This detector includes a tamper-resistant feature that pre-

vents its removal from the bracket without the use of a

tool. To make the detector tamper-resistant, remove the

smaller tab by breaking it at the scribed line on the tamper

resistant tab on the detector mounting bracket (see Figure

3), then install the detector. To remove the detector from

the bracket once it has been made tamper resistant,  use a

small screwdriver to depress the tamper-resistant tab, lo-

cated in the slot on the mounting bracket, and turn the de-

tector counterclockwise.

Wiring Installation Guidelines

All wiring must be installed in compliance with the Na-

tional Electrical Code, applicable local codes, and any spe-

cial requirements of the local authority having jurisdiction.

Proper wire gauges should be used. The conductors used to

connect smoke detectors to control panels and accessory

devices should be color-coded to reduce the likelihood of

wiring errors. Improper connections can prevent a system

from responding properly in the event of a fire.

The screw terminal block accepts 14 – 22 gauge wire. For

best system performance, all wiring should be installed in

separate grounded conduit. Do not mix fire system wiring

in the same conduit as any other electrical wiring. Twisted

pair may be used to provide additional protection against

electrical interference.

Smoke detectors and alarm system control panels have

specifications for allowable loop resistance. Consult the

control panel specifications for the total loop resistance al-

lowed for the control panel being used before wiring the

detector loops.

Before Installing

Please thoroughly read the System Sensor manual I56-407,

Guide for Proper Use of System Smoke Detectors, which pro-

vides detailed information on detector spacing, placement,

zoning, wiring, and special applications. Copies of this

manual are available at no charge from System Sensor.

NOTICE: This manual shall be left with the owner/user of

this equipment.

IMPORTANT: This detector must be tested and maintained

following NFPA 72 requirements. The detector should be

cleaned at least once a year.

General Description

Models 2112/24R and 2112/24TR are 4-wire photoelectronic

smoke detectors that use a state-of-the-art optical sensing

chamber. The 2112/24TR also provides restorable, 135˚F

fixed-temperature heat detection. The 2112/24TR heat-de-

tection unit is integrated with the photoelectronic sensor.

Installation of this detector is simplified by the use of a

mounting bracket and a plug-in screw terminal block that can

be prewired to the system, allowing the detector to be easily

installed or removed for cleaning. The detector’s sensitivity

can be tested in place using the MOD400R Test Module.

An LED on the detector provides a local visual indication of

the detector’s status. If power is applied to the detector and

it is functioning normally in standby within the listed sensi-

tivity ranges, the status LED blinks every ten seconds.  The

LED also latches on in alarm.

TAMPER SLOT
(DEPRESS TAB TO
REMOVE DETECTOR)

TAMPER RESISTANT TAB
 (CUT OFF SMALL TAB TO
 ACTIVATE TAMPER-RESIST
 FEATURE)

ALIGNMENT
ARROWS