System Sensor 2012JA Installation And Maintenance Instructions Download Page 2

                                                                                                           2                                                                                                     I56-2012-

007

Figure 2: Recommended smoke alarm protection for single-floor 

residence with more than one sleeping area:

BEDROOM

SMOKE ALARMS FOR

MINIMUM PROTECTION
SMOKE ALARMS FOR

MORE PROTECTION AND 

REQUIRED IN NEW CONSTRUCTION

BEDROOM

BEDROOM

LIVING ROOM

DINING

ROOM

KITCHEN

FAMILY ROOM

NFPA 72, Chapter 2, Section 2-2.1.1.1 states as follows: “Smoke

 

alarms 

shall be installed outside of each separate sleeping area in the immediate 

vicinity of the bedrooms and on each additional story of the family living 

unit, including basements and excluding crawl spaces and unfinished 

attics. In new construction, a smoke-alarm also shall be installed in each 

sleeping room.”

The above NFPA standard is a minimum requirement for smoke

 alarm

installation. 

For better protection, we also require the installation of a 

smoke

 

alarm inside every bedroom in existing construction.

•   Install a minimum of two smoke alarms in any household, no matter 

how small it is.

•   Put a smoke alarm in the hallway outside of every separate bedroom 

area. (See Figure 1.) A minimum of two smoke alarms are required in 

homes with two bedroom areas. (See Figure 2.)

•   Put a smoke alarm on every level of a multi-level residence. (See

 

Figure 3.)

• 

Install basement smoke alarms on the ceiling at the bottom of the 

basement stairwell. (See Figure 3.)

Figure 3: Recommended smoke alarm protection for a multi-level 

residence:

BEDROOM

BEDROOM BEDROOM

LIVING

ROOM

KITCHEN

BASEMENT

GARAGE

SMOKE ALARMS FOR MINIMUM PROTECTION
SMOKE ALARMS FOR MORE PROTECTION AND

REQUIRED IN NEW CONSTRUCTION

  

Install smoke alarms on the ceiling as close to the center of the room 

as possible. If this is not practical, install it on the ceiling no closer 

than 4 inches (10 cm) from any wall or corner. (See Figure 4.)

• 

  If wall-mounting is permitted by local and state codes, and ceiling 

mounting is not practical, install smoke alarms on an inside wall 

between 4 and 6 inches (10 and 15 cm) from the ceiling. (See Figure 

4.)

Figure 4: Recommended smoke alarm mounting locations:

BEST LOCATION

ACCEPTABLE LOCATION

DEAD AIR

SPACE

BEST IN CENTER

OF CEILING

NO CLOSER THAN 4

" (10 cm)

FROM SIDE WALL

MOUNT ON WALL

AT LEAST 4

" (10 cm)

FROM CEILING

NO MORE

THAN 6

" (15 cm)

FROM CEILING

  

Put smoke alarms at both ends of a bedroom hallway if the hallway is 

more than 30 feet (9 meters) long. In addition, large rooms will require 

more than a single unit if the room is over 900 square feet.

 

Rooms or areas that do not have smooth ceilings, or which have 

short, transom-type walls coming down from the ceiling require 

additional smoke alarms.

 

Install second-floor smoke alarms on the ceiling at the top of the first-

to-second floor stairwell. Be sure no door or other obstruction blocks 

the path of smoke to the unit.

 

In rooms with sloped, peaked, or gabled ceilings, install smoke alarms 

3 feet (0.9 meter) measured down on the slant from the highest point 

of the ceiling. See Figure 5.

Figure 5: Recommended smoke alarm location in rooms with sloped, 

gabled or peaked ceilings:

HORIZONTAL

DISTANCE

FROM PEAK

3 FEET

(.9M)

Where Smoke Alarms Should NOT Be Installed

 

In or near areas where combustion particles are normally present 

such as kitchens; in garages where there are particles of combustion 

in vehicle exhausts; near furnaces, hot water heaters, or gas space 

heaters. Install smoke alarms at least 20 feet (6 meters) away from 

kitchens and other areas where combustion particles are normally 

present.

• 

On the ceiling in rooms next to kitchens where there is no transom 

between the kitchen and these rooms. Instead, install the smoke 

alarm on an inside wall, furthest from the kitchen (See Figure 6). Be 

sure not to install smoke alarms within 4" of the ceiling or any corner 

or more than 6" from the ceiling.

Figure 6: Recommended smoke alarm locations to avoid air streams 

with combustion particles:

CORRECT

AIR RETURN

BEDROOM

BATH

BEDROOM

LIVING

ROOM

INCORRECT

KITCHEN

STOVE

AIR INLET

 

In damp or very humid areas, or next to bathrooms with showers. 

The moisture in humid air can enter the sensing chamber as water 

vapor, then cool and condense into droplets that cause a nuisance 

alarm. Install smoke alarms at least 5 feet (1.5 meters) away from 

bathrooms.

• 

In very cold or very hot rooms or areas. Operating temperature of the 

smoke alarm is 40°F to 100°F (4°C to 38°C).

• 

In dusty, dirty, or insect-infested areas. Dust and dirt can build up on 

the unit’s sensing chamber and make it overly sensitive, or can block 

openings to the sensing chamber and keep the unit from sensing 

smoke.

• 

Near fresh air inlets or returns or excessively drafty areas. Air 

conditioners, 

heaters, fans, and fresh air intakes and returns can drive 

smoke away 

from smoke alarms, making the units less effective.

• 

In dead air spaces at the top of a peaked ceiling or wall/ceiling 

intersect. 

Dead air may prevent smoke from reaching a unit. 

• 

Near fluorescent light fixtures. Install smoke alarms at least 10 feet (3 

meters) away from such light fixtures.

Installation Requirements

Warning: Electrical Shock Hazard. 

Turn off power at the main fuse box 

or circuit breaker to the area of unit installation before beginning installation 

procedures. 

 

Mount unit to a 4-inch octagonal junction box only. Mount the 12 Volt 

D.C. power supply to a 4" square junction box 2-1/8" deep only. (If 

necessary, add an extension ring if the selected box does not have 

adequate volume.) The power supply may be mounted remotely from 

the unit.

 

All wiring must be performed by a licensed electrician and installed in 

compliance with the Canadian Electrical Code, applicable local codes, 

and any special requirements of the local authority having jurisdiction.

 

Use only the specified wire gauge. Maximum interconnect bus length 

is 5,000 feet, #14 – 22 AWG cable.

 The smoke

 

alarm includes a tamper-resist feature that, when 

activated, 

requires a tool for smoke

 

alarm removal. The following 

smoke alarm 

installation instructions include how to activate this 

feature instructions 

include how to activate this feature.

                                                                                                          3                                                                                                     I56-2012-

007

Installation Instructions

1.  Turn off power at main service panel.

2.  Using wire connectors, attach either 

black 

wire from power supply to 

black AC

 power wire. Attach other 

black 

wire from power supply to 

white AC

 neutral wire.

3.  Using wire connectors, connect 

red 

and 

gray 

power supply output 

wires to the bus line wires supplying power to the remote smoke 

alarms. (See Figure 7.) Use color-coded bus wires.

4.  Mount power supply to junction box and cover junction box with a 4" 

square box cover, using box mounting screws.

5.  Install a junction box where you plan to install the unit. (See type and 

size for junction box above.)

6.  Install bus line wires from power supply output to junction box. Use 

#14-18 AWG wire only. See Figure 7 to determine maximum power 

bus length for wire size and number of interconnected smoke alarms.

7.  Connect color-coded DC power bus wires to power input screw 

terminals, located on unit back. If smoke alarms will be interconnected 

or the relay used, see following sections for specific installation 

instructions.

 8.  Remove unit from mounting bracket by turning the unit counter-

clockwise and pulling the unit away from the bracket.

9.  Remove small tab on mounting bracket to activate tamper-resist 

feature, if desired. (To release a unit with this feature, push up on 

locking tab with screwdriver while turning unit counterclockwise.)

10.  Install mounting bracket to junction box.

11.  Connect power wires to unit(s) as shown in Figure 7. Be sure to 

tighten each terminal screw to secure wire in place. Tug wire to be 

sure it is connected properly.

12. Attach smoke alarm to mounting bracket by aligning arrows on side 

of 

mounting bracket 1-inch to the right of the nib on the unit. Rotate 

until 

the arrow and nib line up. (See Figure 8).

13.  After installing all smoke alarms, turn on power at the main service 

panel.

14.  Check for the green LED to flash about once every 30 to 40 seconds. 

This means the unit is receiving power. Check all smoke alarms.

Note:

 

If the LED does not flash, power is not getting to the smoke 

alarm. Check wiring. If LED still does not flash, return the 

smoke alarm to the manufacturer for repair.

15.

   

Test each unit in the system. (See “Testing” below for more detailed 

instructions.)

Figure 8:

Figure 7:

INTERCONNECT

SIGRLY  GND  SIGSND

-    +

POWER INPUT

REL

AY

NC        C        NO

      DC POWER SUPPLY

      MAX. 30V DC, 100VA

(-)
(+)

Black

White

120VAC

INTERCONNECT UP TO 

12 SMOKE ALARMS

SIGSND MODE

INTERCONNECT

SIGRLY  GND  SIGSND

-    +

POWER INPUT

REL

AY

NC        C        NO

-    +

POWER INPUT

REL

AY

NC        C        NO

INTERCONNECT

SIGRLY  GND  SIGSND

INTERCONNECT

SIGRLY  GND  SIGSND

-    +

POWER INPUT

REL

AY

NC        C        NO

     DC POWER SUPPLY

      MAX. 30V DC, 100VA

(-)
(+)

Black

White

120VAC

INTERCONNECT UP TO 

12 SMOKE ALARMS

SIGRLY MODE

INTERCONNECT

SIGRLY  GND  SIGSND

-    +

POWER INPUT

REL

AY

NC        C        NO

-    +

POWER INPUT

REL

AY

NC        C        NO

INTERCONNECT

SIGRLY  GND  SIGSND

Maximum power bus length in feet, given number of units (maximum per bus) and wire gauge(AWG)

Supply Voltage = 12VDC

Wire Gauge 1 Unit

2 Units

3 Units

4 Units

5 Units

6 Units

7 Units

8 Units

9 Units

10 Units

11 Units

12 Units

14

13587

6795

4529

3397

2718

2266

1941

1699

1510

1358

1234

1134

16

8505

4254

2835

2126

1701

1419

1216

1064

945

852

772

705

18

5360

2679

1787

1339

1071

894

765

670

595

537

488

443

20

3383

1692

1127

847

677

565

483

422

376

338

308

282

22

2114

1057

705

527

422

352

301

264

236

212

191

175

For 24VDC supply voltage, the maximum power bus length is 4 times as long as 12VDC supply voltage.

Maximum interconnect bus length: 5000 FT, No. 14-22AWG cable

All wiring must conform to local electrical codes.

Remove

Mounting Bracket

Install

W

hen

 I

nstalling

A

lign

 

arrows

 

on

 

mounting

bracket

 1" 

to

 

the

 

right

 

of

the

 

nib

 

on

 

the

 

smoke 

alarm

Rotate

 

until

 

arrow

 

and

nib

 

l

i

ne

 

up  

 

 
 
 

 

 
 
 

 

 
 
 

 

 
 
 

 

 

 

 

 

 

  
 

 

 

 

 

 
 
 
 
 

 

 

 

 

 
 
 
 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reviews: