background image

D200-83-00

1

I56-1239-01

2112/24R and 2112/24TR Photoelectronic

Smoke Detectors

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Specifications

Diameter:

5.5 inches (140 mm)

Height (including mounting bracket):

1.7 inches (43 mm)

Weight:

6.8 oz. (190 g)

Operating Temperature Range

Model 2112/24R: 32

°

F to 120

°

F (0

°

C to 49

°

C)

Model 2112/24TR: 32

°

F to 100

°

F (0

°

C to 39

°

C)

Operating Humidity Range:

10% to 93% Relative Humidity, Noncondensing

Latching Alarm:

Reset by momentary power interruption

Heat Sensor (Model 2112/24TR only):

135

°

F Fixed Temperature Electronic Thermistor

Electrical Ratings

System Voltage (nominal):

12 or 24 VDC

Minimum:

10 VDC

Maximum:

35 VDC

Maximum Ripple Voltage:

30% of nom. Voltage (peak to peak)

Standby Current:

50 

µ

A maximum

Alarm Current:

28 mA typical, 35 mA max. at 12V

36 mA typical, 45 mA max. at 24V

Reset Voltage:

0.8 VDC minimum

Reset Time:

0.3 seconds maximum

Start-up Time:

30 seconds maximum (after 60 sec. reset)

EOL Relay:

A77-716B, 12/24 VDC

Alarm Initiation and Auxiliary Relay:

1A @ 30 VAC

Contact Ratings, Resistive  Load:

1A @ 30 VDC

Figure 1. Wiring diagram for the 2112/24R and 2112/24TR detector:

A78-2336-16

OPTIONAL CLASS A WIRING

EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER

EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V

POWER

TO

DETECTORS

UL LISTED

COMPATIBLE

CONTROL

PANEL

INITIATING

LOOP

+

P

W

R

A
U
X

P

W

R

A
U
X

+
+

A
A

NC

C

NO

+
+

A
A

NC

C

NO

ALARM
CONTACT

ALARM
CONTACT

(OPTIONAL)
RELEASING

DEVICE

NC

COMMON

NO

(OPTIONAL)
RELEASING

DEVICE

NC

COMMON

NO

Technical Manuals Online! - http://www.tech-man.com